wtWebio577xxEA2x2PortLogicInputMask
Webio-Digital-MIB-US ·
.1.3.6.1.4.1.5040.1.2.52.3.2.2.1.5
Object
column
mandatory
r/w
OctetString
Selecting one of these inputs by setting the corresponding bit to 1 enables the logic function for the output identified by the index within this table. The calculation take place in 4 steps: 1. Selecting inputs (wtWebio577xxEA2x2PortLogicInputMask) 2. Inverting inputs if necessary (wtWebio577xxEA2x2PortLogicInputInverter) 3. Logical combination (wtWebio577xxEA2x2PortLogicFunction) 4. Inverting the result if necessary (wtWebio577xxEA2x2PortLogicOutputInverter) OCTET 1: unused OCTET 2: unused OCTET 3: unused OCTET 4: Bit 0-1 : inputs 0-1
Context
- MIB
- Webio-Digital-MIB-US
- OID
.1.3.6.1.4.1.5040.1.2.52.3.2.2.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- wtWebio577xxEA2x2OutputPortEntry
- Table
- wtWebio577xxEA2x2OutputPortTable
- Siblings
- 9
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| wtWebio577xxEA2x2PortOutputName mandatory Name of the output. | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.1 |
| wtWebio577xxEA2x2PortPulsePolarity mandatory This value defines the polarity of the output pulse, if wtWebio577xxEA2x2PortPulseDuration is not set to zero.
After the pulse is finished, the output switches back to the opposit… | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.10 |
| wtWebio577xxEA2x2PortOutputText mandatory Description of the output. | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.2 |
| wtWebio577xxEA2x2PortOutputGroupMode mandatory It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits
of such a group has to be … | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.3 |
| wtWebio577xxEA2x2PortOutputSafetyState mandatory This variable allows setting of individual digital outputs. The OCTETS are
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds
to the LSB.
The fi… | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.4 |
| wtWebio577xxEA2x2PortLogicInputInverter mandatory Every input bit selected here will be inverted.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4: Bit 0-1 : inputs 0-1 | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.6 |
| wtWebio577xxEA2x2PortLogicFunction mandatory This determines the logic function. No more than one function
may be selected.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4:
Bit 0 : logic function OR (default)
… | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.7 |
| wtWebio577xxEA2x2PortLogicOutputInverter mandatory The logical operation result could be inverteted by setting the corresponding
bit to 1.
OCTET 1: unused
OCTET 2: unused
OCTET 3: unused
OCTET 4:
Bit 0 : Output Inverter enab… | column | OctetString | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.8 |
| wtWebio577xxEA2x2PortPulseDuration mandatory Pulse length in 1/1000 sec. Setting this value to zero, disables the pulse output. | column | Integer32 | .1.3.6.1.4.1.5040.1.2.52.3.2.2.1.9 |