transferSwitchTransferToInlet

PDU2-MIB · .1.3.6.1.4.1.13742.6.4.3.1.1.2

Object

column r/w Integer32
Select the active inlet. The written value must be between 1 and the
value of inletCount. If the selected inlet is available it will become
both active and preferred, otherwise an inconsistentValue error will
be returned.
By default the switching operation will fail if the phase difference
between the inlets is too large. In this case the switch can be forced
by writing transferSwitchAlarmOverride as True in the same request.
This variable will always read as 0.