wtTrapReceiver2x2ActionOutputAction

Webio-Digital-MIB-US · .1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.57

Object

column mandatory r/w OctetString
This variable allows setting of individual output. 
The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. 
Bit 0 corresponds to the LSB.
	The first four OCTETS contain the mask which determines which of the outputs are to 
	be considered (corresponding bit = 1) and which outputs are to ignore 
	(corresponding bit = 0):
	OCTET 1 : unused
	OCTET 2 : unused
	OCTET 3 : unused
	OCTET 4, Bit 0-1: Mask for digital outputs 0-1
              	
	OCTETS 5-8 contain the level (1=HIGH, 0=LOW) which the outputs 
	should assume:
	OCTET 5 : unused
	OCTET 6 : unused
	OCTET 7 : unused
OCTET 8, Bit 0-1: Level of digital outputs 0-1
              
	OCTETS 9-12 contain the TOOGLE bit (1=ON, 0=OFF). outputs masked with the TOGGLE bit trigger change 
	their state on every action. Settings in OCTET 5-9 are then unused:
	OCTET 9: unused
	OCTET 10: unused
	OCTET 11: unused
	OCTET 12, Bit 0-1: TOGGLE bits of digital outputs 0-1

Context

MIB
Webio-Digital-MIB-US
OID
.1.3.6.1.4.1.5040.1.2.33.3.1.5.3.1.57
Type
column
Access
readwrite
Status
mandatory
Parent
wtTrapReceiver2x2ActionEntry
Table
wtTrapReceiver2x2ActionTable
Siblings
26

Syntax

OctetString

Values & Constraints

No enumerated values or constraints recorded.

Related Objects