transferSwitchTransferToInlet
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.4.3.1.1.2
Object
column
r/w
Integer32
Select the active inlet. The written value must be between 1 and the value of inletCount. If the selected inlet is available it will become both active and preferred, otherwise an inconsistentValue error will be returned. By default the switching operation will fail if the phase difference between the inlets is too large. In this case the switch can be forced by writing transferSwitchAlarmOverride as True in the same request. This variable will always read as 0.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.4.3.1.1.2- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- transferSwitchControlEntry
- Table
- transferSwitchControlTable
- Siblings
- 3
Syntax
Integer32
Values & Constraints
Object Constraints
range: 0-64
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| transferSwitchActiveInlet The index of the currently active inlet. The value normally ranges
between 1 and the value of inletCount, but can be 0 in case no inlet
is active (e.g. overload alarm). | column | Integer32 | .1.3.6.1.4.1.13742.6.4.3.1.1.1 |
| transferSwitchAlarmOverride Force transfer even if the phase difference between the inlets is too
large.
This may only be written together with transferSwitchTransferToInlet,
otherwise an inconsistentValue e… | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.4.3.1.1.3 |
| transferSwitchLastTransferReason The reason for the most recent transfer | column | TransferSwitchTransferReasonEnumeration | .1.3.6.1.4.1.13742.6.4.3.1.1.4 |