measurementsOutletSensorMinValue
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.5.4.3.1.8
Object
column
SNMPv2-SMIUnsigned32
The minimum value of sensor reading since last reset as an unsigned integer The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSensorDecimalDigits is 2, then actual value is 0.01. This value will wrap around if the scaled sensor reading exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without a numerical reading, or sensors that are not present or are in an unavailable state.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.5.4.3.1.8- Type
- column
- Access
- readonly
- Status
- current
- Parent
- outletSensorMeasurementsEntry
- Table
- outletSensorMeasurementsTable
- Siblings
- 12
Syntax
SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| measurementsOutletSensorMinTimeStamp The timestamp of last change of the minimum value of sensor reading
provided as measurementOutletSensor[Signed]MinValue | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.10 |
| measurementsOutletSensorMaxValue The maximum value of sensor reading since last reset as an unsigned integer
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.11 |
| measurementsOutletSensorSignedMaxValue The maximum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.4.3.1.12 |
| measurementsOutletSensorMaxTimeStamp The timestamp of last change of the maximum value of sensor reading
provided as measurementOutletSensor[Signed]MaxValue | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.13 |
| measurementsOutletSensorMinMaxResetTimeStamp The timestamp of last reset of all minimum and maximum values of sensor reading
including their timestamps, provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp}
… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.14 |
| measurementsOutletSensorIsAvailable The sensor is present. | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.5.4.3.1.2 |
| measurementsOutletSensorState The sensor state. | column | SensorStateEnumeration | .1.3.6.1.4.1.13742.6.5.4.3.1.3 |
| measurementsOutletSensorValue The sensor reading as an unsigned integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 and
outletSensorDecimalDigi… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.4 |
| measurementsOutletSensorTimeStamp The timestamp for reading. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.5.4.3.1.5 |
| measurementsOutletSensorSignedValue The sensor reading as a signed integer.
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is 1 and
outletSensorDecimalDigits … | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.4.3.1.6 |
| measurementsOutletSensorMinMaxValid The minimum and maximum values of sensor reading and their timestamps
provided as measurementsOutletSensor[Signed]{Min|Max}{Value|TimeStamp} are valid | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.5.4.3.1.7 |
| measurementsOutletSensorSignedMinValue The minimum value of sensor reading since last reset as a signed integer
The value of this OID variable should be scaled by
outletSensorDecimalDigits. For example, if the value is… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.5.4.3.1.9 |