inletLinePairSensorUpperWarningThreshold
PDU2-MIB ·
.1.3.6.1.4.1.13742.6.3.3.8.1.24
Object
The upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletLinePairSensorDecimalDigits. For example, if the value is 1 and inletLinePairSensorDecimalDigits is 2, then actual value is 0.01. The value is clamped if the scaled threshold exceeds 4294967295. It is undefined for sensors which can have negative readings. This parameter does not apply to sensors without numerical reading.
Context
- MIB
- PDU2-MIB
- OID
.1.3.6.1.4.1.13742.6.3.3.8.1.24- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- inletLinePairSensorConfigurationEntry
- Table
- inletLinePairSensorConfigurationTable
- Siblings
- 18
Syntax
SNMPv2-SMIUnsigned32
- Source
- SNMPv2-SMIUnsigned32
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| inletLinePairSensorMaximum The largest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletL… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.11 |
| inletLinePairSensorMinimum The smallest possible reading as an unsigned integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inlet… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.12 |
| inletLinePairSensorHysteresis The hysteresis used when crossing a threshold towards the normal state.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the va… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.13 |
| inletLinePairSensorStateChangeDelay The delay measured in samples before a state is asserted.
If the value is zero, then the state is asserted as soon as
it is detected; if it is non-zero, say n, then the assertion
… | column | Unsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.14 |
| inletLinePairSensorLowerCriticalThreshold The lower critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletL… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.21 |
| inletLinePairSensorLowerWarningThreshold The lower warning threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLi… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.22 |
| inletLinePairSensorUpperCriticalThreshold The upper critical threshold as an unsigned integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletL… | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.23 |
| inletLinePairSensorEnabledThresholds A bit string indicating which thresholds are enabled.
This parameter does not apply to sensors without numerical reading. | column | Bits | .1.3.6.1.4.1.13742.6.3.3.8.1.25 |
| inletLinePairSensorSignedMaximum The largest possible reading as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLine… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.26 |
| inletLinePairSensorSignedMinimum The smallest possible reading as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLin… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.27 |
| inletLinePairSensorSignedLowerCriticalThreshold The lower critical threshold as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLine… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.28 |
| inletLinePairSensorSignedLowerWarningThreshold The lower warning threshold as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLineP… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.29 |
| inletLinePairSensorSignedUpperCriticalThreshold The upper critical threshold as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLine… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.30 |
| inletLinePairSensorSignedUpperWarningThreshold The upper warning threshold as a signed integer.
The value of this OID variable should be scaled by
inletLinePairSensorDecimalDigits. For example, if the value is 1 and
inletLineP… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.13742.6.3.3.8.1.31 |
| inletLinePairSensorLogAvailable Is data logging enabled for this sensor? | column | SNMPv2-TCTruthValue | .1.3.6.1.4.1.13742.6.3.3.8.1.4 |
| inletLinePairSensorUnits The unit in which the sensor reading is reported.
This parameter does not apply to sensors without numerical reading. | column | SensorUnitsEnumeration | .1.3.6.1.4.1.13742.6.3.3.8.1.6 |
| inletLinePairSensorDecimalDigits The number of digits displayed to the right of the decimal point.
This parameter does not apply to sensors without numerical reading. | column | SNMPv2-SMIUnsigned32 | .1.3.6.1.4.1.13742.6.3.3.8.1.7 |
| inletLinePairSensorResolution The resolution: the minimum difference between any two measured values
The value of this OID variable should be scaled by