overCurrentProtectorSensorSignedUpperWarningThreshold
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.3.4.4.1.31
Object
The upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01. The value is undefined for sensors whose range exceeds the Integer32 range (-2147483648 .. 2147483647). This parameter does not apply to sensors without numerical reading.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.3.4.4.1.31- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- overCurrentProtectorSensorConfigurationEntry
- Table
- overCurrentProtectorSensorConfigurationTable
- Siblings
- 20
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| overCurrentProtectorSensorTolerance deprecated The tolerance: the maximum difference between measurement and the
actual value. The value of this OID variable should be scaled by
(overCurrentProtectorSensorDecimalDigits + 1). F… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.10 |
| overCurrentProtectorSensorMaximum The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.11 |
| overCurrentProtectorSensorMinimum The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 an… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.12 |
| overCurrentProtectorSensorHysteresis The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.13 |
| overCurrentProtectorSensorStateChangeDelay The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as
it is detected; if it is non-zero, say n, then the assertion
… | column | Unsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.14 |
| overCurrentProtectorSensorLowerCriticalThreshold The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.21 |
| overCurrentProtectorSensorLowerWarningThreshold The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.22 |
| overCurrentProtectorSensorUpperCriticalThreshold The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.23 |
| overCurrentProtectorSensorUpperWarningThreshold The upper warning threshold as an unsigned integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.24 |
| overCurrentProtectorSensorEnabledThresholds A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. | column | Bits | .1.3.6.1.4.1.13742.6.3.4.4.1.25 |
| overCurrentProtectorSensorSignedMaximum The largest possible reading as a signed integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
ov… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.4.4.1.26 |
| overCurrentProtectorSensorSignedMinimum The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
o… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.4.4.1.27 |
| overCurrentProtectorSensorSignedLowerCriticalThreshold The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
ov… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.4.4.1.28 |
| overCurrentProtectorSensorSignedLowerWarningThreshold The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
ove… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.4.4.1.29 |
| overCurrentProtectorSensorSignedUpperCriticalThreshold The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
ov… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.4.4.1.30 |
| overCurrentProtectorSensorLogAvailable Is data logging enabled for this sensor? | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.3.4.4.1.4 |
| overCurrentProtectorSensorUnits The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. | column | SensorUnitsEnumeration | .1.3.6.1.4.1.13742.6.3.4.4.1.6 |
| overCurrentProtectorSensorDecimalDigits The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.7 |
| overCurrentProtectorSensorAccuracy deprecated The accuracy: the maximum relative difference (in percent) between
measurement and the actual value.
This parameter does not apply to sensors without numerical reading. | column | HundredthsOfAPercentage | .1.3.6.1.4.1.13742.6.3.4.4.1.8 |
| overCurrentProtectorSensorResolution The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by
overCurrentProtectorSensorDecimalDigits. For example, if … | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.4.4.1.9 |