logOutletSensorSignedMinValue
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.6.4.3.1.9
Object
column
SNMPv2-SMIInteger32
The minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This object does not apply to sensors without numerical reading.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.6.4.3.1.9- Type
- column
- Access
- readonly
- Status
- current
- Parent
- outletSensorLogEntry
- Table
- outletSensorLogTable
- Siblings
- 7
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| logOutletSensorDataAvailable Is data available for this sensor during this measurement period? | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.6.4.3.1.2 |
| logOutletSensorState The most critical sensor state during this measurement period. | column | SensorStateEnumeration | .1.3.6.1.4.1.13742.6.6.4.3.1.3 |
| logOutletSensorAvgValue The average sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.4.3.1.4 |
| logOutletSensorMaxValue The maximum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.4.3.1.5 |
| logOutletSensorMinValue The minimum sensor reading for the log period as an unsigned integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.6.4.3.1.6 |
| logOutletSensorSignedAvgValue The average sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 and… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.6.4.3.1.7 |
| logOutletSensorSignedMaxValue The maximum sensor reading for the log period as a signed integer.
The value of this OID variable should be scaled by