inletPoleSensorSignedMinimum

PDU2-MIB · .1.3.6.1.4.1.13742.6.3.3.6.1.27

Object

column SNMPv2-SMIInteger32
The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by
inletPoleSensorDecimalDigits. For example, if the value is 1 and
inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
This value determines whether to use the signed or unsigned threshold
and value columns: If the minimum is below zero the sensor can have
negative readings and the signed columns should be used.
This parameter does not apply to sensors without numerical reading.

Context

MIB
PDU2-MIB
OID
.1.3.6.1.4.1.13742.6.3.3.6.1.27
Type
column
Access
readonly
Status
current
Parent
inletPoleSensorConfigurationEntry
Table
inletPoleSensorConfigurationTable
Siblings
21

Syntax

SNMPv2-SMIInteger32
Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647

Related Objects