.1.3.6.1.4.1.5040.1.2.4.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.4.1.3.1.1 |
|
wtWebioEA12x12InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.4.1.3.1.2 |
|
wtWebioEA12x12InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.1.3.1.3 |
|
wtWebioEA12x12InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.4.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.4.1.5.1.1 |
|
wtWebioEA12x12OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.1 |
|
wtWebioEA12x12BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.2 |
|
wtWebioEA12x12BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.3 |
|
wtWebioEA12x12BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.4 |
|
wtWebioEA12x12BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.5 |
|
wtWebioEA12x12BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.6 |
|
wtWebioEA12x12BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.7 |
|
wtWebioEA12x12BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.8 |
|
wtWebioEA12x12BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.9 |
|
wtWebioEA12x12BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.10 |
|
wtWebioEA12x12BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.11 |
|
wtWebioEA12x12BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.12 |
|
wtWebioEA12x12BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.13 |
|
wtWebioEA12x12BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.14 |
|
wtWebioEA12x12BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.15 |
|
wtWebioEA12x12BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.16 |
|
wtWebioEA12x12BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.17 |
|
wtWebioEA12x12BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.18 |
|
wtWebioEA12x12BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.19 |
|
wtWebioEA12x12BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Constraints: range: 1-65535Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.20 |
|
wtWebioEA12x12BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.21 |
|
wtWebioEA12x12BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.4.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2:… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.4.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.1 |
|
wtWebioEA12x12AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.2 |
|
wtWebioEA12x12AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.3 |
|
wtWebioEA12x12AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA12x12AlarmInputTrigger are not c… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.4 |
|
wtWebioEA12x12AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.5 |
|
wtWebioEA12x12AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.6 |
|
wtWebioEA12x12AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.7 |
|
wtWebioEA12x12AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.8 |
|
wtWebioEA12x12AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.9 |
|
wtWebioEA12x12AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.10 |
|
wtWebioEA12x12AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.11 |
|
wtWebioEA12x12AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.12 |
|
wtWebioEA12x12AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.13 |
|
wtWebioEA12x12AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.14 |
|
wtWebioEA12x12AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.15 |
|
wtWebioEA12x12AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.16 |
|
wtWebioEA12x12AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.17 |
|
wtWebioEA12x12AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.18 |
|
wtWebioEA12x12AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.19 |
|
wtWebioEA12x12AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.20 |
|
wtWebioEA12x12AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.21 |
|
wtWebioEA12x12AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.22 |
|
wtWebioEA12x12AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.23 |
|
wtWebioEA12x12AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.24 |
|
wtWebioEA12x12AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.25 |
|
wtWebioEA12x12AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.26 |
|
wtWebioEA12x12AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.27 |
|
wtWebioEA12x12AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.28 |
|
wtWebioEA12x12AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.29 |
|
wtWebioEA12x12AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.30 |
|
wtWebioEA12x12AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.31 |
|
wtWebioEA12x12AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.4.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.1.1.1 |
|
wtWebioEA12x12PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.1.1.2 |
|
wtWebioEA12x12PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.3 |
|
wtWebioEA12x12PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.4 |
|
wtWebioEA12x12PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.5 |
|
wtWebioEA12x12PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.4.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x12PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.1 |
|
wtWebioEA12x12PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.2 |
|
wtWebioEA12x12PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.4.3.2.2.1.3 |
|
wtWebioEA12x12PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.4.3.2.2.1.4 |
|
wtWebioEA12x12PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.5 |
|
wtWebioEA12x12PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: Bit 0-3 : inputs 8-11 Bit 4-7 : unused OCTET 4: Bit 0-7 : inputs 0-7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.6 |
|
wtWebioEA12x12PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.7 |
|
wtWebioEA12x12PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.4.3.2.2.1.8 |
|
wtWebioEA12x12PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.4.3.2.2.1.9 |
|
wtWebioEA12x12PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA12x12PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OC… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.4.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.13.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.13.1.3.1.1 |
|
wtWebioEA2x2InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.13.1.3.1.2 |
|
wtWebioEA2x2InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.1.3.1.3 |
|
wtWebioEA2x2InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.13.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2OutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.1.5.1.1 |
|
wtWebioEA2x2OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.1 |
|
wtWebioEA2x2BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.2 |
|
wtWebioEA2x2BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.3 |
|
wtWebioEA2x2BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.4 |
|
wtWebioEA2x2BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.5 |
|
wtWebioEA2x2BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.6 |
|
wtWebioEA2x2BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.7 |
|
wtWebioEA2x2BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.8 |
|
wtWebioEA2x2BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.9 |
|
wtWebioEA2x2BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.10 |
|
wtWebioEA2x2BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.11 |
|
wtWebioEA2x2BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.12 |
|
wtWebioEA2x2BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.13 |
|
wtWebioEA2x2BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.14 |
|
wtWebioEA2x2BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.15 |
|
wtWebioEA2x2BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.16 |
|
wtWebioEA2x2BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.17 |
|
wtWebioEA2x2BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.18 |
|
wtWebioEA2x2BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.19 |
|
wtWebioEA2x2BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Constraints: range: 12-12Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.20 |
|
wtWebioEA2x2BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.21 |
|
wtWebioEA2x2BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.13.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.13.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.1 |
|
wtWebioEA2x2AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.2 |
|
wtWebioEA2x2AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.3 |
|
wtWebioEA2x2AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA2x2AlarmInputTrigger are not con… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.4 |
|
wtWebioEA2x2AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.5 |
|
wtWebioEA2x2AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.6 |
|
wtWebioEA2x2AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.7 |
|
wtWebioEA2x2AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.8 |
|
wtWebioEA2x2AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.9 |
|
wtWebioEA2x2AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.10 |
|
wtWebioEA2x2AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.11 |
|
wtWebioEA2x2AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.12 |
|
wtWebioEA2x2AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.13 |
|
wtWebioEA2x2AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.14 |
|
wtWebioEA2x2AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.15 |
|
wtWebioEA2x2AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.16 |
|
wtWebioEA2x2AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.17 |
|
wtWebioEA2x2AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.18 |
|
wtWebioEA2x2AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.19 |
|
wtWebioEA2x2AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.20 |
|
wtWebioEA2x2AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.21 |
|
wtWebioEA2x2AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.22 |
|
wtWebioEA2x2AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.23 |
|
wtWebioEA2x2AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.24 |
|
wtWebioEA2x2AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.25 |
|
wtWebioEA2x2AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.26 |
|
wtWebioEA2x2AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.27 |
|
wtWebioEA2x2AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.28 |
|
wtWebioEA2x2AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.29 |
|
wtWebioEA2x2AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.30 |
|
wtWebioEA2x2AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.31 |
|
wtWebioEA2x2AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.1.1.1 |
|
wtWebioEA2x2PortInputText
mandatory
Description of the input.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1.1.2 |
|
wtWebioEA2x2PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1.1.3 |
|
wtWebioEA2x2PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1.1.4 |
|
wtWebioEA2x2PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1.1.5 |
|
wtWebioEA2x2PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.13.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.1 |
|
wtWebioEA2x2PortOutputText
mandatory
Description of the output.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.13.3.2.2.1.2 |
|
wtWebioEA2x2PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.13.3.2.2.1.3 |
|
wtWebioEA2x2PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.4 |
|
wtWebioEA2x2PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.5 |
|
wtWebioEA2x2PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.6 |
|
wtWebioEA2x2PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.7 |
|
wtWebioEA2x2PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.13.3.2.2.1.8 |
|
wtWebioEA2x2PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.13.3.2.2.1.9 |
|
wtWebioEA2x2PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA2x2PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OCTE… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.13.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.14.1.3
·
1 row entry
·
4 columns
List of input indices.
Numbers of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.14.1.3.1.1 |
|
wtWebioEA24oemInputCounter
mandatory
Value of the input counter.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.1.3.1.2 |
|
wtWebioEA24oemInputCounterClear
mandatory
Value of the input counter. After reading this counter will be cleared.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.1.3.1.3 |
|
wtWebioEA24oemInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 1-12Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.14.1.5
·
1 row entry
·
2 columns
List of output indices.
Numbers of the outputs.
Indexes
wtWebAlarm6x6AlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemOutputNo
mandatory
Index numbers of the outputs.
|
Integer32 Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.14.1.5.1.1 |
|
wtWebioEA24oemOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.1 |
|
wtWebioEA24oemBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.2 |
|
wtWebioEA24oemBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.3 |
|
wtWebioEA24oemBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.4 |
|
wtWebioEA24oemBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.5 |
|
wtWebioEA24oemBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.6 |
|
wtWebioEA24oemBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.7 |
|
wtWebioEA24oemBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.8 |
|
wtWebioEA24oemBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.9 |
|
wtWebioEA24oemBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.10 |
|
wtWebioEA24oemBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.11 |
|
wtWebioEA24oemBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.12 |
|
wtWebioEA24oemBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.13 |
|
wtWebioEA24oemBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.14 |
|
wtWebioEA24oemBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.15 |
|
wtWebioEA24oemBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.16 |
|
wtWebioEA24oemBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.17 |
|
wtWebioEA24oemBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.18 |
|
wtWebioEA24oemBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.19 |
|
wtWebioEA24oemBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.20 |
|
wtWebioEA24oemBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.21 |
|
wtWebioEA24oemBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.14.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.14.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.14.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.14.3.1.5.3
·
1 row entry
·
25 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.1 |
|
wtWebioEA24oemAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.2 |
|
wtWebioEA24oemAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.3 |
|
wtWebioEA24oemAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA24oemAlarmInputTrigger are not c… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.4 |
|
wtWebioEA24oemAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.5 |
|
wtWebioEA24oemAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.6 |
|
wtWebioEA24oemAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.7 |
|
wtWebioEA24oemAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.8 |
|
wtWebioEA24oemAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.9 |
|
wtWebioEA24oemAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.10 |
|
wtWebioEA24oemAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.11 |
|
wtWebioEA24oemAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.12 |
|
wtWebioEA24oemAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.13 |
|
wtWebioEA24oemAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.14 |
|
wtWebioEA24oemAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.15 |
|
wtWebioEA24oemAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.16 |
|
wtWebioEA24oemAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.17 |
|
wtWebioEA24oemAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.18 |
|
wtWebioEA24oemAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.19 |
|
wtWebioEA24oemAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.20 |
|
wtWebioEA24oemAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.21 |
|
wtWebioEA24oemAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.22 |
|
wtWebioEA24oemAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.23 |
|
wtWebioEA24oemAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.24 |
|
wtWebioEA24oemAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.1.5.3.1.25 |
.1.3.6.1.4.1.5040.1.2.14.3.2.1
·
1 row entry
·
4 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemPortInputName
mandatory
Name of the input.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.14.3.2.1.1.1 |
|
wtWebioEA24oemPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.1.1.2 |
|
wtWebioEA24oemPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.1.1.3 |
|
wtWebioEA24oemPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.3.2.1.1.4 |
.1.3.6.1.4.1.5040.1.2.14.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA24oemPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.1 |
|
wtWebioEA24oemPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.2 |
|
wtWebioEA24oemPortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.3 |
|
wtWebioEA24oemPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.14.3.2.2.1.4 |
|
wtWebioEA24oemPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (wt… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.5 |
|
wtWebioEA24oemPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: Bit 0-7 : inputs 16 - 23 OCTET 3: Bit 0-7 : inputs 8 - 15 OCTET 4: Bit 0-7 : inputs 0 - 7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.6 |
|
wtWebioEA24oemPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.14.3.2.2.1.7 |
|
wtWebioEA24oemPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.8 |
|
wtWebioEA24oemPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.14.3.2.2.1.9 |
|
wtWebioEA24oemPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA24oemPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OC… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.14.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.19.1.3
·
1 row entry
·
3 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.19.1.3.1.1 |
|
wtWebioEA12x6RelInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.19.1.3.1.2 |
|
wtWebioEA12x6RelInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.1.3.1.3 |
.1.3.6.1.4.1.5040.1.2.19.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.1.5.1.1 |
|
wtWebioEA12x6RelOutputState
mandatory
Setting and reading of the states of the outputs, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.1 |
|
wtWebioEA12x6RelBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.2 |
|
wtWebioEA12x6RelBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.3 |
|
wtWebioEA12x6RelBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.4 |
|
wtWebioEA12x6RelBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.5 |
|
wtWebioEA12x6RelBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.6 |
|
wtWebioEA12x6RelBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.7 |
|
wtWebioEA12x6RelBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.8 |
|
wtWebioEA12x6RelBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.9 |
|
wtWebioEA12x6RelBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.10 |
|
wtWebioEA12x6RelBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.11 |
|
wtWebioEA12x6RelBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.12 |
|
wtWebioEA12x6RelBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.13 |
|
wtWebioEA12x6RelBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.14 |
|
wtWebioEA12x6RelBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.15 |
|
wtWebioEA12x6RelBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.16 |
|
wtWebioEA12x6RelBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.17 |
|
wtWebioEA12x6RelBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.18 |
|
wtWebioEA12x6RelBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.19 |
|
wtWebioEA12x6RelBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.20 |
|
wtWebioEA12x6RelBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.21 |
|
wtWebioEA12x6RelBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.19.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each set of octets corresponding to an output. Bi… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.19.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.1 |
|
wtWebioEA12x6RelAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.2 |
|
wtWebioEA12x6RelAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.3 |
|
wtWebioEA12x6RelAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA12x6RelAlarmInputTrigger are not… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.4 |
|
wtWebioEA12x6RelAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.5 |
|
wtWebioEA12x6RelAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.6 |
|
wtWebioEA12x6RelAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.7 |
|
wtWebioEA12x6RelAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.8 |
|
wtWebioEA12x6RelAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.9 |
|
wtWebioEA12x6RelAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.10 |
|
wtWebioEA12x6RelAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.11 |
|
wtWebioEA12x6RelAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.12 |
|
wtWebioEA12x6RelAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.13 |
|
wtWebioEA12x6RelAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.14 |
|
wtWebioEA12x6RelAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.15 |
|
wtWebioEA12x6RelAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.16 |
|
wtWebioEA12x6RelAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.17 |
|
wtWebioEA12x6RelAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.18 |
|
wtWebioEA12x6RelAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.19 |
|
wtWebioEA12x6RelAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.20 |
|
wtWebioEA12x6RelAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.21 |
|
wtWebioEA12x6RelAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.22 |
|
wtWebioEA12x6RelAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.23 |
|
wtWebioEA12x6RelAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.24 |
|
wtWebioEA12x6RelAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.25 |
|
wtWebioEA12x6RelAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.26 |
|
wtWebioEA12x6RelAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.27 |
|
wtWebioEA12x6RelAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.28 |
|
wtWebioEA12x6RelAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.29 |
|
wtWebioEA12x6RelAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.30 |
|
wtWebioEA12x6RelAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.31 |
|
wtWebioEA12x6RelAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.19.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.1.1.1 |
|
wtWebioEA12x6RelPortInputText
mandatory
Description of the input.
|
OctetStringr/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.19.3.2.1.1.2 |
|
wtWebioEA12x6RelPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.1.1.3 |
|
wtWebioEA12x6RelPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.3.2.1.1.4 |
|
wtWebioEA12x6RelPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.19.3.2.1.1.5 |
|
wtWebioEA12x6RelPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Constraints: range: 12-12Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.19.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.1 |
|
wtWebioEA12x6RelPortOutputText
mandatory
Description of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.19.3.2.2.1.2 |
|
wtWebioEA12x6RelPortOutputGroupMode
mandatory
Unused in this device 57634
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.3 |
|
wtWebioEA12x6RelPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.4 |
|
wtWebioEA12x6RelPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.5 |
|
wtWebioEA12x6RelPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: Bit 0-3 : inputs 8-11 Bit 4-7 : unused OCTET 4: Bit 0-7 : inputs 0-7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.6 |
|
wtWebioEA12x6RelPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.7 |
|
wtWebioEA12x6RelPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.8 |
|
wtWebioEA12x6RelPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.19.3.2.2.1.9 |
|
wtWebioEA12x6RelPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA12x6RelPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.19.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.20.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.20.1.3.1.1 |
|
wtWebAlarm6x6InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.20.1.3.1.2 |
|
wtWebAlarm6x6InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.1.3.1.3 |
|
wtWebAlarm6x6InputState
mandatory
States of the inputs, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.20.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.20.1.5.1.1 |
|
wtWebAlarm6x6OutputState
mandatory
States of the outputs, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.20.1.8
·
1 row entry
·
2 columns
List of alarm indices..
Index reference.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6AlarmOutputState
mandatory
State of the alarm, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.1.8.1.1 |
|
wtWebAlarm6x6AlarmTriggerState
mandatory
State of the trigger condition, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.1.8.1.2 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.20.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3
·
1 row entry
·
48 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.1 |
|
wtWebAlarm6x6AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebAlarm6x6AlarmInputTrigger are not co… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.4 |
|
wtWebAlarm6x6AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.5 |
|
wtWebAlarm6x6AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Output Switch Enable Bit 1: Mail Enable Bit 2: SNMP Trap enable Bit 3: UDP enable Bit 4: unused Bit 5: TCP Client ena… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.6 |
|
wtWebAlarm6x6AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.7 |
|
wtWebAlarm6x6AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.8 |
|
wtWebAlarm6x6AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.9 |
|
wtWebAlarm6x6AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.10 |
|
wtWebAlarm6x6AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.11 |
|
wtWebAlarm6x6AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.12 |
|
wtWebAlarm6x6AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.13 |
|
wtWebAlarm6x6AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.14 |
|
wtWebAlarm6x6AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.15 |
|
wtWebAlarm6x6AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.16 |
|
wtWebAlarm6x6AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.17 |
|
wtWebAlarm6x6AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.18 |
|
wtWebAlarm6x6AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.19 |
|
wtWebAlarm6x6AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.20 |
|
wtWebAlarm6x6AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.21 |
|
wtWebAlarm6x6AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.22 |
|
wtWebAlarm6x6AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.23 |
|
wtWebAlarm6x6AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.24 |
|
wtWebAlarm6x6AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.26 |
|
wtWebAlarm6x6AlarmMailReleaseText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.27 |
|
wtWebAlarm6x6AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.28 |
|
wtWebAlarm6x6AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.29 |
|
wtWebAlarm6x6AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.30 |
|
wtWebAlarm6x6AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.31 |
|
wtWebAlarm6x6AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.32 |
|
wtWebAlarm6x6AlarmName
mandatory
Name of the alarm.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.33 |
|
wtWebAlarm6x6AlarmGlobalEnable
mandatory
Binary coded alarm activation:
Die OCTETS werden bitweise interpretiert. Bit 0 entspricht dem LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.34 |
|
wtWebAlarm6x6AlarmCounterClear
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Counter clear on Alarm acknowledge Bit 0… |
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.35 |
|
wtWebAlarm6x6AlarmAckEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Software acknowledge enable Bit 0 : Hard… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.36 |
|
wtWebAlarm6x6AlarmAckPort
mandatory
Number of the input, which clears the alarm (1-6).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.37 |
|
wtWebAlarm6x6AlarmSetPort
mandatory
Number of the output, which will be set by this alarm (1-6).
The configuration of pulse mode and polarity defined in the port output section is used. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.38 |
|
wtWebAlarm6x6AlarmMailTrgClearSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.39 |
|
wtWebAlarm6x6AlarmMailTrgClearText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.40 |
|
wtWebAlarm6x6AlarmSnmpTrapTrgClearText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.41 |
|
wtWebAlarm6x6AlarmUdpTrgClearText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.42 |
|
wtWebAlarm6x6AlarmTcpTrgClearText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.43 |
|
wtWebAlarm6x6AlarmSyslogTrgClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.44 |
|
wtWebAlarm6x6AlarmFtpTrgClearText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.45 |
|
wtWebAlarm6x6AlarmMailTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.46 |
|
wtWebAlarm6x6AlarmSnmpTrapTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.47 |
|
wtWebAlarm6x6AlarmUdpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.48 |
|
wtWebAlarm6x6AlarmTcpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.49 |
|
wtWebAlarm6x6AlarmSyslogTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.50 |
|
wtWebAlarm6x6AlarmFtpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.1.5.3.1.51 |
.1.3.6.1.4.1.5040.1.2.20.3.2.1
·
1 row entry
·
5 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6PortInputName
mandatory
Name of the input.
|
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.20.3.2.1.1.1 |
|
wtWebAlarm6x6PortInputText
mandatory
Description of the input.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.2.1.1.2 |
|
wtWebAlarm6x6PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.3.2.1.1.4 |
|
wtWebAlarm6x6PortInputPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.2.1.1.5 |
|
wtWebAlarm6x6PortInputCounterSet
mandatory
Writing to this variable presets the counter, while reading returns the actual value.
|
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.3.2.1.1.7 |
.1.3.6.1.4.1.5040.1.2.20.3.2.2
·
1 row entry
·
4 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebAlarm6x6PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.2.2.1.1 |
|
wtWebAlarm6x6PortOutputText
mandatory
Description of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.20.3.2.2.1.2 |
|
wtWebAlarm6x6PortPulseDuration
mandatory
Pulse length in 1/100 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.20.3.2.2.1.9 |
|
wtWebAlarm6x6PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebAlarm6x6PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OCT… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.20.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.22.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebCount6InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.22.1.3.1.1 |
|
wtWebCount6InputCounter
mandatory
Value of the input counter.
|
Integer32 Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.22.1.3.1.2 |
|
wtWebCount6InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Constraints: range: 12-12Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.1.3.1.3 |
|
wtWebCount6InputState
mandatory
Tates of the inputs, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.22.1.8
·
1 row entry
·
2 columns
List of Report indices..
Index reference.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebCount6ReportOutputState
mandatory
State of the Report, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.1.8.1.1 |
|
wtWebCount6ReportTriggerState
mandatory
State of the trigger condition, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.1.8.1.2 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.2
·
1 row entry
·
1 columns
List of Report indices.
Numbers of the Reports.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebCount6ReportNo
mandatory
Numbers of the Reports.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.22.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3
·
1 row entry
·
30 columns
List of settings depending on the Report number.
Report parameters of the individual Reports.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebCount6ReportInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.1 |
|
wtWebCount6ReportSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 7 : Timer OFF Bit 6 : Time Window … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.3 |
|
wtWebCount6ReportMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding Report is triggered. Input counters with its mask bit unset in wtWebCount6ReportInputTrigger are not co… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.4 |
|
wtWebCount6ReportInterval
mandatory
Send interval for Report messages.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.5 |
|
wtWebCount6ReportEnable
mandatory
Binary coded Report enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Output Switch Enable Bit 1: Mail Enable Bit 2: SNMP Trap enable Bit 3: UDP enable Bit 4: unused Bit 5: TCP Client en… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.6 |
|
wtWebCount6ReportMailAddr
mandatory
E-Mail address for sending the Report mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.7 |
|
wtWebCount6ReportMailSubject
mandatory
Subject line for Report mail.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.8 |
|
wtWebCount6ReportMailText
mandatory
Report mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.9 |
|
wtWebCount6ReportSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.10 |
|
wtWebCount6ReportSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.11 |
|
wtWebCount6ReportUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.12 |
|
wtWebCount6ReportUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.13 |
|
wtWebCount6ReportUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.14 |
|
wtWebCount6ReportTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.15 |
|
wtWebCount6ReportTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.16 |
|
wtWebCount6ReportTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.17 |
|
wtWebCount6ReportSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.18 |
|
wtWebCount6ReportSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.19 |
|
wtWebCount6ReportSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.20 |
|
wtWebCount6ReportFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.21 |
|
wtWebCount6ReportFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.22 |
|
wtWebCount6ReportFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.23 |
|
wtWebCount6ReportFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.24 |
|
wtWebCount6ReportTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a report, weekday and day of month are interpreted separatley. 1: Minutes Range… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.25 |
|
wtWebCount6ReportName
mandatory
Name of the Report.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.33 |
|
wtWebCount6ReportGlobalEnable
mandatory
Binary coded Report activation:
Die OCTETS werden bitweise interpretiert. Bit 0 entspricht dem LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Report enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.34 |
|
wtWebCount6ReportCounterClear
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Counter clear on Report send |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.35 |
|
wtWebCount6ReportRateOfChange
mandatory
This variable configures a max. counter value within a time slot. If an input counter value
exceeds this max. value, the corresponding Report is triggered. Input counters with its mask bit unset in wtWebCount6ReportInpu… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.52 |
|
wtWebCount6ReportRateOfChangeWindow
mandatory
This variable configures the time slot of wtWebCount6ReportRateOfChange. Input counters with
its mask bit unset in wtWebCount6ReportInputTrigger are not considered. A value of Zero disable the tracing of rate of change. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.53 |
|
wtWebCount6ReportRateOfChangeMode
mandatory
Binary coded options:
Minimum mode: a report will be send if the count of pulses is lower than the given pulse count in wtWebCount6ReportRateOfChange. Maximum mode: a report will be send if the count of pulses is greate… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.1.5.3.1.54 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1
·
1 row entry
·
9 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebCount6PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.2.1.1.1 |
|
wtWebCount6PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.2.1.1.2 |
|
wtWebCount6PortInputMode
mandatory
Binary coded modes:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. Selection for input 0-1: OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Bidirectional counter… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.3 |
|
wtWebCount6PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.4 |
|
wtWebCount6PortInputPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.5 |
|
wtWebCount6PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.6 |
|
wtWebCount6PortInputCounterSet
mandatory
Writing to this variable presets the counter, while reading returns the actual value.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.7 |
|
wtWebCount6PortInputCounterScale
mandatory
Conversion factor for this counter.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.22.3.2.1.1.8 |
|
wtWebCount6PortInputCounterUnit
mandatory
Unit for this counter.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.22.3.2.1.1.9 |
.1.3.6.1.4.1.5040.1.2.24.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6InputNo
mandatory
Index numbers of the inputs.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.24.1.3.1.1 |
|
wtWebioEA6x6InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.24.1.3.1.2 |
|
wtWebioEA6x6InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.1.3.1.3 |
|
wtWebioEA6x6InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.24.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.24.1.5.1.1 |
|
wtWebioEA6x6OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.1 |
|
wtWebioEA6x6BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.2 |
|
wtWebioEA6x6BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.3 |
|
wtWebioEA6x6BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.4 |
|
wtWebioEA6x6BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.5 |
|
wtWebioEA6x6BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.6 |
|
wtWebioEA6x6BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.7 |
|
wtWebioEA6x6BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.8 |
|
wtWebioEA6x6BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 0-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.9 |
|
wtWebioEA6x6BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.10 |
|
wtWebioEA6x6BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.11 |
|
wtWebioEA6x6BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.12 |
|
wtWebioEA6x6BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.13 |
|
wtWebioEA6x6BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.14 |
|
wtWebioEA6x6BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.15 |
|
wtWebioEA6x6BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.16 |
|
wtWebioEA6x6BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.17 |
|
wtWebioEA6x6BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.18 |
|
wtWebioEA6x6BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.19 |
|
wtWebioEA6x6BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Constraints: range: 1-65535Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.20 |
|
wtWebioEA6x6BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.21 |
|
wtWebioEA6x6BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.24.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2:… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.24.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.1 |
|
wtWebioEA6x6AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.2 |
|
wtWebioEA6x6AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.3 |
|
wtWebioEA6x6AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA6x6AlarmInputTrigger are not con… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.4 |
|
wtWebioEA6x6AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.5 |
|
wtWebioEA6x6AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.6 |
|
wtWebioEA6x6AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.7 |
|
wtWebioEA6x6AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.8 |
|
wtWebioEA6x6AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.9 |
|
wtWebioEA6x6AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.10 |
|
wtWebioEA6x6AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.11 |
|
wtWebioEA6x6AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.12 |
|
wtWebioEA6x6AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.13 |
|
wtWebioEA6x6AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.14 |
|
wtWebioEA6x6AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.15 |
|
wtWebioEA6x6AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.16 |
|
wtWebioEA6x6AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.17 |
|
wtWebioEA6x6AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.18 |
|
wtWebioEA6x6AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.19 |
|
wtWebioEA6x6AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.20 |
|
wtWebioEA6x6AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.21 |
|
wtWebioEA6x6AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.22 |
|
wtWebioEA6x6AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.23 |
|
wtWebioEA6x6AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.24 |
|
wtWebioEA6x6AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.25 |
|
wtWebioEA6x6AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.26 |
|
wtWebioEA6x6AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.27 |
|
wtWebioEA6x6AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.28 |
|
wtWebioEA6x6AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.29 |
|
wtWebioEA6x6AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.30 |
|
wtWebioEA6x6AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.31 |
|
wtWebioEA6x6AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.24.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6PortInputName
mandatory
Name of the input.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.1.1.1 |
|
wtWebioEA6x6PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.1.1.2 |
|
wtWebioEA6x6PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.1.1.3 |
|
wtWebioEA6x6PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.3.2.1.1.4 |
|
wtWebioEA6x6PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.1.1.5 |
|
wtWebioEA6x6PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA6x6PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.2.1.1 |
|
wtWebioEA6x6PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.2.1.2 |
|
wtWebioEA6x6PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.3 |
|
wtWebioEA6x6PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.4 |
|
wtWebioEA6x6PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.5 |
|
wtWebioEA6x6PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-5 : inputs 0-5 Bit 6-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.6 |
|
wtWebioEA6x6PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.2.1.7 |
|
wtWebioEA6x6PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.8 |
|
wtWebioEA6x6PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.9 |
|
wtWebioEA6x6PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA6x6PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OCTE… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.24.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.25.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.25.1.3.1.1 |
|
wtWebioEA2x2ERPInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.25.1.3.1.2 |
|
wtWebioEA2x2ERPInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.1.3.1.3 |
|
wtWebioEA2x2ERPInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.25.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPOutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.25.1.5.1.1 |
|
wtWebioEA2x2ERPOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.1 |
|
wtWebioEA2x2ERPBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.2 |
|
wtWebioEA2x2ERPBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.3 |
|
wtWebioEA2x2ERPBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.4 |
|
wtWebioEA2x2ERPBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.5 |
|
wtWebioEA2x2ERPBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.6 |
|
wtWebioEA2x2ERPBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.7 |
|
wtWebioEA2x2ERPBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.8 |
|
wtWebioEA2x2ERPBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.9 |
|
wtWebioEA2x2ERPBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-4 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.10 |
|
wtWebioEA2x2ERPBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.11 |
|
wtWebioEA2x2ERPBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.12 |
|
wtWebioEA2x2ERPBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.13 |
|
wtWebioEA2x2ERPBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.14 |
|
wtWebioEA2x2ERPBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.15 |
|
wtWebioEA2x2ERPBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.16 |
|
wtWebioEA2x2ERPBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.17 |
|
wtWebioEA2x2ERPBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.18 |
|
wtWebioEA2x2ERPBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.19 |
|
wtWebioEA2x2ERPBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.20 |
|
wtWebioEA2x2ERPBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.21 |
|
wtWebioEA2x2ERPBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.25.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.25.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.25.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.25.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.1 |
|
wtWebioEA2x2ERPAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.2 |
|
wtWebioEA2x2ERPAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.3 |
|
wtWebioEA2x2ERPAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA2x2ERPAlarmInputTrigger are not … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.4 |
|
wtWebioEA2x2ERPAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.5 |
|
wtWebioEA2x2ERPAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.6 |
|
wtWebioEA2x2ERPAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.7 |
|
wtWebioEA2x2ERPAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.8 |
|
wtWebioEA2x2ERPAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.9 |
|
wtWebioEA2x2ERPAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.10 |
|
wtWebioEA2x2ERPAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.11 |
|
wtWebioEA2x2ERPAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.12 |
|
wtWebioEA2x2ERPAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.13 |
|
wtWebioEA2x2ERPAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.14 |
|
wtWebioEA2x2ERPAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.15 |
|
wtWebioEA2x2ERPAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.16 |
|
wtWebioEA2x2ERPAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.17 |
|
wtWebioEA2x2ERPAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.18 |
|
wtWebioEA2x2ERPAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.19 |
|
wtWebioEA2x2ERPAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.20 |
|
wtWebioEA2x2ERPAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.21 |
|
wtWebioEA2x2ERPAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.22 |
|
wtWebioEA2x2ERPAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.23 |
|
wtWebioEA2x2ERPAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.24 |
|
wtWebioEA2x2ERPAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.25 |
|
wtWebioEA2x2ERPAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.26 |
|
wtWebioEA2x2ERPAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.27 |
|
wtWebioEA2x2ERPAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.28 |
|
wtWebioEA2x2ERPAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.29 |
|
wtWebioEA2x2ERPAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.30 |
|
wtWebioEA2x2ERPAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.31 |
|
wtWebioEA2x2ERPAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.25.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.1.1.1 |
|
wtWebioEA2x2ERPPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.1.1.2 |
|
wtWebioEA2x2ERPPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.1.1.3 |
|
wtWebioEA2x2ERPPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.3.2.1.1.4 |
|
wtWebioEA2x2ERPPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.1.1.5 |
|
wtWebioEA2x2ERPPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.25.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERPPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.1 |
|
wtWebioEA2x2ERPPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.2 |
|
wtWebioEA2x2ERPPortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.25.3.2.2.1.3 |
|
wtWebioEA2x2ERPPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.25.3.2.2.1.4 |
|
wtWebioEA2x2ERPPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.5 |
|
wtWebioEA2x2ERPPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.6 |
|
wtWebioEA2x2ERPPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.7 |
|
wtWebioEA2x2ERPPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.8 |
|
wtWebioEA2x2ERPPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Constraints: range: 1-1Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.25.3.2.2.1.9 |
|
wtWebioEA2x2ERPPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA2x2ERPPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused O… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.25.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.26.1.3
·
1 row entry
·
3 columns
List of input indices.
Number of the inputs.
Indexes
wtWebioEA2x2-24VBinaryModeNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPInputNo
mandatory
Index numbers of the inputs.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.26.1.3.1.1 |
|
wtWebioEA12x6RelERPInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.26.1.3.1.2 |
|
wtWebioEA12x6RelERPInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.1.3.1.3 |
.1.3.6.1.4.1.5040.1.2.26.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.1.5.1.1 |
|
wtWebioEA12x6RelERPOutputState
mandatory
Setting and reading of the states of the outputs, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.1 |
|
wtWebioEA12x6RelERPBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.2 |
|
wtWebioEA12x6RelERPBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.3 |
|
wtWebioEA12x6RelERPBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.4 |
|
wtWebioEA12x6RelERPBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.5 |
|
wtWebioEA12x6RelERPBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.6 |
|
wtWebioEA12x6RelERPBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.7 |
|
wtWebioEA12x6RelERPBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.8 |
|
wtWebioEA12x6RelERPBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.9 |
|
wtWebioEA12x6RelERPBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.10 |
|
wtWebioEA12x6RelERPBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.11 |
|
wtWebioEA12x6RelERPBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.12 |
|
wtWebioEA12x6RelERPBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.13 |
|
wtWebioEA12x6RelERPBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.14 |
|
wtWebioEA12x6RelERPBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.15 |
|
wtWebioEA12x6RelERPBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.16 |
|
wtWebioEA12x6RelERPBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.17 |
|
wtWebioEA12x6RelERPBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.18 |
|
wtWebioEA12x6RelERPBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.19 |
|
wtWebioEA12x6RelERPBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.20 |
|
wtWebioEA12x6RelERPBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.21 |
|
wtWebioEA12x6RelERPBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.26.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.26.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each set of octets corresponding to an output. Bi… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.26.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.1 |
|
wtWebioEA12x6RelERPAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.2 |
|
wtWebioEA12x6RelERPAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.3 |
|
wtWebioEA12x6RelERPAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA12x6RelERPAlarmInputTrigger are … |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.4 |
|
wtWebioEA12x6RelERPAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.5 |
|
wtWebioEA12x6RelERPAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.6 |
|
wtWebioEA12x6RelERPAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.7 |
|
wtWebioEA12x6RelERPAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.8 |
|
wtWebioEA12x6RelERPAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.9 |
|
wtWebioEA12x6RelERPAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.10 |
|
wtWebioEA12x6RelERPAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.11 |
|
wtWebioEA12x6RelERPAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.12 |
|
wtWebioEA12x6RelERPAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.13 |
|
wtWebioEA12x6RelERPAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.14 |
|
wtWebioEA12x6RelERPAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.15 |
|
wtWebioEA12x6RelERPAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.16 |
|
wtWebioEA12x6RelERPAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.17 |
|
wtWebioEA12x6RelERPAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.18 |
|
wtWebioEA12x6RelERPAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.19 |
|
wtWebioEA12x6RelERPAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.20 |
|
wtWebioEA12x6RelERPAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.21 |
|
wtWebioEA12x6RelERPAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.22 |
|
wtWebioEA12x6RelERPAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.23 |
|
wtWebioEA12x6RelERPAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.24 |
|
wtWebioEA12x6RelERPAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.25 |
|
wtWebioEA12x6RelERPAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.26 |
|
wtWebioEA12x6RelERPAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.27 |
|
wtWebioEA12x6RelERPAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.28 |
|
wtWebioEA12x6RelERPAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.29 |
|
wtWebioEA12x6RelERPAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.30 |
|
wtWebioEA12x6RelERPAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.31 |
|
wtWebioEA12x6RelERPAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.26.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.1.1.1 |
|
wtWebioEA12x6RelERPPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.1.1.2 |
|
wtWebioEA12x6RelERPPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.1.1.3 |
|
wtWebioEA12x6RelERPPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.3.2.1.1.4 |
|
wtWebioEA12x6RelERPPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.2.1.1.5 |
|
wtWebioEA12x6RelERPPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA12x6RelERPPortOutputName
mandatory
Name of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2.1.1 |
|
wtWebioEA12x6RelERPPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.2.1.2 |
|
wtWebioEA12x6RelERPPortOutputGroupMode
mandatory
Unused in this device 57634
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.2.1.3 |
|
wtWebioEA12x6RelERPPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2.1.4 |
|
wtWebioEA12x6RelERPPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2.1.5 |
|
wtWebioEA12x6RelERPPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: Bit 0-3 : inputs 8-11 Bit 4-7 : unused OCTET 4: Bit 0-7 : inputs 0-7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.2.1.6 |
|
wtWebioEA12x6RelERPPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.2.1.7 |
|
wtWebioEA12x6RelERPPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.26.3.2.2.1.8 |
|
wtWebioEA12x6RelERPPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2.1.9 |
|
wtWebioEA12x6RelERPPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA12x6RelERPPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unus… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.26.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.27.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.27.1.3.1.1 |
|
wtIpWatcherInputCounter
mandatory
Value of the input counter.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.27.1.3.1.2 |
|
wtIpWatcherInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.1.3.1.3 |
|
wtIpWatcherInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.27.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.1.5.1.1 |
|
wtIpWatcherOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.27.1.8
·
1 row entry
·
2 columns
List of alarm indices..
Index reference.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherAlarmOutputState
mandatory
State of the alarm, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.1.8.1.1 |
|
wtIpWatcherAlarmTriggerState
mandatory
State of the trigger condition, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.1.8.1.2 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.2
·
1 row entry
·
1 columns
Table of inices.
Table entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherIpListNo
mandatory
List number of this entry.
|
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.2.1.1 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3
·
1 row entry
·
5 columns
List of ip addresses.
List entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherIpListName
mandatory
Name or IP address.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3.1.1 |
|
wtIpWatcherIpListPort
mandatory
Port number, zero in the case of broadcast or Ping.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3.1.2 |
|
wtIpWatcherIpListService
mandatory
Binary coded scan mode, only one mode can be selected at a particular time:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Ping enable Bit 1-7: unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3.1.3 |
|
wtIpWatcherIpListEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: enabled in Alarm 1 Bit 1: enabled in Alarm 2 Bit 2: enabled in Alarm 3 Bit 3: enabled in Alarm 4 Bit 4-7: unused |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3.1.4 |
|
wtIpWatcherIpListAlias
mandatory
Alias Name
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.3.11.3.1.5 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3
·
1 row entry
·
49 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.5 |
|
wtIpWatcherAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.6 |
|
wtIpWatcherAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.7 |
|
wtIpWatcherAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.8 |
|
wtIpWatcherAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 1-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.9 |
|
wtIpWatcherAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.10 |
|
wtIpWatcherAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.11 |
|
wtIpWatcherAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.12 |
|
wtIpWatcherAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.13 |
|
wtIpWatcherAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.14 |
|
wtIpWatcherAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.15 |
|
wtIpWatcherAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.16 |
|
wtIpWatcherAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.17 |
|
wtIpWatcherAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.18 |
|
wtIpWatcherAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.19 |
|
wtIpWatcherAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.20 |
|
wtIpWatcherAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.21 |
|
wtIpWatcherAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.22 |
|
wtIpWatcherAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.23 |
|
wtIpWatcherAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.24 |
|
wtIpWatcherAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.25 |
|
wtIpWatcherAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.26 |
|
wtIpWatcherAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.27 |
|
wtIpWatcherAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.28 |
|
wtIpWatcherAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.29 |
|
wtIpWatcherAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.30 |
|
wtIpWatcherAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.31 |
|
wtIpWatcherAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.32 |
|
wtIpWatcherAlarmName
mandatory
Name of the alarm.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.33 |
|
wtIpWatcherAlarmGlobalEnable
mandatory
Binary coded alarm activation:
Die OCTETS werden bitweise interpretiert. Bit 0 entspricht dem LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.34 |
|
wtIpWatcherAlarmCounterClear
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Counter clear on Alarm acknowledge Bit 0… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.35 |
|
wtIpWatcherAlarmAckEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Software acknowledge enable Bit 0 : Hard… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.36 |
|
wtIpWatcherAlarmAckPort
mandatory
Number of the input, which clears the alarm (1-6).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.37 |
|
wtIpWatcherAlarmSetPort
mandatory
Number of the output, which will be set by this alarm (1-6).
The configuration of pulse mode and polarity defined in the port output section is used. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.38 |
|
wtIpWatcherAlarmMailTrgClearSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.39 |
|
wtIpWatcherAlarmMailTrgClearText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.40 |
|
wtIpWatcherAlarmSnmpTrapTrgClearText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.41 |
|
wtIpWatcherAlarmUdpTrgClearText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.42 |
|
wtIpWatcherAlarmTcpTrgClearText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.43 |
|
wtIpWatcherAlarmSyslogTrgClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.44 |
|
wtIpWatcherAlarmFtpTrgClearText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.45 |
|
wtIpWatcherAlarmMailTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.46 |
|
wtIpWatcherAlarmSnmpTrapTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.47 |
|
wtIpWatcherAlarmUdpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.48 |
|
wtIpWatcherAlarmTcpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.49 |
|
wtIpWatcherAlarmSyslogTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.50 |
|
wtIpWatcherAlarmFtpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.51 |
|
wtIpWatcherAlarmTriggerCount
mandatory
Alarm will be send if the trigger condition occours TriggerCount times.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.52 |
|
wtIpWatcherAlarmPollingRate
mandatory
Time in seconds.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.1.5.3.1.53 |
.1.3.6.1.4.1.5040.1.2.27.3.2.1
·
1 row entry
·
3 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.2.1.1.1 |
|
wtIpWatcherPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.2.1.1.2 |
|
wtIpWatcherPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.2.1.1.4 |
.1.3.6.1.4.1.5040.1.2.27.3.2.2
·
1 row entry
·
4 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcherPortOutputName
mandatory
Name of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.27.3.2.2.1.1 |
|
wtIpWatcherPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.2.2.1.2 |
|
wtIpWatcherPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.27.3.2.2.1.9 |
|
wtIpWatcherPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtIpWatcherPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused OCTET… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.27.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.30.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VInputNo
mandatory
Index numbers of the inputs.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.30.1.3.1.1 |
|
wtWebioEA2x2-24VInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.30.1.3.1.2 |
|
wtWebioEA2x2-24VInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.1.3.1.3 |
|
wtWebioEA2x2-24VInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.30.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VOutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.30.1.5.1.1 |
|
wtWebioEA2x2-24VOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
wtIpWatcher-24VIpListNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w Constraints: range: 1-999 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.1 |
|
wtWebioEA2x2-24VBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.2 |
|
wtWebioEA2x2-24VBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.3 |
|
wtWebioEA2x2-24VBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.4 |
|
wtWebioEA2x2-24VBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.5 |
|
wtWebioEA2x2-24VBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.6 |
|
wtWebioEA2x2-24VBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.7 |
|
wtWebioEA2x2-24VBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.8 |
|
wtWebioEA2x2-24VBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.9 |
|
wtWebioEA2x2-24VBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.10 |
|
wtWebioEA2x2-24VBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 1-4 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.11 |
|
wtWebioEA2x2-24VBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.12 |
|
wtWebioEA2x2-24VBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.13 |
|
wtWebioEA2x2-24VBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.14 |
|
wtWebioEA2x2-24VBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.15 |
|
wtWebioEA2x2-24VBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.16 |
|
wtWebioEA2x2-24VBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.17 |
|
wtWebioEA2x2-24VBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.18 |
|
wtWebioEA2x2-24VBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.19 |
|
wtWebioEA2x2-24VBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.20 |
|
wtWebioEA2x2-24VBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.21 |
|
wtWebioEA2x2-24VBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.30.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.30.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.30.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.30.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.30.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.30.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.1 |
|
wtWebioEA2x2-24VAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.2 |
|
wtWebioEA2x2-24VAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.3 |
|
wtWebioEA2x2-24VAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA2x2-24VAlarmInputTrigger are not… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.4 |
|
wtWebioEA2x2-24VAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.5 |
|
wtWebioEA2x2-24VAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.6 |
|
wtWebioEA2x2-24VAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.7 |
|
wtWebioEA2x2-24VAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.8 |
|
wtWebioEA2x2-24VAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.9 |
|
wtWebioEA2x2-24VAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.10 |
|
wtWebioEA2x2-24VAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.11 |
|
wtWebioEA2x2-24VAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.12 |
|
wtWebioEA2x2-24VAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.13 |
|
wtWebioEA2x2-24VAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.14 |
|
wtWebioEA2x2-24VAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.15 |
|
wtWebioEA2x2-24VAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.16 |
|
wtWebioEA2x2-24VAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.17 |
|
wtWebioEA2x2-24VAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.18 |
|
wtWebioEA2x2-24VAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.19 |
|
wtWebioEA2x2-24VAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.20 |
|
wtWebioEA2x2-24VAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.21 |
|
wtWebioEA2x2-24VAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.22 |
|
wtWebioEA2x2-24VAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.23 |
|
wtWebioEA2x2-24VAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.24 |
|
wtWebioEA2x2-24VAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.25 |
|
wtWebioEA2x2-24VAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.26 |
|
wtWebioEA2x2-24VAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.27 |
|
wtWebioEA2x2-24VAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.28 |
|
wtWebioEA2x2-24VAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.29 |
|
wtWebioEA2x2-24VAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.30 |
|
wtWebioEA2x2-24VAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.31 |
|
wtWebioEA2x2-24VAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.30.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
wtIpWatcher-24VInputNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.1.1.1 |
|
wtWebioEA2x2-24VPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.1.1.2 |
|
wtWebioEA2x2-24VPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.1.1.3 |
|
wtWebioEA2x2-24VPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.3.2.1.1.4 |
|
wtWebioEA2x2-24VPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.1.1.5 |
|
wtWebioEA2x2-24VPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.30.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2-24VPortOutputName
mandatory
Name of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.30.3.2.2.1.1 |
|
wtWebioEA2x2-24VPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.2 |
|
wtWebioEA2x2-24VPortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.3 |
|
wtWebioEA2x2-24VPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.30.3.2.2.1.4 |
|
wtWebioEA2x2-24VPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.5 |
|
wtWebioEA2x2-24VPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.6 |
|
wtWebioEA2x2-24VPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.7 |
|
wtWebioEA2x2-24VPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.30.3.2.2.1.8 |
|
wtWebioEA2x2-24VPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.30.3.2.2.1.9 |
|
wtWebioEA2x2-24VPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA2x2-24VPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.30.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.31.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.31.1.3.1.1 |
|
wtWebioEA2x2ERP-24VInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.31.1.3.1.2 |
|
wtWebioEA2x2ERP-24VInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.1.3.1.3 |
|
wtWebioEA2x2ERP-24VInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 1-2Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.31.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
wtTrapReceiver2x2ButtonNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 1-8 |
.1.3.6.1.4.1.5040.1.2.31.1.5.1.1 |
|
wtWebioEA2x2ERP-24VOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3
·
1 row entry
·
22 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.1 |
|
wtWebioEA2x2ERP-24VBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.2 |
|
wtWebioEA2x2ERP-24VBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.3 |
|
wtWebioEA2x2ERP-24VBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.4 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.5 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.6 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.7 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.8 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.9 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.10 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.11 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.12 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.13 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.14 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.15 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.16 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.17 |
|
wtWebioEA2x2ERP-24VBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.18 |
|
wtWebioEA2x2ERP-24VBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.19 |
|
wtWebioEA2x2ERP-24VBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.20 |
|
wtWebioEA2x2ERP-24VBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.21 |
|
wtWebioEA2x2ERP-24VBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.3.6.3.1.22 |
.1.3.6.1.4.1.5040.1.2.31.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.31.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.31.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.31.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.31.3.1.5.3
·
1 row entry
·
32 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.1 |
|
wtWebioEA2x2ERP-24VAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.2 |
|
wtWebioEA2x2ERP-24VAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.3 |
|
wtWebioEA2x2ERP-24VAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebioEA2x2ERP-24VAlarmInputTrigger are … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.4 |
|
wtWebioEA2x2ERP-24VAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.5 |
|
wtWebioEA2x2ERP-24VAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.6 |
|
wtWebioEA2x2ERP-24VAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.7 |
|
wtWebioEA2x2ERP-24VAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.8 |
|
wtWebioEA2x2ERP-24VAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.9 |
|
wtWebioEA2x2ERP-24VAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.10 |
|
wtWebioEA2x2ERP-24VAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.11 |
|
wtWebioEA2x2ERP-24VAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.12 |
|
wtWebioEA2x2ERP-24VAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.13 |
|
wtWebioEA2x2ERP-24VAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.14 |
|
wtWebioEA2x2ERP-24VAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.15 |
|
wtWebioEA2x2ERP-24VAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.16 |
|
wtWebioEA2x2ERP-24VAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.17 |
|
wtWebioEA2x2ERP-24VAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.18 |
|
wtWebioEA2x2ERP-24VAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.19 |
|
wtWebioEA2x2ERP-24VAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.20 |
|
wtWebioEA2x2ERP-24VAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.21 |
|
wtWebioEA2x2ERP-24VAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.22 |
|
wtWebioEA2x2ERP-24VAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.23 |
|
wtWebioEA2x2ERP-24VAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.24 |
|
wtWebioEA2x2ERP-24VAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.25 |
|
wtWebioEA2x2ERP-24VAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.26 |
|
wtWebioEA2x2ERP-24VAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.27 |
|
wtWebioEA2x2ERP-24VAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.28 |
|
wtWebioEA2x2ERP-24VAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.29 |
|
wtWebioEA2x2ERP-24VAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.30 |
|
wtWebioEA2x2ERP-24VAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.31 |
|
wtWebioEA2x2ERP-24VAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.31.3.1.5.3.1.32 |
.1.3.6.1.4.1.5040.1.2.31.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
wtWebio577xxEA1x1InputNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VPortInputName
mandatory
Name of the input.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.31.3.2.1.1.1 |
|
wtWebioEA2x2ERP-24VPortInputText
mandatory
Description of the input.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.31.3.2.1.1.2 |
|
wtWebioEA2x2ERP-24VPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.1.1.3 |
|
wtWebioEA2x2ERP-24VPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.3.2.1.1.4 |
|
wtWebioEA2x2ERP-24VPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.1.1.5 |
|
wtWebioEA2x2ERP-24VPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebioEA2x2ERP-24VPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.2.1.1 |
|
wtWebioEA2x2ERP-24VPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.2.1.2 |
|
wtWebioEA2x2ERP-24VPortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.3 |
|
wtWebioEA2x2ERP-24VPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.2.1.4 |
|
wtWebioEA2x2ERP-24VPortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.31.3.2.2.1.5 |
|
wtWebioEA2x2ERP-24VPortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.6 |
|
wtWebioEA2x2ERP-24VPortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.7 |
|
wtWebioEA2x2ERP-24VPortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.8 |
|
wtWebioEA2x2ERP-24VPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.9 |
|
wtWebioEA2x2ERP-24VPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebioEA2x2ERP-24VPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unus… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.31.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.32.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.32.1.3.1.1 |
|
wtIpWatcher-24VInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.32.1.3.1.2 |
|
wtIpWatcher-24VInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.1.3.1.3 |
|
wtIpWatcher-24VInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 0-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.32.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.1.5.1.1 |
|
wtIpWatcher-24VOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.32.1.8
·
1 row entry
·
2 columns
List of alarm indices..
Index reference.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VAlarmOutputState
mandatory
State of the alarm, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.1.8.1.1 |
|
wtIpWatcher-24VAlarmTriggerState
mandatory
State of the trigger condition, 0-OFF, 1-ON.
|
Integer32 Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.1.8.1.2 |
.1.3.6.1.4.1.5040.1.2.32.3.1.3.11.2
·
1 row entry
·
1 columns
Table of inices.
Table entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VIpListNo
mandatory
List number of this entry.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.3.11.2.1.1 |
.1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3
·
1 row entry
·
5 columns
List of ip addresses.
List entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VIpListName
mandatory
Name or IP address.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3.1.1 |
|
wtIpWatcher-24VIpListPort
mandatory
Port number, zero in the case of broadcast or Ping.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3.1.2 |
|
wtIpWatcher-24VIpListService
mandatory
Binary coded scan mode, only one mode can be selected at a particular time:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Ping enable Bit 1-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3.1.3 |
|
wtIpWatcher-24VIpListEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: enabled in Alarm 1 Bit 1: enabled in Alarm 2 Bit 2: enabled in Alarm 3 Bit 3: enabled in Alarm 4 Bit 4-7: unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3.1.4 |
|
wtIpWatcher-24VIpListAlias
mandatory
Alias Name
|
OctetStringr/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.32.3.1.3.11.3.1.5 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
wtWebio577xxEA1x1AlarmNo
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3
·
1 row entry
·
49 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.5 |
|
wtIpWatcher-24VAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.6 |
|
wtIpWatcher-24VAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.7 |
|
wtIpWatcher-24VAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.8 |
|
wtIpWatcher-24VAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.9 |
|
wtIpWatcher-24VAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.10 |
|
wtIpWatcher-24VAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.11 |
|
wtIpWatcher-24VAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.12 |
|
wtIpWatcher-24VAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.13 |
|
wtIpWatcher-24VAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.14 |
|
wtIpWatcher-24VAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.15 |
|
wtIpWatcher-24VAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.16 |
|
wtIpWatcher-24VAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.17 |
|
wtIpWatcher-24VAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.18 |
|
wtIpWatcher-24VAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.19 |
|
wtIpWatcher-24VAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.20 |
|
wtIpWatcher-24VAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.21 |
|
wtIpWatcher-24VAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.22 |
|
wtIpWatcher-24VAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.23 |
|
wtIpWatcher-24VAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.24 |
|
wtIpWatcher-24VAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.25 |
|
wtIpWatcher-24VAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.26 |
|
wtIpWatcher-24VAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.27 |
|
wtIpWatcher-24VAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.28 |
|
wtIpWatcher-24VAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.29 |
|
wtIpWatcher-24VAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.30 |
|
wtIpWatcher-24VAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.31 |
|
wtIpWatcher-24VAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.32 |
|
wtIpWatcher-24VAlarmName
mandatory
Name of the alarm.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.33 |
|
wtIpWatcher-24VAlarmGlobalEnable
mandatory
Binary coded alarm activation:
Die OCTETS werden bitweise interpretiert. Bit 0 entspricht dem LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.34 |
|
wtIpWatcher-24VAlarmCounterClear
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Counter clear on Alarm acknowledge Bit 0… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.35 |
|
wtIpWatcher-24VAlarmAckEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : Software acknowledge enable Bit 0 : Hard… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.36 |
|
wtIpWatcher-24VAlarmAckPort
mandatory
Number of the input, which clears the alarm (1-6).
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.37 |
|
wtIpWatcher-24VAlarmSetPort
mandatory
Number of the output, which will be set by this alarm (1-6).
The configuration of pulse mode and polarity defined in the port output section is used. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.38 |
|
wtIpWatcher-24VAlarmMailTrgClearSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.39 |
|
wtIpWatcher-24VAlarmMailTrgClearText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.40 |
|
wtIpWatcher-24VAlarmSnmpTrapTrgClearText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.41 |
|
wtIpWatcher-24VAlarmUdpTrgClearText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.42 |
|
wtIpWatcher-24VAlarmTcpTrgClearText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.43 |
|
wtIpWatcher-24VAlarmSyslogTrgClearText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.44 |
|
wtIpWatcher-24VAlarmFtpTrgClearText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.45 |
|
wtIpWatcher-24VAlarmMailTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.46 |
|
wtIpWatcher-24VAlarmSnmpTrapTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.47 |
|
wtIpWatcher-24VAlarmUdpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.48 |
|
wtIpWatcher-24VAlarmTcpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.49 |
|
wtIpWatcher-24VAlarmSyslogTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.50 |
|
wtIpWatcher-24VAlarmFtpTrapTxEnable
mandatory
Binary coded options:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Alarm OFF message enable Bit 2 : Trigger… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.51 |
|
wtIpWatcher-24VAlarmTriggerCount
mandatory
Alarm will be send if the trigger condition occours TriggerCount times.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.52 |
|
wtIpWatcher-24VAlarmPollingRate
mandatory
Time in seconds.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.1.5.3.1.53 |
.1.3.6.1.4.1.5040.1.2.32.3.2.1
·
1 row entry
·
3 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.2.1.1.1 |
|
wtIpWatcher-24VPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.2.1.1.2 |
|
wtIpWatcher-24VPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.2.1.1.4 |
.1.3.6.1.4.1.5040.1.2.32.3.2.2
·
1 row entry
·
4 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtIpWatcher-24VPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.2.2.1.1 |
|
wtIpWatcher-24VPortOutputText
mandatory
Description of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.32.3.2.2.1.2 |
|
wtIpWatcher-24VPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.32.3.2.2.1.9 |
|
wtIpWatcher-24VPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtIpWatcher-24VPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused O… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.32.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.33.1.3
·
1 row entry
·
2 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.33.1.3.1.1 |
|
wtTrapReceiver2x2InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.33.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2OutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.1.5.1.1 |
|
wtTrapReceiver2x2OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.33.1.8
·
1 row entry
·
2 columns
List of alarm indices..
Index reference.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2ActionOutputState
mandatory
State of the alarm, 0-OFF, 1-ON.
|
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.1.8.1.1 |
|
wtTrapReceiver2x2ActionTriggerState
mandatory
State of the trigger condition, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.1.8.1.2 |
.1.3.6.1.4.1.5040.1.2.33.1.9
·
1 row entry
·
1 columns
List of system timer.
Number of the system timer.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2SystemTimerNo
mandatory
Index number of the system timer.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.33.1.9.1.1 |
.1.3.6.1.4.1.5040.1.2.33.1.10
·
1 row entry
·
1 columns
List of buttons.
Number of the button.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2ButtonNo
mandatory
Index numder of the button.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.33.1.10.1.1 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2ActionNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.33.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3
·
1 row entry
·
27 columns
List of settings depending on the alarm number.
Action parameters of the individual alarms.
Indexes
wtWebio577xxEA12x12BinaryModeNo
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2ActionInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The four OCTETS contain the mask whic… |
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.1 |
|
wtTrapReceiver2x2ActionInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.5 |
|
wtTrapReceiver2x2ActionEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: UDP enable Bit 3: Send inputs to pending TCP connections Bit 4: TCP Client e… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.6 |
|
wtTrapReceiver2x2ActionMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.7 |
|
wtTrapReceiver2x2ActionMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.8 |
|
wtTrapReceiver2x2ActionMailText
mandatory
Action mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.9 |
|
wtTrapReceiver2x2ActionSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.10 |
|
wtTrapReceiver2x2ActionSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.11 |
|
wtTrapReceiver2x2ActionUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.12 |
|
wtTrapReceiver2x2ActionUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.13 |
|
wtTrapReceiver2x2ActionUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.14 |
|
wtTrapReceiver2x2ActionTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.15 |
|
wtTrapReceiver2x2ActionTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.16 |
|
wtTrapReceiver2x2ActionTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.17 |
|
wtTrapReceiver2x2ActionSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.18 |
|
wtTrapReceiver2x2ActionSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.19 |
|
wtTrapReceiver2x2ActionSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.20 |
|
wtTrapReceiver2x2ActionFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.21 |
|
wtTrapReceiver2x2ActionFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.22 |
|
wtTrapReceiver2x2ActionFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.23 |
|
wtTrapReceiver2x2ActionFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.24 |
|
wtTrapReceiver2x2ActionTimerCron
mandatory
This entry contains 10 space or tab seperated text fields defining a time window for sending
time triggered messages. 2 CRON time for start time and stop time are defined as follows: Start time: field 1: Minutes Range 0… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.25 |
|
wtTrapReceiver2x2ActionName
mandatory
Name of the alarm.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.33 |
|
wtTrapReceiver2x2ActionGlobalEnable
mandatory
Binary coded alarm activation:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bi… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.34 |
|
wtTrapReceiver2x2ActionSystemTimerTrigger
mandatory
Binary coded system timer activation:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OC… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.55 |
|
wtTrapReceiver2x2ActionSystemButtonTrigger
mandatory
Binary coded button activation:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4:… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.56 |
|
wtTrapReceiver2x2ActionOutputAction
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determines… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.57 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.2
·
1 row entry
·
1 columns
Table of inices.
Table entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2WatchListNo
mandatory
List number of this entry.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.33.3.1.6.1.2.1.1 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3
·
1 row entry
·
9 columns
List of ip addresses.
List entry.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2WatchListName
mandatory
Name or IP address.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.1 |
|
wtTrapReceiver2x2WatchListPort
mandatory
Port number, zero in the case of broadcast or Ping.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.2 |
|
wtTrapReceiver2x2WatchListService
mandatory
Binary coded scan mode, only one mode can be selected at a particular time:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: unused Bit 1: unused Bit 2: SNMP Trap reveive enable Bit 3: Syslog rece… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.3 |
|
wtTrapReceiver2x2WatchListEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Octet 3: Bit 0: enabled in Report 9 Bit 1: enabled in Report 10 Bit 2: enabled in Report 11 Bit 3: enabled in Report 12 Bit 4-7: unused Octet 4: Bit 0… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.4 |
|
wtTrapReceiver2x2WatchListAlias
mandatory
Alias Name
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.5 |
|
wtTrapReceiver2x2WatchListTrapNo
mandatory
SNMP Trap No: this filter is only active, if SNMP Trap reveive enable in
wtTrapReceiver2x2WatchListService is set. wtTrapReceiver2x2WatchListTrapNo-ColdStart(0), wtTrapReceiver2x2WatchListTrapNo-WarmStart(1), wtTrapRece… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.6 |
|
wtTrapReceiver2x2WatchListSpecificNo
mandatory
SNMP Specific No: this filter is only active, if SNMP Trap reveive enable in
wtTrapReceiver2x2WatchListService is set. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.7 |
|
wtTrapReceiver2x2WatchListFacility
mandatory
Syslog message level Facility: this filter is only active, if Syslog receive enable in
wtTrapReceiver2x2WatchListService is set. wtTrapReceiver2x2WatchListFacility-Emergency(0), wtTrapReceiver2x2WatchListFacility-Alert(… |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.8 |
|
wtTrapReceiver2x2WatchListSeverity
mandatory
Syslog message level Severity: this filter is only active, if Syslog receive enable in
wtTrapReceiver2x2WatchListService is set. wtTrapReceiver2x2WatchListSeverity-kernel-messages(0), wtTrapReceiver2x2WatchListSeverity-… |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.1.3.1.9 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.2.1
·
1 row entry
·
3 columns
List of settings depending on the SystemTimer number.
SystemTimer parameter for the individual SystemTimer.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2PortSystemTimerEnable
mandatory
Binary coded SystemTimer enable:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: ungenutzt OCTET 2: ungenutzt OCTET 3: ungenutzt OCTET 4, Bit 1-7: … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.2.1.1.1 |
|
wtTrapReceiver2x2PortSystemTimerName
mandatory
Name of the SystemTimer.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.2.1.1.2 |
|
wtTrapReceiver2x2PortSystemTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.2.1.1.3 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.3.1
·
1 row entry
·
4 columns
List of settings depending on the button number.
Button parameter for the individual buttons.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2PortButtonEnable
mandatory
Binary coded button enable:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: ungenutzt OCTET 2: ungenutzt OCTET 3: ungenutzt OCTET 4, Bit 1-7: ungen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.3.1.1.1 |
|
wtTrapReceiver2x2PortButtonName
mandatory
Name of the button.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.3.1.1.2 |
|
wtTrapReceiver2x2PortButtonText
mandatory
Description of the button.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.3.1.1.3 |
|
wtTrapReceiver2x2PortButtonAccess
mandatory
Binary coded button access level:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 3-7: unused … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.3.1.1.4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.4.1
·
1 row entry
·
3 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.4.1.1.1 |
|
wtTrapReceiver2x2PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.6.4.1.1.2 |
|
wtTrapReceiver2x2PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.6.4.1.1.4 |
.1.3.6.1.4.1.5040.1.2.33.3.1.7.1.1
·
1 row entry
·
4 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtTrapReceiver2x2PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.7.1.1.1.1 |
|
wtTrapReceiver2x2PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.7.1.1.1.2 |
|
wtTrapReceiver2x2PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.33.3.1.7.1.1.1.9 |
|
wtTrapReceiver2x2PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtTrapReceiver2x2PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.33.3.1.7.1.1.1.10 |
.1.3.6.1.4.1.5040.1.2.48.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.48.1.3.1.1 |
|
wtWebio577xxEA1x1InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.48.1.3.1.2 |
|
wtWebio577xxEA1x1InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.1.3.1.3 |
|
wtWebio577xxEA1x1InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.48.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.48.1.5.1.1 |
|
wtWebio577xxEA1x1OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3
·
1 row entry
·
23 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.1 |
|
wtWebio577xxEA1x1BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.2 |
|
wtWebio577xxEA1x1BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.3 |
|
wtWebio577xxEA1x1BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.4 |
|
wtWebio577xxEA1x1BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.5 |
|
wtWebio577xxEA1x1BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.6 |
|
wtWebio577xxEA1x1BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.7 |
|
wtWebio577xxEA1x1BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.8 |
|
wtWebio577xxEA1x1BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.9 |
|
wtWebio577xxEA1x1BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.10 |
|
wtWebio577xxEA1x1BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.11 |
|
wtWebio577xxEA1x1BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.12 |
|
wtWebio577xxEA1x1BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.13 |
|
wtWebio577xxEA1x1BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.14 |
|
wtWebio577xxEA1x1BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.15 |
|
wtWebio577xxEA1x1BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.16 |
|
wtWebio577xxEA1x1BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.17 |
|
wtWebio577xxEA1x1BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.18 |
|
wtWebio577xxEA1x1BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.19 |
|
wtWebio577xxEA1x1BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.20 |
|
wtWebio577xxEA1x1BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.21 |
|
wtWebio577xxEA1x1BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.22 |
|
wtWebio577xxEA1x1BinaryTcpClientServerUserName
mandatory
User Name to login at the remote server, if authentication needed.
|
OctetString | .1.3.6.1.4.1.5040.1.2.48.3.1.3.6.3.1.23 |
.1.3.6.1.4.1.5040.1.2.48.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.48.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3
·
1 row entry
·
54 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.1 |
|
wtWebio577xxEA1x1AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.2 |
|
wtWebio577xxEA1x1AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.3 |
|
wtWebio577xxEA1x1AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebio577xxEA1x1AlarmInputTrigger are no… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.4 |
|
wtWebio577xxEA1x1AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.5 |
|
wtWebio577xxEA1x1AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Bit 0: UDP enable Bit1-7: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog Messages enable Bit 4: F… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.6 |
|
wtWebio577xxEA1x1AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.7 |
|
wtWebio577xxEA1x1AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.8 |
|
wtWebio577xxEA1x1AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.9 |
|
wtWebio577xxEA1x1AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.10 |
|
wtWebio577xxEA1x1AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.11 |
|
wtWebio577xxEA1x1AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.12 |
|
wtWebio577xxEA1x1AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.13 |
|
wtWebio577xxEA1x1AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.14 |
|
wtWebio577xxEA1x1AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.15 |
|
wtWebio577xxEA1x1AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.16 |
|
wtWebio577xxEA1x1AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.17 |
|
wtWebio577xxEA1x1AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.18 |
|
wtWebio577xxEA1x1AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.19 |
|
wtWebio577xxEA1x1AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.20 |
|
wtWebio577xxEA1x1AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.21 |
|
wtWebio577xxEA1x1AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.22 |
|
wtWebio577xxEA1x1AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.23 |
|
wtWebio577xxEA1x1AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.24 |
|
wtWebio577xxEA1x1AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.25 |
|
wtWebio577xxEA1x1AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.26 |
|
wtWebio577xxEA1x1AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.27 |
|
wtWebio577xxEA1x1AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.28 |
|
wtWebio577xxEA1x1AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.29 |
|
wtWebio577xxEA1x1AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.30 |
|
wtWebio577xxEA1x1AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.31 |
|
wtWebio577xxEA1x1AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.32 |
|
wtWebio577xxEA1x1AlarmGlobalEnable
mandatory
Binary coded alarm activation:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.34 |
|
wtWebio577xxEA1x1AlarmCombinationLogic
mandatory
Binary coded alarm activation::
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : OR Bit 0 : AND |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.58 |
|
wtWebio577xxEA1x1AlarmTrgMqttTopic
mandatory
MQTT subscribe topic.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.59 |
|
wtWebio577xxEA1x1AlarmTrgMqttTopicText
mandatory
Receiving this text from the MQTT Broker, Alarm will be triggered.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.60 |
|
wtWebio577xxEA1x1AlarmHttpReqAuthEnable
mandatory
Binary coded alarm activation:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.61 |
|
wtWebio577xxEA1x1AlarmHttpReqAuthUser
mandatory
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.62 |
|
wtWebio577xxEA1x1AlarmHttpReqAuthPassword
mandatory
HTTP Request: Password
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.63 |
|
wtWebio577xxEA1x1AlarmHttpReqSetUrl
mandatory
HTTP Request: Set URL
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.64 |
|
wtWebio577xxEA1x1AlarmHttpReqClearUrl
mandatory
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.65 |
|
wtWebio577xxEA1x1AlarmHttpReqServerPort
mandatory
HTTP Request: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.66 |
|
wtWebio577xxEA1x1AlarmMqttTopicPath
mandatory
MQTT Publish: Topic path
|
OctetStringr/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.67 |
|
wtWebio577xxEA1x1AlarmMqttTopicSetTopic
mandatory
MQTT Publish: Topic SET message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.68 |
|
wtWebio577xxEA1x1AlarmMqttTopicClear
mandatory
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.69 |
|
wtWebio577xxEA1x1AlarmSetOutputsOwn
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.70 |
|
wtWebio577xxEA1x1AlarmSetOutputsServerIp
mandatory
Set Outputs: Server IP Address
|
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.71 |
|
wtWebio577xxEA1x1AlarmSetOutputsServerPort
mandatory
Set Outputs: Server Port
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.72 |
|
wtWebio577xxEA1x1AlarmSetOutputsServerPassword
mandatory
Set Outputs: Server Pasword
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.73 |
|
wtWebio577xxEA1x1AlarmSetOutputsServerOutputs
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.74 |
|
wtWebio577xxEA1x1AlarmSetOutputsDest
mandatory
Binary coded value:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : set … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.75 |
|
wtWebio577xxEA1x1AlarmSnmpManagerPort
mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.76 |
|
wtWebio577xxEA1x1AlarmMqttQoS
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.77 |
|
wtWebio577xxEA1x1AlarmMqttRetain
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.1.5.3.1.78 |
.1.3.6.1.4.1.5040.1.2.48.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.1.1.1 |
|
wtWebio577xxEA1x1PortInputText
mandatory
Description of the input.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.2.1.1.2 |
|
wtWebio577xxEA1x1PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.1.1.3 |
|
wtWebio577xxEA1x1PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.3.2.1.1.4 |
|
wtWebio577xxEA1x1PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.48.3.2.1.1.5 |
|
wtWebio577xxEA1x1PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.48.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA1x1PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.1 |
|
wtWebio577xxEA1x1PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.2 |
|
wtWebio577xxEA1x1PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.3 |
|
wtWebio577xxEA1x1PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.4 |
|
wtWebio577xxEA1x1PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.48.3.2.2.1.5 |
|
wtWebio577xxEA1x1PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.6 |
|
wtWebio577xxEA1x1PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.7 |
|
wtWebio577xxEA1x1PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.8 |
|
wtWebio577xxEA1x1PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.48.3.2.2.1.9 |
|
wtWebio577xxEA1x1PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebio577xxEA1x1PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.48.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.49.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.49.1.3.1.1 |
|
wtWebio577xxEA12x12InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.49.1.3.1.2 |
|
wtWebio577xxEA12x12InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.1.3.1.3 |
|
wtWebio577xxEA12x12InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.49.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.49.1.5.1.1 |
|
wtWebio577xxEA12x12OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3
·
1 row entry
·
23 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.1 |
|
wtWebio577xxEA12x12BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.2 |
|
wtWebio577xxEA12x12BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.3 |
|
wtWebio577xxEA12x12BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.4 |
|
wtWebio577xxEA12x12BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.5 |
|
wtWebio577xxEA12x12BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.6 |
|
wtWebio577xxEA12x12BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.7 |
|
wtWebio577xxEA12x12BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.8 |
|
wtWebio577xxEA12x12BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Constraints: range: 4-4Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.9 |
|
wtWebio577xxEA12x12BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.10 |
|
wtWebio577xxEA12x12BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.11 |
|
wtWebio577xxEA12x12BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.12 |
|
wtWebio577xxEA12x12BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.13 |
|
wtWebio577xxEA12x12BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.14 |
|
wtWebio577xxEA12x12BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.15 |
|
wtWebio577xxEA12x12BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.16 |
|
wtWebio577xxEA12x12BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.17 |
|
wtWebio577xxEA12x12BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.18 |
|
wtWebio577xxEA12x12BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.19 |
|
wtWebio577xxEA12x12BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.20 |
|
wtWebio577xxEA12x12BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.21 |
|
wtWebio577xxEA12x12BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.22 |
|
wtWebio577xxEA12x12BinaryTcpClientServerUserName
mandatory
User Name to login at the remote server, if authentication needed.
|
OctetString | .1.3.6.1.4.1.5040.1.2.49.3.1.3.6.3.1.23 |
.1.3.6.1.4.1.5040.1.2.49.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
wtWebio577xxEA2x2InputNo
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3
·
1 row entry
·
54 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.1 |
|
wtWebio577xxEA12x12AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.2 |
|
wtWebio577xxEA12x12AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.3 |
|
wtWebio577xxEA12x12AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebio577xxEA12x12AlarmInputTrigger are … |
OctetStringr/w Constraints: range: 1-1 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.4 |
|
wtWebio577xxEA12x12AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.5 |
|
wtWebio577xxEA12x12AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Bit 0: UDP enable Bit1-7: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog Messages enable Bit 4: F… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.6 |
|
wtWebio577xxEA12x12AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.7 |
|
wtWebio577xxEA12x12AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 1-2 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.8 |
|
wtWebio577xxEA12x12AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.9 |
|
wtWebio577xxEA12x12AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.10 |
|
wtWebio577xxEA12x12AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.11 |
|
wtWebio577xxEA12x12AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.12 |
|
wtWebio577xxEA12x12AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.13 |
|
wtWebio577xxEA12x12AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.14 |
|
wtWebio577xxEA12x12AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.15 |
|
wtWebio577xxEA12x12AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.16 |
|
wtWebio577xxEA12x12AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.17 |
|
wtWebio577xxEA12x12AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.18 |
|
wtWebio577xxEA12x12AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.19 |
|
wtWebio577xxEA12x12AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.20 |
|
wtWebio577xxEA12x12AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.21 |
|
wtWebio577xxEA12x12AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.22 |
|
wtWebio577xxEA12x12AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.23 |
|
wtWebio577xxEA12x12AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.24 |
|
wtWebio577xxEA12x12AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.25 |
|
wtWebio577xxEA12x12AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.26 |
|
wtWebio577xxEA12x12AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w Constraints: range: 0-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.27 |
|
wtWebio577xxEA12x12AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.28 |
|
wtWebio577xxEA12x12AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.29 |
|
wtWebio577xxEA12x12AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.30 |
|
wtWebio577xxEA12x12AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.31 |
|
wtWebio577xxEA12x12AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.32 |
|
wtWebio577xxEA12x12AlarmGlobalEnable
mandatory
Binary coded alarm activation:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.34 |
|
wtWebio577xxEA12x12AlarmCombinationLogic
mandatory
Binary coded logic, all Input/Output-trigger will be combined:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : OR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.58 |
|
wtWebio577xxEA12x12AlarmTrgMqttTopic
mandatory
MQTT subscribe topic.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.59 |
|
wtWebio577xxEA12x12AlarmTrgMqttTopicText
mandatory
Receiving this text from the MQTT Broker, Alarm will be triggered.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.60 |
|
wtWebio577xxEA12x12AlarmHttpReqAuthEnable
mandatory
Binary coded value:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.61 |
|
wtWebio577xxEA12x12AlarmHttpReqAuthUser
mandatory
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.62 |
|
wtWebio577xxEA12x12AlarmHttpReqAuthPassword
mandatory
HTTP Request: Password
|
OctetStringr/w Constraints: range: 1-12 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.63 |
|
wtWebio577xxEA12x12AlarmHttpReqSetUrl
mandatory
HTTP Request: Set URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.64 |
|
wtWebio577xxEA12x12AlarmHttpReqClearUrl
mandatory
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.65 |
|
wtWebio577xxEA12x12AlarmHttpReqServerPort
mandatory
HTTP Request: Server Port
|
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.66 |
|
wtWebio577xxEA12x12AlarmMqttTopicPath
mandatory
MQTT Publish: Topic path
|
OctetStringr/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.67 |
|
wtWebio577xxEA12x12AlarmMqttTopicSetTopic
mandatory
MQTT Publish: Topic SET message
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.68 |
|
wtWebio577xxEA12x12AlarmMqttTopicClear
mandatory
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.69 |
|
wtWebio577xxEA12x12AlarmSetOutputsOwn
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.70 |
|
wtWebio577xxEA12x12AlarmSetOutputsServerIp
mandatory
Set Outputs: Server IP Address
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.71 |
|
wtWebio577xxEA12x12AlarmSetOutputsServerPort
mandatory
Set Outputs: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.72 |
|
wtWebio577xxEA12x12AlarmSetOutputsServerPassword
mandatory
Set Outputs: Server Pasword
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.73 |
|
wtWebio577xxEA12x12AlarmSetOutputsServerOutputs
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.74 |
|
wtWebio577xxEA12x12AlarmSetOutputsDest
mandatory
Binary coded value:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : set outputs of remote server. Bit 0 : set outputs of this WEB-IO |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.75 |
|
wtWebio577xxEA12x12AlarmSnmpManagerPort
mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.76 |
|
wtWebio577xxEA12x12AlarmMqttQoS
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.77 |
|
wtWebio577xxEA12x12AlarmMqttRetain
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused |
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.1.5.3.1.78 |
.1.3.6.1.4.1.5040.1.2.49.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12PortInputName
mandatory
Name of the input.
|
OctetStringr/w Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.49.3.2.1.1.1 |
|
wtWebio577xxEA12x12PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.1.1.2 |
|
wtWebio577xxEA12x12PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.1.1.3 |
|
wtWebio577xxEA12x12PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Constraints: range: 1-65535Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.3.2.1.1.4 |
|
wtWebio577xxEA12x12PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.1.1.5 |
|
wtWebio577xxEA12x12PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.49.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x12PortOutputName
mandatory
Name of the output.
|
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.49.3.2.2.1.1 |
|
wtWebio577xxEA12x12PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.2 |
|
wtWebio577xxEA12x12PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.3 |
|
wtWebio577xxEA12x12PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.4 |
|
wtWebio577xxEA12x12PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (wt… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.5 |
|
wtWebio577xxEA12x12PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: Bit 0-3 : inputs 8-11 OCTET 4: Bit 0-7 : inputs 0-7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.6 |
|
wtWebio577xxEA12x12PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.7 |
|
wtWebio577xxEA12x12PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: Bit 0-3 : Output Inverter enable 8-11 OCTET 4: Bit 0-7 : Output Inverter enable 0-7 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.8 |
|
wtWebio577xxEA12x12PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.49.3.2.2.1.9 |
|
wtWebio577xxEA12x12PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebio577xxEA12x12PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unus… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.49.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.51.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelInputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.51.1.3.1.1 |
|
wtWebio577xxEA12x6RelInputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.51.1.3.1.2 |
|
wtWebio577xxEA12x6RelInputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.1.3.1.3 |
|
wtWebio577xxEA12x6RelInputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.51.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelOutputNo
mandatory
Output number.
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.5040.1.2.51.1.5.1.1 |
|
wtWebio577xxEA12x6RelOutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelBinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3
·
1 row entry
·
23 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelBinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.1 |
|
wtWebio577xxEA12x6RelBinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 12-12 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.2 |
|
wtWebio577xxEA12x6RelBinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.3 |
|
wtWebio577xxEA12x6RelBinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.4 |
|
wtWebio577xxEA12x6RelBinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.5 |
|
wtWebio577xxEA12x6RelBinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.6 |
|
wtWebio577xxEA12x6RelBinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.7 |
|
wtWebio577xxEA12x6RelBinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.8 |
|
wtWebio577xxEA12x6RelBinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.9 |
|
wtWebio577xxEA12x6RelBinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.10 |
|
wtWebio577xxEA12x6RelBinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.11 |
|
wtWebio577xxEA12x6RelBinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.12 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.13 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.14 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.15 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.16 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.17 |
|
wtWebio577xxEA12x6RelBinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.18 |
|
wtWebio577xxEA12x6RelBinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.19 |
|
wtWebio577xxEA12x6RelBinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.20 |
|
wtWebio577xxEA12x6RelBinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.21 |
|
wtWebio577xxEA12x6RelBinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.22 |
|
wtWebio577xxEA12x6RelBinaryTcpClientServerUserName
mandatory
User Name to login at the remote server, if authentication needed.
|
OctetString Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.3.6.3.1.23 |
.1.3.6.1.4.1.5040.1.2.51.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelOutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w Constraints: range: 4-4 |
.1.3.6.1.4.1.5040.1.2.51.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.51.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelAlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.51.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.51.3.1.5.3
·
1 row entry
·
54 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelAlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.1 |
|
wtWebio577xxEA12x6RelAlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.2 |
|
wtWebio577xxEA12x6RelAlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.3 |
|
wtWebio577xxEA12x6RelAlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebio577xxEA12x6RelAlarmInputTrigger ar… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.4 |
|
wtWebio577xxEA12x6RelAlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.5 |
|
wtWebio577xxEA12x6RelAlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Bit 0: UDP enable Bit1-7: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog Messages enable Bit 4: F… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.6 |
|
wtWebio577xxEA12x6RelAlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.7 |
|
wtWebio577xxEA12x6RelAlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.8 |
|
wtWebio577xxEA12x6RelAlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.9 |
|
wtWebio577xxEA12x6RelAlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.10 |
|
wtWebio577xxEA12x6RelAlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.11 |
|
wtWebio577xxEA12x6RelAlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.12 |
|
wtWebio577xxEA12x6RelAlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.13 |
|
wtWebio577xxEA12x6RelAlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.14 |
|
wtWebio577xxEA12x6RelAlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.15 |
|
wtWebio577xxEA12x6RelAlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.16 |
|
wtWebio577xxEA12x6RelAlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.17 |
|
wtWebio577xxEA12x6RelAlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.18 |
|
wtWebio577xxEA12x6RelAlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.19 |
|
wtWebio577xxEA12x6RelAlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.20 |
|
wtWebio577xxEA12x6RelAlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.21 |
|
wtWebio577xxEA12x6RelAlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.22 |
|
wtWebio577xxEA12x6RelAlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.23 |
|
wtWebio577xxEA12x6RelAlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.24 |
|
wtWebio577xxEA12x6RelAlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.25 |
|
wtWebio577xxEA12x6RelAlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.26 |
|
wtWebio577xxEA12x6RelAlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.27 |
|
wtWebio577xxEA12x6RelAlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.28 |
|
wtWebio577xxEA12x6RelAlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.29 |
|
wtWebio577xxEA12x6RelAlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.30 |
|
wtWebio577xxEA12x6RelAlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.31 |
|
wtWebio577xxEA12x6RelAlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.32 |
|
wtWebio577xxEA12x6RelAlarmGlobalEnable
mandatory
Binary coded alarm activation:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.34 |
|
wtWebio577xxEA12x6RelAlarmCombinationLogic
mandatory
Binary coded logic, all Input/Output-trigger will be combined:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : OR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.58 |
|
wtWebio577xxEA12x6RelAlarmTrgMqttTopic
mandatory
MQTT subscribe topic.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.59 |
|
wtWebio577xxEA12x6RelAlarmTrgMqttTopicText
mandatory
Receiving this text from the MQTT Broker, Alarm will be triggered.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.60 |
|
wtWebio577xxEA12x6RelAlarmHttpReqAuthEnable
mandatory
Binary coded value:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.61 |
|
wtWebio577xxEA12x6RelAlarmHttpReqAuthUser
mandatory
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.62 |
|
wtWebio577xxEA12x6RelAlarmHttpReqAuthPassword
mandatory
HTTP Request: Password
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.63 |
|
wtWebio577xxEA12x6RelAlarmHttpReqSetUrl
mandatory
HTTP Request: Set URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.64 |
|
wtWebio577xxEA12x6RelAlarmHttpReqClearUrl
mandatory
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.65 |
|
wtWebio577xxEA12x6RelAlarmHttpReqServerPort
mandatory
HTTP Request: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.66 |
|
wtWebio577xxEA12x6RelAlarmMqttTopicPath
mandatory
MQTT Publish: Topic path
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.67 |
|
wtWebio577xxEA12x6RelAlarmMqttTopicSetTopic
mandatory
MQTT Publish: Topic SET message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.68 |
|
wtWebio577xxEA12x6RelAlarmMqttTopicClear
mandatory
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.69 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsOwn
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.70 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsServerIp
mandatory
Set Outputs: Server IP Address
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.71 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsServerPort
mandatory
Set Outputs: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.72 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsServerPassword
mandatory
Set Outputs: Server Pasword
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.73 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsServerOutputs
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.74 |
|
wtWebio577xxEA12x6RelAlarmSetOutputsDest
mandatory
Binary coded value:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : set outputs of remote server. Bit 0 : set outputs of this WEB-IO |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.75 |
|
wtWebio577xxEA12x6RelAlarmSnmpManagerPort
mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.76 |
|
wtWebio577xxEA12x6RelAlarmMqttQoS
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.77 |
|
wtWebio577xxEA12x6RelAlarmMqttRetain
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.1.5.3.1.78 |
.1.3.6.1.4.1.5040.1.2.51.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelPortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.1.1.1 |
|
wtWebio577xxEA12x6RelPortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.1.1.2 |
|
wtWebio577xxEA12x6RelPortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.1.1.3 |
|
wtWebio577xxEA12x6RelPortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.3.2.1.1.4 |
|
wtWebio577xxEA12x6RelPortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.1.1.5 |
|
wtWebio577xxEA12x6RelPortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.51.3.2.2
·
1 row entry
·
6 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA12x6RelPortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.1 |
|
wtWebio577xxEA12x6RelPortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.2 |
|
wtWebio577xxEA12x6RelPortOutputGroupMode
mandatory
No function within this device.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.3 |
|
wtWebio577xxEA12x6RelPortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.4 |
|
wtWebio577xxEA12x6RelPortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.51.3.2.2.1.9 |
|
wtWebio577xxEA12x6RelPortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebio577xxEA12x6RelPortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: un… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.10 |
.1.3.6.1.4.1.5040.1.2.52.1.3
·
1 row entry
·
4 columns
List of input indices.
Number of the inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2InputNo
mandatory
Index numbers of the inputs.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.52.1.3.1.1 |
|
wtWebio577xxEA2x2InputCounter
mandatory
Value of the input counter.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.52.1.3.1.2 |
|
wtWebio577xxEA2x2InputCounterClear
mandatory
Clears the input counter after returning its value.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.1.3.1.3 |
|
wtWebio577xxEA2x2InputState
mandatory
Value of a single input bit, 0-OFF, 1-ON.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.1.3.1.4 |
.1.3.6.1.4.1.5040.1.2.52.1.5
·
1 row entry
·
2 columns
List of output indices.
Number of the outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2OutputNo
mandatory
Output number.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.52.1.5.1.1 |
|
wtWebio577xxEA2x2OutputState
mandatory
Value of a single output bit, 0-OFF, 1-ON.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.1.5.1.2 |
.1.3.6.1.4.1.5040.1.2.52.3.1.3.6.2
·
1 row entry
·
1 columns
Table of indices.
Indices of the binary channels.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2BinaryModeNo
mandatory
Number of the binary channel.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.2.1.1 |
.1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3
·
1 row entry
·
23 columns
Table of properties of the binary mode.
Binary properties.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2BinaryOperationMode
mandatory
Selection of the operation mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : UDP Peer Bit 1 : TCP Client … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.1 |
|
wtWebio577xxEA2x2BinaryTcpServerLocalPort
mandatory
Local TCP port for data exchange in this server mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.2 |
|
wtWebio577xxEA2x2BinaryTcpServerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.3 |
|
wtWebio577xxEA2x2BinaryTcpServerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 4-7: unused Bit 3 : OPC Device Bit 2 : Box2Box S… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.4 |
|
wtWebio577xxEA2x2BinaryTcpClientLocalPort
mandatory
Local TCP port for data exchange in this client mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.5 |
|
wtWebio577xxEA2x2BinaryTcpClientServerPort
mandatory
Port number of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.6 |
|
wtWebio577xxEA2x2BinaryTcpClientServerIpAddr
mandatory
Ip address of the server. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the server IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.7 |
|
wtWebio577xxEA2x2BinaryTcpClientServerPassword
mandatory
Building a connection may be protected by the
administrator password of the server. Enter the server password to establish the connection, if a server administrator password exists. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.8 |
|
wtWebio577xxEA2x2BinaryTcpClientInactivity
mandatory
Connection timeout in 100ms. If no data are exchanged within the specified
time, the device closes the connection to the server. The value 0 deactivates the timer. Using the Box2Box mode this function is disabled. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.9 |
|
wtWebio577xxEA2x2BinaryTcpClientInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.10 |
|
wtWebio577xxEA2x2BinaryTcpClientInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured application. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.11 |
|
wtWebio577xxEA2x2BinaryTcpClientApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused Bit 2 : Box2Box Slave Bit 1 : Compat… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.12 |
|
wtWebio577xxEA2x2BinaryUdpPeerLocalPort
mandatory
Local UDP port for data exchange in this peer to peer mode.
This port number must be unique within the device. Reserved port number must not be used (refere to the manual). |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.13 |
|
wtWebio577xxEA2x2BinaryUdpPeerRemotePort
mandatory
Port number of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote port to zero. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.14 |
|
wtWebio577xxEA2x2BinaryUdpPeerRemoteIpAddr
mandatory
Ip address of the remote device. A complete set of port number, IP address
and a valid input/output mask starts this mode. No data exchange take place when setting the remote device IP address to 0.0.0.0. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.15 |
|
wtWebio577xxEA2x2BinaryUdpPeerInputTrigger
mandatory
Every change on the inputs causes their state to be transmitted to the
remote device. To minimize data traffic, individual inputs may be exempted from this rule. Nevertheless every transmission will contain all input … |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.16 |
|
wtWebio577xxEA2x2BinaryUdpPeerInterval
mandatory
Configurable interval with a 100ms base, in which the Webio device sends
data to the configured remote device. A interval of zero stopps the periodical sending. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.17 |
|
wtWebio577xxEA2x2BinaryUdpPeerApplicationMode
mandatory
Selection of the application mode:
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 3-7: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.18 |
|
wtWebio577xxEA2x2BinaryConnectedPort
mandatory
Port number of the remote device, after connection has been established.
In case of no connection or missing port informations a zero will be read. |
Integer32 | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.19 |
|
wtWebio577xxEA2x2BinaryConnectedIpAddr
mandatory
IP address of the remote device, after connection has been established.
In case of no connection or missing port informations 0.0.0.0 will be read. |
RFC1155-SMIIpAddress Textual Convention: RFC1155-SMIIpAddress OctetStringType Constraints: range: 4 |
.1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.20 |
|
wtWebio577xxEA2x2BinaryTcpServerClientHttpPort
mandatory
HTTP port number of the remote device at TCP Server Mode. If an mailfunction occurs
status informations will be send to this port. Not used at mode Compatible 50xxx. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.21 |
|
wtWebio577xxEA2x2BinaryTcpClientServerHttpPort
mandatory
HTTP port number of the remote device at TCP Client Mode. In the operating mode
Box2Box connection status informations will be exchanged through this port. |
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.22 |
|
wtWebio577xxEA2x2BinaryTcpClientServerUserName
mandatory
User Name to login at the remote server, if authentication needed.
|
OctetString | .1.3.6.1.4.1.5040.1.2.52.3.1.3.6.3.1.23 |
.1.3.6.1.4.1.5040.1.2.52.3.1.4.1
·
1 row entry
·
1 columns
Table of output mode configurations dependent on the output indices.
Output mode configurations of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2OutputModeBit
mandatory
This binary coded output mode defines the individual operation mode for any
output. More than one mode must not be selected. The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corres… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.4.1.1.1 |
.1.3.6.1.4.1.5040.1.2.52.3.1.5.2
·
1 row entry
·
1 columns
List of alarm indices.
Numbers of the alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2AlarmNo
mandatory
Numbers of the alarms.
|
Integer32 | .1.3.6.1.4.1.5040.1.2.52.3.1.5.2.1.1 |
.1.3.6.1.4.1.5040.1.2.52.3.1.5.3
·
1 row entry
·
54 columns
List of settings depending on the alarm number.
Alarm parameters of the individual alarms.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2AlarmInputTrigger
mandatory
This variable allows setting of individual input trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. The first four OCTETS contain the mas… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.1 |
|
wtWebio577xxEA2x2AlarmOutputTrigger
mandatory
This variable allows setting of individual output trigger conditions.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the m… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.2 |
|
wtWebio577xxEA2x2AlarmSystemTrigger
mandatory
Binary coded trigger conditions:
The OCTETS are interpreted bit-by-bit. Bit 0 corresponds to the LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 4-7: unused Bit 3 : Warm Start Bit 2 : Cold Sta… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.3 |
|
wtWebio577xxEA2x2AlarmMaxCounterValue
mandatory
This variable configures a max. counter value. If an input counter value
exceeds this max. value, the corresponding alarm is triggered. Input counters with its mask bit unset in wtWebio577xxEA2x2AlarmInputTrigger are no… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.4 |
|
wtWebio577xxEA2x2AlarmInterval
mandatory
Send interval for alarm messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.5 |
|
wtWebio577xxEA2x2AlarmEnable
mandatory
Binary coded alarm enable:
Octet 1: unused Octet 2: unused Bit 0: UDP enable Bit1-7: unused Octet 4: Bit 0: Mail Enable Bit 1: SNMP Trap enable Bit 2: TCP Client enable Bit 3: Syslog Messages enable Bit 4: F… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.6 |
|
wtWebio577xxEA2x2AlarmMailAddr
mandatory
E-Mail address for sending the alarm mail to.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.7 |
|
wtWebio577xxEA2x2AlarmMailSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.8 |
|
wtWebio577xxEA2x2AlarmMailText
mandatory
Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.9 |
|
wtWebio577xxEA2x2AlarmSnmpManagerIP
mandatory
IP address of the SNMP Manager to which the Webio device should send SNMP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.10 |
|
wtWebio577xxEA2x2AlarmSnmpTrapText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.11 |
|
wtWebio577xxEA2x2AlarmUdpIpAddr
mandatory
IP address of the UDP listener to which the Webio device should send UDP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.12 |
|
wtWebio577xxEA2x2AlarmUdpPort
mandatory
Port number of the UDP listener to which the Webio device should send UDP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.13 |
|
wtWebio577xxEA2x2AlarmUdpText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.14 |
|
wtWebio577xxEA2x2AlarmTcpIpAddr
mandatory
IP address of the TCP listener to which the Webio device should send TCP traps.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.15 |
|
wtWebio577xxEA2x2AlarmTcpPort
mandatory
Port number of the TCP listener to which the Webio device should send TCP traps.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.16 |
|
wtWebio577xxEA2x2AlarmTcpText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.17 |
|
wtWebio577xxEA2x2AlarmSyslogIpAddr
mandatory
IP address of the syslog server to which the Webio device should send syslog messages.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.18 |
|
wtWebio577xxEA2x2AlarmSyslogPort
mandatory
Port number of the syslog server to which the Webio device should send syslog messages.
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.19 |
|
wtWebio577xxEA2x2AlarmSyslogText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.20 |
|
wtWebio577xxEA2x2AlarmFtpDataPort
mandatory
Local data port: 1..65535 or AUTO: the next free port will be assigned.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.21 |
|
wtWebio577xxEA2x2AlarmFtpFileName
mandatory
Name of the file including path informations.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.22 |
|
wtWebio577xxEA2x2AlarmFtpText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.23 |
|
wtWebio577xxEA2x2AlarmFtpOption
mandatory
Binary coded options, select only one option at the same time:
STORE = replace file APPEND = append message at the end of the file Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : STOR… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.24 |
|
wtWebio577xxEA2x2AlarmTimerCron
mandatory
This entry contains 5 space or tab seperated text fields for time trigger definition.
Each field must match with the actual time to trigger a message, weekday and day of month are interpreted separatley. 1: Minutes Rang… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.25 |
|
wtWebio577xxEA2x2AlarmMailReleaseSubject
mandatory
Subject line for alarm mail.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.26 |
|
wtWebio577xxEA2x2AlarmMailReleaseText
mandatory
Release Alarm mail text:
States of the Webio device can be included by using special tags. Please refer to the respective Webio manual |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.27 |
|
wtWebio577xxEA2x2AlarmSnmpTrapReleaseText
mandatory
This text appears in the trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.28 |
|
wtWebio577xxEA2x2AlarmUdpReleaseText
mandatory
This text appears in the UDP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.29 |
|
wtWebio577xxEA2x2AlarmTcpReleaseText
mandatory
This text appears in the TCP trap body.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.30 |
|
wtWebio577xxEA2x2AlarmSyslogReleaseText
mandatory
Every message starts with the priority key, a time stamp and the host ip address, according RFC3164.
This text appears in the following syslog message body. |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.31 |
|
wtWebio577xxEA2x2AlarmFtpReleaseText
mandatory
Message text to store on the FTP server.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.32 |
|
wtWebio577xxEA2x2AlarmGlobalEnable
mandatory
Binary coded alarm activation:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : Alarm enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.34 |
|
wtWebio577xxEA2x2AlarmCombinationLogic
mandatory
Binary coded logic:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : OR Bit 0 : AND |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.58 |
|
wtWebio577xxEA2x2AlarmTrgMqttTopic
mandatory
MQTT subscribe topic.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.59 |
|
wtWebio577xxEA2x2AlarmTrgMqttTopicText
mandatory
Reveiving this message from the MQTT Broker, this alarm will be triggered.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.60 |
|
wtWebio577xxEA2x2AlarmHttpReqAuthEnable
mandatory
Binnary coded value:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 1-7: unused Bit 0 : HHTP Request Authentication enable |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.61 |
|
wtWebio577xxEA2x2AlarmHttpReqAuthUser
mandatory
HTTP Request: User
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.62 |
|
wtWebio577xxEA2x2AlarmHttpReqAuthPassword
mandatory
HTTP Request: Password
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.63 |
|
wtWebio577xxEA2x2AlarmHttpReqSetUrl
mandatory
HTTP Request: Set URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.64 |
|
wtWebio577xxEA2x2AlarmHttpReqClearUrl
mandatory
HTTP Request: Clear URL
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.65 |
|
wtWebio577xxEA2x2AlarmHttpReqServerPort
mandatory
HTTP Request: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.66 |
|
wtWebio577xxEA2x2AlarmMqttTopicPath
mandatory
MQTT Publish: Topic path
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.67 |
|
wtWebio577xxEA2x2AlarmMqttTopicSetTopic
mandatory
MQTT Publish: Topic SET message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.68 |
|
wtWebio577xxEA2x2AlarmMqttTopicClear
mandatory
MQTT Publish: Topic CLEAR message
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.69 |
|
wtWebio577xxEA2x2AlarmSetOutputsOwn
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.70 |
|
wtWebio577xxEA2x2AlarmSetOutputsServerIp
mandatory
Set Outputs: Server IP Address
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.71 |
|
wtWebio577xxEA2x2AlarmSetOutputsServerPort
mandatory
Set Outputs: Server Port
|
Integer32r/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.72 |
|
wtWebio577xxEA2x2AlarmSetOutputsServerPassword
mandatory
Set Outputs: Server Pasword
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.73 |
|
wtWebio577xxEA2x2AlarmSetOutputsServerOutputs
mandatory
This variable allows setting of individual output.
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which determine… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.74 |
|
wtWebio577xxEA2x2AlarmSetOutputsDest
mandatory
Binary coded value:
Bit 0 = LSB. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4, Bit 2-7: unused Bit 1 : set outputs of remote server. Bit 0 : set outputs of this WEB-IO |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.75 |
|
wtWebio577xxEA2x2AlarmSnmpManagerPort
mandatory
Port number of the SNMP Manager to which the Webio device should send SNMP traps.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.76 |
|
wtWebio577xxEA2x2AlarmMqttQoS
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0: QoS 0 Bit 1: QoS 1 Bit 2: QoS 2 Bit 3-7:unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.77 |
|
wtWebio577xxEA2x2AlarmMqttRetain
mandatory
Binary coded value:
Octet 1: unused Octet 2: unused Octet 3: unused Octet 4: Bit 0 : retain enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.1.5.3.1.78 |
.1.3.6.1.4.1.5040.1.2.52.3.2.1
·
1 row entry
·
6 columns
List of settings depending on the input number.
Input parameter for the individual inputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2PortInputName
mandatory
Name of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.1.1.1 |
|
wtWebio577xxEA2x2PortInputText
mandatory
Description of the input.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.1.1.2 |
|
wtWebio577xxEA2x2PortInputMode
mandatory
Binary coded modes:
Selecting short pulse detection enable by setting the corresponding bit to 1 enables interrupt support for counting. Only positive edges are accepted as trigger source. The maximum counting frequen… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.1.1.3 |
|
wtWebio577xxEA2x2PortInputFilter
mandatory
Pulses with a duration shorter than here specified (duration in 1/1000 sec),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.3.2.1.1.4 |
|
wtWebio577xxEA2x2PortInputBicountPulsePolarity
mandatory
This value defines the polarity of the input pulse.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : negative polarity Bit 1 : positive polarity Bit 2-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.1.1.5 |
|
wtWebio577xxEA2x2PortInputBicountInactivTimeout
mandatory
Pulse chains with a duration shorter than here specified (in 1/10 sek),
are ignored. |
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.3.2.1.1.6 |
.1.3.6.1.4.1.5040.1.2.52.3.2.2
·
1 row entry
·
10 columns
List of settings depending on the output number.
Output parameters of the individual outputs.
Indexes
No indexes recorded
| Column | Syntax | OID |
|---|---|---|
|
wtWebio577xxEA2x2PortOutputName
mandatory
Name of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.1 |
|
wtWebio577xxEA2x2PortOutputText
mandatory
Description of the output.
|
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.2 |
|
wtWebio577xxEA2x2PortOutputGroupMode
mandatory
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits of such a group has to be set all together in the same way. This v… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.3 |
|
wtWebio577xxEA2x2PortOutputSafetyState
mandatory
This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds to the LSB. The first four OCTETS contain the mask which d… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.4 |
|
wtWebio577xxEA2x2PortLogicInputMask
mandatory
Selecting one of these inputs by setting the corresponding bit to 1
enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (w… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.5 |
|
wtWebio577xxEA2x2PortLogicInputInverter
mandatory
Every input bit selected here will be inverted.
OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1 |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.6 |
|
wtWebio577xxEA2x2PortLogicFunction
mandatory
This determines the logic function. No more than one function
may be selected. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : logic function OR (default) Bit 1 : logic function AND Bit 2-7 :… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.7 |
|
wtWebio577xxEA2x2PortLogicOutputInverter
mandatory
The logical operation result could be inverteted by setting the corresponding
bit to 1. OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0 : Output Inverter enable Bit 1-7 : unused |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.8 |
|
wtWebio577xxEA2x2PortPulseDuration
mandatory
Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output.
|
Integer32r/w Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.5040.1.2.52.3.2.2.1.9 |
|
wtWebio577xxEA2x2PortPulsePolarity
mandatory
This value defines the polarity of the output pulse, if wtWebio577xxEA2x2PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposite state. OCTET 1: unused OCTET 2: unused… |
OctetStringr/w | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.10 |