inletEnableState
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.3.3.3.1.13
Object
Enable/disable PDU operation for this inlet. When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet switching is no longer allowed. This is only meaningful for multi-inlet units if one inlet is temporarily expected to be powered down. Disabling the inlet of a single-inlet unit is forbidden and any attempt to do so will result in an error.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.3.3.3.1.13- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- inletConfigurationEntry
- Table
- inletConfigurationTable
- Siblings
- 16
Values & Constraints
Type Values
1 | true |
2 | false |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| inletId A unique value for each inlet. Its value ranges between 1 and the
value of inletCount. | column | Integer32 | .1.3.6.1.4.1.13742.6.3.3.3.1.1 |
| inletDeviceCapabilities A bit string indicating which inlet sensors are available. | column | Bits | .1.3.6.1.4.1.13742.6.3.3.3.1.10 |
| inletPoleCapabilities A bit string indicating which inlet pole sensors are available. | column | Bits | .1.3.6.1.4.1.13742.6.3.3.3.1.11 |
| inletPlugDescriptor The inlet plug type as a string. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.12 |
| inletRCMResidualOperatingCurrent obsolete **NOTE:This object is obsolete.
Its functionality was implemented by existing RCM sensor thresholds.
The Residual Operating Current (Threshold) for the RCM State sensor.
For inlet… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.3.1.14 |
| inletIsDC Inlet current type: true for DC, false for AC | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.3.3.3.1.15 |
| inletLinePairCount The number of inlet line pairs. | column | Integer32 | .1.3.6.1.4.1.13742.6.3.3.3.1.16 |
| inletLinePairCapabilities A bit string indicating which inlet line pair sensors are available. | column | Bits | .1.3.6.1.4.1.13742.6.3.3.3.1.17 |
| inletLabel The label on the PDU identifying the inlet. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.2 |
| inletName The user-defined name. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.3 |
| inletPlug deprecated The type of plug/receptacle wired to the inlet.
Note: PlugTypeEnumeration is no longer updated, unlisted plugs will be
reported as plugOTHER. Use inletPlugDescriptor to reliably d… | column | PlugTypeEnumeration | .1.3.6.1.4.1.13742.6.3.3.3.1.4 |
| inletPoleCount The number of poles.
PDU:
2 for 1-phase circuits
3 for 3-phase delta-wired models
4 for 3-phase wye-wired models, pole 4 is neutral
Power Meter:
2 to 5 depending on the po… | column | Integer32 | .1.3.6.1.4.1.13742.6.3.3.3.1.5 |
| inletRatedVoltage The inlet voltage rating. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.6 |
| inletRatedCurrent The inlet current rating. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.7 |
| inletRatedFrequency deprecated The inlet frequency rating.
Deprecated: use pduRatedFrequency for unit nameplate information. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.8 |
| inletRatedVA deprecated The inlet VA (VoltAmps) rating.
Deprecated: use pduRatedVA for unit nameplate information. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.13742.6.3.3.3.1.9 |