wtWebio577xxEA12x6RelPortOutputSafetyState

Webio-Digital-MIB-US · .1.3.6.1.4.1.5040.1.2.51.3.2.2.1.4

Object

column mandatory r/w OctetString
This variable allows setting of individual digital outputs. The OCTETS are 
interpreted bit-by-bit, with each bit corresponding to an output. Bit 0 corresponds 
to the LSB.
The first four OCTETS contain the mask which determines which of the outputs are to 
be set (corresponding bit = 1) and which outputs are to remain unchanged 
(corresponding bit = 0):
OCTET 1		: unused
OCTET 2		: unused
OCTET 3	 	: unused
OCTET 4  Bit 0-6: Mask for digital output 0-6
OCTETS 5-8 contain the level (1=HIGH, 0=LOW) which the outputs to be changed 
should assume:
OCTET 5		: unused
OCTET 6		: unused
OCTET 7	 	: Unused
OCTET 8  Bit 0-6: Level of digital output 0-6