wtWebioEA6x6PortOutputGroupMode

Webio-Digital-MIB-US · .1.3.6.1.4.1.5040.1.2.24.3.2.2.1.3

Object

column mandatory r/w OctetString
It is possible to connect outputs together to increase the output current.
This could be done by connecting 2 or 4 outputs in a group together. All bits
of such a group has to be set all together in the same way. This variable
configures this group scheme. If one output bit of a group is set, all other 
output bits of the same group will be set in the same manner.
More than one configuration must not be selected.
	Selection for outputs 0-3:
Octet 1: unused
Octet 2: unused
Octet 3: unused
OCTET 4: Bit 0   : outputs 0,1,2,3 disconnected (default)
	 Bit 1   : outputs 0+1, 2+3 connected
	 Bit 2   : outputs 0+1+2+3 connected
	 Bit 3-7 : unused
	Selection for outputs 4-7:
Octet 1: unused
Octet 2: unused
Octet 3: unused
OCTET 4: Bit 0   : outputs 4, 5 disconnected (default)
	 Bit 1   : outputs 4+5 connected
	 Bit 2-7 : unused        	 
	Selection for outputs 8-11:
Octet 1: unused
Octet 2: unused
Octet 3: unused
OCTET 4: unused

Context

MIB
Webio-Digital-MIB-US
OID
.1.3.6.1.4.1.5040.1.2.24.3.2.2.1.3
Type
column
Access
readwrite
Status
mandatory
Parent
wtWebioEA6x6OutputPortEntry
Table
wtWebioEA6x6OutputPortTable
Siblings
9

Syntax

OctetString

Values & Constraints

Object Constraints
range: 4-4

Related Objects

Sibling Objects