SEVERE: Communication to the UPS has been lost. Steps
to reestablish communication are in progress.
upsDiagnosticsPassed
.1.3.6.1.4.1.318.0.10
INFORMATIONAL: The UPS passed its internal self-test.
mspOutletOn
.1.3.6.1.4.1.318.0.100
INFORMATIONAL: An outlet on the MasterSwitch plus has turned on.
mspOutletOff
.1.3.6.1.4.1.318.0.101
INFORMATIONAL: An outlet on the MasterSwitch plus has turned off.
mspDeviceConfigChange
.1.3.6.1.4.1.318.0.102
INFORMATIONAL: A device configuration change has been made on a MasterSwitch plus.
mspOutletConfigChange
.1.3.6.1.4.1.318.0.103
INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus.
rsSourceSwitched
.1.3.6.1.4.1.318.0.104
INFORMATIONAL: The Redundant Switch has switched source.
The first variable is an integer representing the current source: 0=A, 1=B.
The second variable is the 32-character name of the current source.
The third variable is an integer representing the transfer cause:
0=No Transfers Recorded, 1=Due to user action or preferred switching,
3=Due to line notch or spike, 5=Due to low line voltage,
7=Transfer due to high line voltage,
9=Transfer due to frequency out of range.
The fourth variable is a character string listing the transfer cause.
rsLostRedundancy
.1.3.6.1.4.1.318.0.105
SEVERE: The Redundant Switch has lost redundancy.
The first variable is an integer representing the source which is no longer available: 0=A, 1=B.
The second variable is the 32-character name of the source which is no longer available.
rsRedundancyRestored
.1.3.6.1.4.1.318.0.106
INFORMATIONAL: Redundancy has been restored to the Redundant Switch .
The first variable is an integer representing the source which has been restored: 0=A, 1=B.
The second variable is the 32-character name of the source which has been restored.
rsConfigChange
.1.3.6.1.4.1.318.0.107
INFORMATIONAL: A configuration change has been made on a Redundant Switch.
rsCommunicationEstablished
.1.3.6.1.4.1.318.0.108
INFORMATIONAL: Communications with the Redundant Switch has been established.
rsCommunicationLost
.1.3.6.1.4.1.318.0.109
SEVERE: Communications with the Redundant Switch has been lost.
returnFromLowBattery
.1.3.6.1.4.1.318.0.11
INFORMATIONAL: The UPS has returned from a low battery
condition.
dcCommunicationEstablished
.1.3.6.1.4.1.318.0.110
INFORMATIONAL: Communications with the DC power plant has been established.
dcCommunicationLost
.1.3.6.1.4.1.318.0.111
SEVERE: Communications with the DC power plant has been lost.
dcPINChanged
.1.3.6.1.4.1.318.0.112
INFORMATIONAL: The active PIN on the DC controller has been changed.
dcMajorAlarm
.1.3.6.1.4.1.318.0.113
SEVERE: A Major alarm is active in the DC power plant.
dcMajorAlarmCleared
.1.3.6.1.4.1.318.0.114
INFORMATIONAL: A Major alarm is no longer active in the DC power plant.
dcMinorAlarm
.1.3.6.1.4.1.318.0.115
WARNING: A Minor alarm is active in the DC power plant.
dcMinorAlarmCleared
.1.3.6.1.4.1.318.0.116
INFORMATIONAL: A Minor alarm is no longer active in the DC power plant.
dcOutputRelayOn
.1.3.6.1.4.1.318.0.117
WARNING: An output relay for the powerplant has been activated (state changed to on).
The first variable is an integer representing the output relay number that has gone on.
The second variable is the 16-character name of the output relay.
dcOutputRelayOff
.1.3.6.1.4.1.318.0.118
INFORMATIONAL: An output relay for the powerplant has been deactivated (state changed to off).
The first variable is an integer representing the output relay number that has gone off.
The second variable is the 16-character name of the output relay.
dcInputRelayOn
.1.3.6.1.4.1.318.0.119
WARNING: An input relay for the powerplant has been activated (state changed to on).
The first variable is an integer representing the input relay number that has gone on.
The second variable is the 16-character name of the input relay.
upsTurnedOff
.1.3.6.1.4.1.318.0.12
WARNING: The UPS has been turned 'off' by the management station.
dcInputRelayOff
.1.3.6.1.4.1.318.0.120
INFORMATIONAL: An input relay for the powerplant has been deactivated (state changed to off).
The first variable is an integer representing the input relay number that has gone off.
The second variable is the 16-character name of the input relay.
logicPowerSuppliesIncreased
.1.3.6.1.4.1.318.0.121
INFORMATIONAL: The number of system power supplies has increased.
logicPowerSuppliesDecreased
.1.3.6.1.4.1.318.0.122
INFORMATIONAL: The number of system power supplies has decreased.
externalSwitchGearClosed
.1.3.6.1.4.1.318.0.123
INFORMATIONAL: External Switch Gear closed.
externalSwitchGearOpened
.1.3.6.1.4.1.318.0.124
INFORMATIONAL: External Switch Gear opened.
generalDeviceEvent
.1.3.6.1.4.1.318.0.125
INFORMATIONAL: APC Device event.
atsSourceSwitched
.1.3.6.1.4.1.318.0.126
INFORMATIONAL: The Automatic Transfer Switch has switched source.
The first variable is an integer representing the current source: 0=A, 1=B.
The second variable is the 32-character name of the current source.
atsLostRedundancy
.1.3.6.1.4.1.318.0.127
SEVERE: The Automatic Transfer Switch has lost redundancy. The first variable is an integer representing the source which is no longer available: 0=A, 1=B. The second variable is the 32-character name of the source which is no longer available.
atsRedundancyRestored
.1.3.6.1.4.1.318.0.128
INFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch.
The first variable is an integer representing the source which has been restored: 0=A, 1=B.
The second variable is the 32-character name of the source which has been restored.
atsConfigChange
.1.3.6.1.4.1.318.0.129
INFORMATIONAL: A configuration change has been made on the Automatic Transfer Switch.
The first variable is an integer representing the configuration setting which changed:
0=Transfer Voltage Range, 1=Sensitivity, 2=Preferred Source
3=Front Panel Lockout, 4=Current Limit, 5=Reset XA Processor,
6=Reset to defaults, 7=Product Name, 8=Nominal Voltage, 9=Nominal Line Frequency,
10=Narrow VRMS, 11=Medium VRMS, 12=Wide VRMS,13=Frequency Deviation,
14=ColdStart ATS, 15=Events Count Cleared, 16=Phase or Bank Threshold.
upsSleeping
.1.3.6.1.4.1.318.0.13
WARNING: The UPS is entering 'sleep' mode. Power
to the load will be cut off.
atsCommunicationEstablished
.1.3.6.1.4.1.318.0.130
INFORMATIONAL: Communications with the Automatic Transfer Switch has been established.
atsCommunicationLost
.1.3.6.1.4.1.318.0.131
SEVERE: Communications with the Automatic Transfer Switch has been lost.
atsOverCurrent
.1.3.6.1.4.1.318.0.132
SEVERE: Output Current has exceeded threshold. This is same as atsOverload Trap
for phase or total in case banked units
atsOverCurrentCleared
.1.3.6.1.4.1.318.0.133
INFORMATIONAL: Output Current has returned below threshold.This is same as atsOverloadCleared Trap
for phase or total in case banked units
atsPowerSupplyFailure
.1.3.6.1.4.1.318.0.134
SEVERE: The Automatic Transfer Switch Power Supply has failed.
The first variable is an integer representing the Power Supply which
has failed: 0 = Source A 24V,
1 = 12V,
2 = 5V,
3 = Source B 24V.
atsPowerSupplyFailureCleared
.1.3.6.1.4.1.318.0.135
INFORMATIONAL: The Automatic Transfer Power Supply Failure Cleared.
The first variable is an integer representing the Power Supply which
has cleared: 0 = Source A 24V,
1 = 12V,
2 = 5V,
3 = Source B 24V.
dcMainsFailAlarm
.1.3.6.1.4.1.318.0.136
WARNING: A Mains Fail alarm is active in the DC power plant.
dcMainsFailAlarmCleared
.1.3.6.1.4.1.318.0.137
INFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant.
dcFanFailAlarm
.1.3.6.1.4.1.318.0.138
WARNING: A Fan Fail alarm is active in the DC power plant.
dcFanFailAlarmCleared
.1.3.6.1.4.1.318.0.139
INFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant.
upsWokeUp
.1.3.6.1.4.1.318.0.14
INFORMATION: The UPS has returned from 'sleep' mode. Power
to the load has been restored.
dcRectifierOvertempAlarm
.1.3.6.1.4.1.318.0.140
WARNING: Rect. Overtemp alarm is active in the power plant.
dcRectifierOvertempAlarmCleared
.1.3.6.1.4.1.318.0.141
INFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant.
dcCurrentLimitAlarm
.1.3.6.1.4.1.318.0.142
WARNING: A Current Limit alarm is active in the power plant.
dcCurrentLimitAlarmCleared
.1.3.6.1.4.1.318.0.143
INFORMATIONAL: Current Limit alarm is no longer active in the power plant.
dcRectifierFailAlarm
.1.3.6.1.4.1.318.0.144
WARNING: A Rect. Fail alarm is active in the power plant.
dcRectifierFailAlarmCleared
.1.3.6.1.4.1.318.0.145
INFORMATIONAL: Rect. Fail alarm is no longer active in the power plant.
dcMultRectFailAlarm
.1.3.6.1.4.1.318.0.146
WARNING: Multiple Rect. Fail alarm is active in the powerplant.
dcMultRectFailAlarmCleared
.1.3.6.1.4.1.318.0.147
INFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant.
dcBatteryBreakerAlarm
.1.3.6.1.4.1.318.0.148
WARNING: Batt. Breaker alarm is active in the power plant.
dcBatteryBreakerAlarmCleared
.1.3.6.1.4.1.318.0.149
INFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant.
upsRebootStarted
.1.3.6.1.4.1.318.0.15
WARNING: The UPS has started its reboot sequence.
The UPS will reboot itself at this time.
dcRectifierOVPAlarm
.1.3.6.1.4.1.318.0.150
WARNING: A Rect. OVP alarm is active in the power plant.
dcRectifierOVPAlarmCleared
.1.3.6.1.4.1.318.0.151
INFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant.
dcLVDImminentAlarm
.1.3.6.1.4.1.318.0.152
WARNING: A LVD Imminent alarm is active in the powerplant.
dcLVDImminentAlarmCleared
.1.3.6.1.4.1.318.0.153
INFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant.
dcFuseCBAlarm
.1.3.6.1.4.1.318.0.154
WARNING: A Fuse/CB alarm is active in the DC power plant.
dcFuseCBAlarmCleared
.1.3.6.1.4.1.318.0.155
INFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant.
dcBatteryTestFail
.1.3.6.1.4.1.318.0.156
WARNING: A Battery Test failed in the DC power plant.
dcTemperatureAlarm
.1.3.6.1.4.1.318.0.157
WARNING: A Temperature is active in the power plant.
dcTemperatureAlarmCleared
.1.3.6.1.4.1.318.0.158
INFORMATIONAL: A Temperature alarm is no longer active in the power plant.
dcHumidityAlarm
.1.3.6.1.4.1.318.0.159
WARNING: A Humidity alarm is active in the DC power plant.
upsDipSwitchChanged
.1.3.6.1.4.1.318.0.16
WARNING: The dip switch settings on the UPS have been
changed, possibly altering UPS performance.
dcHumidityAlarmCleared
.1.3.6.1.4.1.318.0.160
INFORMATIONAL: A Humidity alarm is no longer active in the DC power plant.
dcBBCommunicationEstablished
.1.3.6.1.4.1.318.0.161
INFORMATIONAL: Power plant bridging board communications established.
dcBBCommunicationLost
.1.3.6.1.4.1.318.0.162
SEVERE: Power plant bridging board communications lost.
iemHighTempThresholdViolation
.1.3.6.1.4.1.318.0.163
SEVERE: High temperature threshold violated on Integrated
Environmental Monitor probe. The first variable is the
current temperature. The second variable is the temperature
scale. The third variable is the probe number. The fourth
variable is the probe name.
iemHighTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.164
INFORMATIONAL: High temperature threshold violated on Integrated
Environmental Monitor probe has been cleared. The first variable
is the probe number. The second variable is the probe name.
iemLowTempThresholdViolation
.1.3.6.1.4.1.318.0.165
SEVERE: Low temperature threshold violated on integrated
probe. The first variable is the current temperature. The
second variable is the temperature scale. The third
variable is the probe number. The fourth variable is the
probe name.
iemLowTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.166
INFORMATIONAL: Low temperature threshold violated on integrated
probe has been cleared. The first variable is the probe number.
The second variable is the probe name.
iemHighHumidThresholdViolation
.1.3.6.1.4.1.318.0.167
SEVERE: High humidity threshold violated on integrated
probe. The first variable is the current humidity. The
second variable is the probe number. The third variable
is the probe name.
iemHighHumidThresholdViolationCleared
.1.3.6.1.4.1.318.0.168
INFORMATIONAL: High humidity threshold violated on integrated
probe cleared. The first variable is the probe number. The second
variable is the probe name.
iemLowHumidThresholdViolation
.1.3.6.1.4.1.318.0.169
SEVERE: Low humidity threshold violated on integrated
probe. The first variable is the current humidity. The
second variable is the probe number. The third variable
is the probe name.
upsBatteryNeedsReplacement
.1.3.6.1.4.1.318.0.17
SEVERE: The batteries of the UPS need immediate replacement.
iemLowHumidThresholdViolationCleared
.1.3.6.1.4.1.318.0.170
INFORMATIONAL: Low humidity threshold violated on integrated
probe cleared. The first variable is the probe number. The second
variable is the probe name.
iemProbeDisconnected
.1.3.6.1.4.1.318.0.171
WARNING: The temperature/humidity probe on the Integrated
Environmental Monitor has been disconnected. This trap is
generated when a probe that has been in communication with
the Environmental Monitor has been disconnected or can no
longer communicate.
iemProbeConnected
.1.3.6.1.4.1.318.0.172
INFORMATIONAL: The temperature/humidity probe on the Integrated
Environmental Monitor has been connected. This trap is generated
when the Environmental Monitor establishes communication with a
probe that had previously not been connected.
iemContactFault
.1.3.6.1.4.1.318.0.173
SEVERE: There is a contact fault on the Integrated
Environmental Monitor. The first argument is the number
of the contact. The second argument is the name of the
contact.
iemContactFaultCleared
.1.3.6.1.4.1.318.0.174
INFORMATIONAL: The contact fault on the Integrated
Environmental Monitor has been cleared. The first
argument is the number of the contact. The second
argument is the name of the contact.
iemRelayFault
.1.3.6.1.4.1.318.0.175
SEVERE: The output relay on the Integrated Environmental
Monitor has switched to the fault state. The first
argument is the number of the output relay. The second
argument is the name of the output relay. The third
argument is the event that caused the fault.
iemRelayFaultCleared
.1.3.6.1.4.1.318.0.176
INFORMATIONAL: The fault condition on the output relay on the
Integrated Environmental Monitor has cleared. The first
argument is the number of the output relay. The second
argument is the name of the output relay.
bmBatManCommEstab
.1.3.6.1.4.1.318.0.177
INFORMATIONAL: Serial Communications Established with Battery Manager.
bmBatManCommLost
.1.3.6.1.4.1.318.0.178
SEVERE: Serial Communications Lost with Battery Manager.
bmBatManKneeAlarm
.1.3.6.1.4.1.318.0.179
SEVERE: Battery Voltage Knee Threshold Alarm Detected.
contactFault
.1.3.6.1.4.1.318.0.18
SEVERE: One of the contacts on the Environmental Monitor has
changed from its default position. The first variable is
the contact number that is faulted.
bmBatManKneeAlarmCleared
.1.3.6.1.4.1.318.0.180
INFORMATIONAL: Battery Voltage Knee Threshold Alarm Cleared.
bmBatManChargerAlarm
.1.3.6.1.4.1.318.0.181
WARNING: Charger Alarm Detected.
bmBatManChargerAlarmCleared
.1.3.6.1.4.1.318.0.182
INFORMATIONAL: Charger Alarm Cleared.
bmBatManBatteryAlarm
.1.3.6.1.4.1.318.0.183
WARNING: Battery Alarm Detected.
bmBatManBatteryAlarmCleared
.1.3.6.1.4.1.318.0.184
INFORMATIONAL: Battery Alarm Cleared.
bmBatManEnvironmentAlarm
.1.3.6.1.4.1.318.0.185
WARNING: Environment Alarm Detected.
bmBatManEnvironmentAlarmCleared
.1.3.6.1.4.1.318.0.186
INFORMATIONAL: Environment Alarm Cleared.
bmBatManMaintenanceAlarm
.1.3.6.1.4.1.318.0.187
INFORMATIONAL: Maintenance Alarm Detected.
bmBatManMaintenanceAlarmCleared
.1.3.6.1.4.1.318.0.188
INFORMATIONAL: Maintenance Alarm Cleared.
pduCommunicationEstablished
.1.3.6.1.4.1.318.0.189
INFORMATIONAL: Communication Established.
The first argument is the serial number.
The second argument is the device name.
contactFaultResolved
.1.3.6.1.4.1.318.0.19
INFORMATIONAL: A fault on one of the Environmental Monitor contacts
has been resolved. The first variable is
the contact number that has been resolved.
pduCommunicationLost
.1.3.6.1.4.1.318.0.190
SEVERE: Communication Lost.
The first argument is the serial number.
The second argument is the device name.
pduUtilityLineUndervoltage
.1.3.6.1.4.1.318.0.191
SEVERE: Utility Line Undervoltage.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduUtilityLineUndervoltageCleared
.1.3.6.1.4.1.318.0.192
INFORMATIONAL: Utility Line Undervoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduUtilityLineOvervoltage
.1.3.6.1.4.1.318.0.193
SEVERE: Utility Line Overvoltage.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduUtilityLineOvervoltageCleared
.1.3.6.1.4.1.318.0.194
INFORMATIONAL: Utility Line Overvoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduGroundOvercurrent
.1.3.6.1.4.1.318.0.195
SEVERE: Ground Overcurrent.
The first argument is the serial number.
The second argument is the device name.
pduGroundOvercurrentCleared
.1.3.6.1.4.1.318.0.196
INFORMATIONAL: Ground Overcurrent Cleared.
The first argument is the serial number.
The second argument is the device name.
pduCircuitPanelInputUndervoltage
.1.3.6.1.4.1.318.0.197
SEVERE: Circuit Panel Input Undervoltage.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputUndervoltageCleared
.1.3.6.1.4.1.318.0.198
INFORMATIONAL: Circuit Panel Input Undervoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputOvervoltage
.1.3.6.1.4.1.318.0.199
SEVERE: Circuit Panel Input Overvoltage.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
upsOverload
.1.3.6.1.4.1.318.0.2
SEVERE: The UPS has sensed a load greater than 100 percent
of its rated capacity.
hardwareFailureBypass
.1.3.6.1.4.1.318.0.20
SEVERE: UPS on bypass due to internal fault
pduCircuitPanelInputOvervoltageCleared
.1.3.6.1.4.1.318.0.200
INFORMATIONAL: Circuit Panel Input Overvoltage Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputUndercurrent
.1.3.6.1.4.1.318.0.201
SEVERE: Circuit Panel Input Undercurrent.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputUndercurrentCleared
.1.3.6.1.4.1.318.0.202
INFORMATIONAL: Circuit Panel Input Undercurrent Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputOvercurrent
.1.3.6.1.4.1.318.0.203
SEVERE: Circuit Panel Input Overcurrent.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelInputOvercurrentCleared
.1.3.6.1.4.1.318.0.204
INFORMATIONAL: Circuit Panel Input Overcurrent Cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduCircuitPanelFrequencyOutOfRange
.1.3.6.1.4.1.318.0.205
SEVERE: Circuit Panel Input Frequency Out Of Range.
The first argument is the serial number.
The second argument is the device name.
pduCircuitPanelFrequencyOutofRangeCleared
.1.3.6.1.4.1.318.0.206
INFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range.
The first argument is the serial number.
The second argument is the device name.
pduCircuitPanelNeutralOvercurrent
.1.3.6.1.4.1.318.0.207
SEVERE: Circuit Panel Input Neutral Overcurrent.
The first argument is the serial number.
The second argument is the device name.
pduCircuitPanelNeutralOvercurrentCleared
.1.3.6.1.4.1.318.0.208
INFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared.
The first argument is the serial number.
The second argument is the device name.
pduSystemOff
.1.3.6.1.4.1.318.0.209
SEVERE: PDU System Off.
The first argument is the serial number.
The second argument is the device name.
softwareBypass
.1.3.6.1.4.1.318.0.21
WARNING: UPS on bypass - user set via software or panel
pduOnBatteryMode
.1.3.6.1.4.1.318.0.210
SEVERE: PDU is in On Battery Mode.
The first argument is the serial number.
The second argument is the device name.
pduMaintenanceBypassMode
.1.3.6.1.4.1.318.0.211
INFORMATIONAL: PDU is in Maintenance Bypass Mode.
The first argument is the serial number.
The second argument is the device name.
pduAtypicalBypassMode
.1.3.6.1.4.1.318.0.212
WARNING: PDU is in Atypical Bypass Mode.
The first argument is the serial number.
The second argument is the device name.
pduNoPanelFeedMode
.1.3.6.1.4.1.318.0.213
SEVERE: PDU is in No Panel Feed Mode.
The first argument is the serial number.
The second argument is the device name.
pduUpsOperationMode
.1.3.6.1.4.1.318.0.214
INFORMATIONAL: PDU is in Ups Operation Mode.
The first argument is the serial number.
The second argument is the device name.
pduForcedBypassMode
.1.3.6.1.4.1.318.0.215
WARNING: PDU is in Forced Bypass Mode.
The first argument is the serial number.
The second argument is the device name.
pduInputTransformerOverTemperature
.1.3.6.1.4.1.318.0.216
SEVERE: Input Transformer Over Temperature.
The first argument is the serial number.
The second argument is the device name.
pduInputTransformerOverTemperatureCleared
.1.3.6.1.4.1.318.0.217
INFORMATIONAL: Input Transformer Over Temperature Cleared.
The first argument is the serial number.
The second argument is the device name.
pduUPSInputVoltageLost
.1.3.6.1.4.1.318.0.218
SEVERE: UPS Input Voltage phase-N Lost.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
pduUPSInputVoltageRestored
.1.3.6.1.4.1.318.0.219
INFORMATIONAL: UPS Input Voltage phase-N Restored.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
switchedBypass
.1.3.6.1.4.1.318.0.22
WARNING: UPS on bypass - initiated by user
pduContactFault
.1.3.6.1.4.1.318.0.220
SEVERE: A contact closure in the PDU is in an abnormal position.
The first argument is the serial number.
The second argument is the device name.
The third argument is the number of the contact.
pduContactFaultCleared
.1.3.6.1.4.1.318.0.221
INFORMATIONAL: A contact closure in the PDU is in a normal position.
The first argument is the serial number.
The second argument is the device name.
The third argument is the number of the contact.
rPDUBankPhaseLowLoad
.1.3.6.1.4.1.318.0.222
WARNING: A bank or phase on the Rack PDU has violated the low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
rPDUBankPhaseLowLoadCleared
.1.3.6.1.4.1.318.0.223
INFORMATIONAL: The bank or phase low load condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
rPDUBankPhaseNearOverload
.1.3.6.1.4.1.318.0.224
WARNING: A bank or phase of the Rack PDU is near an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
rPDUBankPhaseNearOverloadCleared
.1.3.6.1.4.1.318.0.225
INFORMATIONAL: The bank or phase near overload condition on a Rack PDU has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
rPDUBankPhaseOverload
.1.3.6.1.4.1.318.0.226
SEVERE: A bank or phase of the Rack PDU is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
rPDUBankPhaseOverloadCleared
.1.3.6.1.4.1.318.0.227
INFORMATIONAL: The bank or phase overload condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the bank number (0 if this is phase data).
The fourth argument is the phase number (0 if this is bank data).
aruDeviceConfigChange
.1.3.6.1.4.1.318.0.228
INFORMATIONAL: Remote ARU Device Configuration change.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
rmPDUCommunicationLost
.1.3.6.1.4.1.318.0.229
SEVERE: Communication Lost.
The first argument is the serial number.
The second argument is the device name.
returnFromBypass
.1.3.6.1.4.1.318.0.23
INFORMATIONAL: UPS has returned from bypass
emsCommunicationEstablished
.1.3.6.1.4.1.318.0.230
INFORMATIONAL: Communication Established.
The first argument is the serial number.
The second argument is the device name.
emsCommunicationLost
.1.3.6.1.4.1.318.0.231
SEVERE: Communication Lost.
The first argument is the serial number.
The second argument is the device name.
emsProbeConnected
.1.3.6.1.4.1.318.0.232
INFORMATIONAL: A probe has been connected to the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the probe number.
The fourth argument is the probe name.
emsProbeDisconnected
.1.3.6.1.4.1.318.0.233
SEVERE: A probe has been disconnected from the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the probe number.
The fourth argument is the probe name.
emsSensorConnected
.1.3.6.1.4.1.318.0.234
INFORMATIONAL: A sensor has been connected to the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the sensor number.
The fourth argument is the sensor name.
emsSensorDisconnected
.1.3.6.1.4.1.318.0.235
SEVERE: A sensor has been disconnected from the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the sensor number.
The fourth argument is the sensor name.
emsSensorFault
.1.3.6.1.4.1.318.0.236
SEVERE: A EMS sensor is in the fault condition.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the sensor number.
The fourth argument is the sensor name.
emsSensorFaultCleared
.1.3.6.1.4.1.318.0.237
INFORMATIONAL: A EMS sensor fault condition has cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the sensor number.
The fourth argument is the sensor name.
emsBeaconConnected
.1.3.6.1.4.1.318.0.238
INFORMATIONAL: A beacon has been connected to the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
emsBeaconDisconnected
.1.3.6.1.4.1.318.0.239
SEVERE: A beacon has been disconnected from the EMS.
The first argument is the host device serial number.
The second argument is the host device name.
bypassPowerSupplyFailure
.1.3.6.1.4.1.318.0.24
SEVERE: Base module bypass power supply needs repair
emsBeaconOn
.1.3.6.1.4.1.318.0.240
INFORMATIONAL: A EMS beacon has gone on.
The first argument is the host device serial number.
The second argument is the host device name.
emsBeaconOff
.1.3.6.1.4.1.318.0.241
INFORMATIONAL: A EMS beacon has gone off.
The first argument is the host device serial number.
The second argument is the host device name.
emsMajorAlarm
.1.3.6.1.4.1.318.0.242
SEVERE: A Major Alarm is present in the EMS.
The first argument is the EMS serial number.
The second argument is the EMS name.
emsMajorAlarmCleared
.1.3.6.1.4.1.318.0.243
INFORMATIONAL: A Major Alarm condition has been cleared in the EMS.
The first argument is the EMS serial number.
The second argument is the EMS name.
emsMinorAlarm
.1.3.6.1.4.1.318.0.244
SEVERE: A Minor Alarm is present in the EMS.
The first argument is the EMS serial number.
The second argument is the EMS name.
emsMinorAlarmCleared
.1.3.6.1.4.1.318.0.245
INFORMATIONAL: A Minor Alarm condition has been cleared in the EMS.
The first argument is the EMS serial number.
The second argument is the EMS name.
emsOutletStateAbnormal
.1.3.6.1.4.1.318.0.246
WARNING: An outlet on the EMS has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
The fifth argument is the current outlet state (1=ON, 2=OFF).
The sixth argument is the configured normal outlet state (1=ON, 2=OFF).
emsOutletStateNormal
.1.3.6.1.4.1.318.0.247
INFORMATIONAL: An outlet on the EMS has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the outlet number.
The fourth argument is the outlet name.
The fifth argument is the current outlet state (1=ON, 2=OFF).
The sixth argument is the configured normal outlet state (1=ON, 2=OFF).
emsInputContactStateAbnormal
.1.3.6.1.4.1.318.0.248
WARNING: An input contact on the EMS has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
emsInputContactStateNormal
.1.3.6.1.4.1.318.0.249
INFORMATIONAL: An input contact on the EMS has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
The sixth argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
baseFanFailure
.1.3.6.1.4.1.318.0.25
SEVERE: Base module fan needs repair
emsOutputRelayStateAbnormal
.1.3.6.1.4.1.318.0.250
WARNING: An output relay on the EMS has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the output relay number.
The fourth argument is the output relay name.
The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN).
emsOutputRelayStateNormal
.1.3.6.1.4.1.318.0.251
INFORMATIONAL: An output relay on the EMS has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the output relay number.
The fourth argument is the output relay name.
The fifth argument is the current output relay state (1=CLOSED, 2=OPEN).
The sixth argument is the configured normal output relay state (1=CLOSED, 2=OPEN).
emsDeviceConfigChange
.1.3.6.1.4.1.318.0.252
INFORMATIONAL: A device configuration change has been made on the EMS.
The first argument is the EMS serial number.
The second argument is the EMS name.
envHighTempThresholdViolation
.1.3.6.1.4.1.318.0.253
SEVERE: High temperature threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envHighTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.254
INFORMATIONAL: High temperature threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLowTempThresholdViolation
.1.3.6.1.4.1.318.0.255
SEVERE: Low temperature threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLowTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.256
INFORMATIONAL: Low temperature threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envHighHumidityThresholdViolation
.1.3.6.1.4.1.318.0.257
SEVERE: High humidity threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity
The fourth argument is the probe number.
The fifth argument is the probe name.
envHighHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.258
INFORMATIONAL: High humidity threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity.
The fourth argument is the probe number.
The fifth argument is the probe name.
envLowHumidityThresholdViolation
.1.3.6.1.4.1.318.0.259
SEVERE: Low humidity threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity
The fourth argument is the probe number.
The fifth argument is the probe name.
batteryPackCommLost
.1.3.6.1.4.1.318.0.26
SEVERE: Check installation of external battery packs signal cable
envLowHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.260
INFORMATIONAL: Low humidity threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity.
The fourth argument is the probe number.
The fifth argument is the probe name.
rPDUCommunicationEstablished
.1.3.6.1.4.1.318.0.266
INFORMATIONAL: Communication with a Rack PDU has been established.
The first argument is the serial number.
The second argument is the device name.
rPDUCommunicationLost
.1.3.6.1.4.1.318.0.267
SEVERE: Communication with a Rack PDU has been lost.
The first argument is the serial number.
The second argument is the device name.
rPDUOutletOn
.1.3.6.1.4.1.318.0.268
INFORMATIONAL: An outlet on a Switched Rack PDU has turned on.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
rPDUOutletOff
.1.3.6.1.4.1.318.0.269
INFORMATIONAL: An outlet on a Switched Rack PDU has turned off.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
batteryPackCommEstablished
.1.3.6.1.4.1.318.0.27
INFORMATIONAL: UPS is communicating with the external battery packs.
rPDUDeviceConfigChange
.1.3.6.1.4.1.318.0.270
INFORMATIONAL: A device configuration change has been made on a
Rack PDU.
The first argument is the serial number.
The second argument is the device name.
rPDUOutletConfigChange
.1.3.6.1.4.1.318.0.271
INFORMATIONAL: An outlet configuration change has been made on a
Switched Rack PDU.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number.
The fourth argument is the outlet name.
rPDULowLoad
.1.3.6.1.4.1.318.0.272
WARNING: A Rack PDU has violated the low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDULowLoadCleared
.1.3.6.1.4.1.318.0.273
INFORMATIONAL: The low load condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDUNearOverload
.1.3.6.1.4.1.318.0.274
WARNING: A Rack PDU is near an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDUNearOverloadCleared
.1.3.6.1.4.1.318.0.275
INFORMATIONAL: The near overload condition on a Rack PDU has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDUOverload
.1.3.6.1.4.1.318.0.276
SEVERE: A Rack PDU is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDUOverloadCleared
.1.3.6.1.4.1.318.0.277
INFORMATIONAL: The overload condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase number.
rPDUPowerSupply1Fail
.1.3.6.1.4.1.318.0.278
SEVERE: Power Supply 1 on Rack PDU is in FAIL state.
The first argument is the serial number.
The second argument is the device name.
rPDUPowerSupply1Ok
.1.3.6.1.4.1.318.0.279
INFORMATIONAL: Power Supply 1 on Rack PDU is operating normally.
The first argument is the serial number.
The second argument is the device name.
calibrationStart
.1.3.6.1.4.1.318.0.28
INFORMATIONAL: A battery calibration test has been initiated on the UPS.
rPDUPowerSupply2Fail
.1.3.6.1.4.1.318.0.280
SEVERE: Power Supply 2 on Rack PDU is in FAIL state.
The first argument is the serial number.
The second argument is the device name.
rPDUPowerSupply2Ok
.1.3.6.1.4.1.318.0.281
INFORMATIONAL: Power Supply 2 on Rack PDU is operating normally.
The first argument is the serial number.
The second argument is the device name.
rPDUPhaseConfigChange
.1.3.6.1.4.1.318.0.282
INFORMATIONAL: A phase configuration change has been made on a
Rack PDU.
The first argument is the serial number.
The second argument is the device name.
The third argument is the phase index number.
rPDUCancelPendingCommand
.1.3.6.1.4.1.318.0.283
INFORMATIONAL: A cancel pending command has been made on a
Switched Rack PDU.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet index number (0 indicates all outlets).
The fourth argument is the outlet name (or device name if all outlets).
aruAlinkCommunicationEstablished
.1.3.6.1.4.1.318.0.284
INFORMATIONAL: Remote ARU Communication Established.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruAlinkCommunicationLost
.1.3.6.1.4.1.318.0.285
SEVERE: Remote ARU Communication Lost.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruFanFail
.1.3.6.1.4.1.318.0.286
SEVERE: Remote ARU Fan Fail.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruFanFailCleared
.1.3.6.1.4.1.318.0.287
INFORMATIONAL: Remote ARU Fan Fail Cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruSmokeAlarm
.1.3.6.1.4.1.318.0.288
SEVERE: Remote ARU Smoke Alarm.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruSmokeAlarmCleared
.1.3.6.1.4.1.318.0.289
INFORMATIONAL: Remote ARU Smoke Alarm Cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
restartAgent
.1.3.6.1.4.1.318.0.29
INFORMATIONAL: Agent restarting as commanded by manager.
aruHighTemperatureAlarm
.1.3.6.1.4.1.318.0.290
WARNING: ARU Exhaust temperature has exceeded the override
threshold and the ARU has increased fan speed to
maintain a safe environment in the rack.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruHighTemperatureAlarmCleared
.1.3.6.1.4.1.318.0.291
INFORMATIONAL: ARU temperature override state has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruExhaustTemperatureAlarm
.1.3.6.1.4.1.318.0.292
SEVERE: ARU Extreme Exhaust Temperature Alarm.
The ARU is unable to control the temperature within the rack
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruExhaustTemperatureAlarmCleared
.1.3.6.1.4.1.318.0.293
INFORMATIONAL: Remote ARU Exhaust Temperature Alarm Cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
envAlinkCommunicationEstablished
.1.3.6.1.4.1.318.0.294
INFORMATIONAL: Remote Probe Communication Established.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the probe number.
The fourth argument is the probe name.
envAlinkCommunicationLost
.1.3.6.1.4.1.318.0.295
SEVERE: Remote Probe Communication Lost.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the probe number.
The fourth argument is the probe name.
emsAlinkPowerOverload
.1.3.6.1.4.1.318.0.296
SEVERE: Alink Power Overload.
The first argument is the host device serial number.
The second argument is the host device name.
emsAlinkPowerOverloadCleared
.1.3.6.1.4.1.318.0.297
INFORMATIONAL: Alink Power Overload Cleared.
The first argument is the host device serial number.
The second argument is the host device name.
upsOutletGroupTurnedOn
.1.3.6.1.4.1.318.0.298
INFORMATIONAL: The specified Outlet Group turned on.
upsOutletGroupTurnedOff
.1.3.6.1.4.1.318.0.299
WARNING: The specified Outlet Group turned off.
upsDiagnosticsFailed
.1.3.6.1.4.1.318.0.3
SEVERE: The UPS failed its internal diagnostic self-test.
upsTurnedOn
.1.3.6.1.4.1.318.0.30
INFORMATIONAL: A UPS is turned on.
smwCriticalCondition
.1.3.6.1.4.1.318.0.300
SEVERE: A Symmetra MW UPS critical condition has been detected.
The first variable is the fault condition.
smwCriticalConditionCleared
.1.3.6.1.4.1.318.0.301
INFORMATIONAL: A Symmetra MW UPS critical condition has been cleared.
The first variable is the fault condition.
smwWarningCondition
.1.3.6.1.4.1.318.0.302
WARNING: A Symmetra MW UPS warning condition has been detected.
The first variable is the fault condition.
smwWarningConditionCleared
.1.3.6.1.4.1.318.0.303
WARNING: A Symmetra MW UPS warning condition has been cleared.
The first variable is the fault condition.
smwInformationalCondition
.1.3.6.1.4.1.318.0.304
INFORMATIONAL: A Symmetra MW UPS informational condition has been detected.
The first variable is the fault condition.
smwInformationalConditionCleared
.1.3.6.1.4.1.318.0.305
INFORMATIONAL: A Symmetra MW UPS informational condition has been cleared.
The first variable is the fault condition.
airCriticalCondition
.1.3.6.1.4.1.318.0.306
SEVERE: An Air critical condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
airCriticalConditionCleared
.1.3.6.1.4.1.318.0.307
INFORMATIONAL: An Air critical condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
airWarningCondition
.1.3.6.1.4.1.318.0.308
WARNING: An Air warning condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
airWarningConditionCleared
.1.3.6.1.4.1.318.0.309
WARNING: An Air warning condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
smartAvrReducing
.1.3.6.1.4.1.318.0.31
WARNING: The UPS is reducing the line voltage via SmartTrim(TM).
airInformationalCondition
.1.3.6.1.4.1.318.0.310
INFORMATIONAL: An Air informational condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
airInformationalConditionCleared
.1.3.6.1.4.1.318.0.311
INFORMATIONAL: An Air informational condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
xPDUInputVoltageLowAlarm
.1.3.6.1.4.1.318.0.312
SEVERE: Three-phase input voltage to the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated.
xPDUInputVoltageLowAlarmCleared
.1.3.6.1.4.1.318.0.313
INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
xPDUInputVoltageHighAlarm
.1.3.6.1.4.1.318.0.314
SEVERE: Three-phase input voltage to the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated.
xPDUInputVoltageHighAlarmCleared
.1.3.6.1.4.1.318.0.315
INFORMATIONAL: Three-phase input voltage to the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
xPDUBypassVoltageLowAlarm
.1.3.6.1.4.1.318.0.316
SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated.
xPDUBypassVoltageLowAlarmCleared
.1.3.6.1.4.1.318.0.317
INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
xPDUBypassVoltageHighAlarm
.1.3.6.1.4.1.318.0.318
SEVERE: Three-phase bypass input voltage to the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated.
xPDUBypassVoltageHighAlarmCleared
.1.3.6.1.4.1.318.0.319
INFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
codeAuthenticationDone
.1.3.6.1.4.1.318.0.32
INFORMATIONAL: Authentication on agent code image is done.
xPDUOutputVoltageLowAlarm
.1.3.6.1.4.1.318.0.320
SEVERE: The three-phase output voltage of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated.
xPDUOutputVoltageLowAlarmCleared
.1.3.6.1.4.1.318.0.321
INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
xPDUOutputVoltageHighAlarm
.1.3.6.1.4.1.318.0.322
SEVERE: The three-phase output voltage of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, above which the alarm was generated.
xPDUOutputVoltageHighAlarmCleared
.1.3.6.1.4.1.318.0.323
INFORMATIONAL: The three-phase output voltage of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N).
The fourth argument is the measured voltage in tenths of Volts.
xPDUOutputCurrentLowAlarm
.1.3.6.1.4.1.318.0.324
SEVERE: The three-phase output load current of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
xPDUOutputCurrentLowAlarmCleared
.1.3.6.1.4.1.318.0.325
INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in tenths of Amps.
xPDUOutputCurrentHighAlarm
.1.3.6.1.4.1.318.0.326
SEVERE: The three-phase load current of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated.
xPDUOutputCurrentHighAlarmCleared
.1.3.6.1.4.1.318.0.327
INFORMATIONAL: The three-phase output current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in tenths of Amps.
xPDUOutputFrequencyAlarm
.1.3.6.1.4.1.318.0.328
SEVERE: The devices output frequency is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the frequency deviation from the nominal in tenths of Hertz.
xPDUOutputFrequencyAlarmCleared
.1.3.6.1.4.1.318.0.329
INFORMATIONAL: The devices output frequency is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
upsOverloadCleared
.1.3.6.1.4.1.318.0.33
INFORMATIONAL: The overload condition has been cleared.
xPDUSystemGroundCurrentAlarm
.1.3.6.1.4.1.318.0.330
SEVERE: The earth ground current of the device is over the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured current in tenths of Amps.
The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated.
xPDUSystemGroundCurrentAlarmCleared
.1.3.6.1.4.1.318.0.331
INFORMATIONAL: The earth ground current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured current in tenths of Amps.
xPDUInputContactStateAbnormal
.1.3.6.1.4.1.318.0.332
SEVERE: A user input contact on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED).
xPDUInputContactStateNormal
.1.3.6.1.4.1.318.0.333
INFORMATIONAL: A user input contact on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=CLOSED, 2=OPEN).
The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED).
xPDUOutputNeutralCurrentHighAlarm
.1.3.6.1.4.1.318.0.334
WARNING: The three-phase neutral current of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured current in tenths of Amps.
The fourth argument is the threshold, in tenths of Amps, above which the alarm was generated.
xPDUOutputNeutralCurrentHighAlarmCleared
.1.3.6.1.4.1.318.0.335
INFORMATIONAL: The output neutral current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured current in tenths of Amps.
xPDUCoolingFanAlarm
.1.3.6.1.4.1.318.0.336
SEVERE: The device's internal cooling fans have failed.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUCoolingFanAlarmCleared
.1.3.6.1.4.1.318.0.337
INFORMATIONAL: The device's cooling fans are now functioning properly.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUTransformerTempAlarm
.1.3.6.1.4.1.318.0.338
SEVERE: The device's isolation transformer is over temperature.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUTransformerTempAlarmCleared
.1.3.6.1.4.1.318.0.339
INFORMATIONAL: The device's isolation transformer is no longer over temperature.
The first argument is the host device serial number.
The second argument is the host device name.
smartBoostOff
.1.3.6.1.4.1.318.0.34
INFORMATIONAL: The UPS has returned from SmartBoost(TM).
xPDUBranchCurrentLowAlarm
.1.3.6.1.4.1.318.0.340
WARNING: The current in a branch circuit is outside the limits specified for that
branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
xPDUBranchCurrentLowAlarmCleared
.1.3.6.1.4.1.318.0.341
INFORMATIONAL: The current in a branch circuit is back within the limits
specified for that branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
xPDUBranchCurrentHighAlarm
.1.3.6.1.4.1.318.0.342
WARNING: The current in a branch circuit is outside the limits specified for that
branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated.
xPDUBranchCurrentHighAlarmCleared
.1.3.6.1.4.1.318.0.343
INFORMATIONAL: The current in a branch circuit is back within the limits
specified for that branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
xPDUInternalCommError
.1.3.6.1.4.1.318.0.344
SEVERE: There is an internal communication error in the device.
The first argument is the host device serial number.
The second argument is the host device name.
emsHardwareStateAbnormal
.1.3.6.1.4.1.318.0.345
SEVERE: The device's hardware is improperly configured and operating outside
normal bounds for the hardware. This can be caused by improper devices being
connected to the EMS ports or Alink Current limit detection.
emsHardwareStateNormal
.1.3.6.1.4.1.318.0.346
INFORMATIONAL: The device's hardware is in its normal operational state.
The first argument is the host device serial number.
ceSevereCondition
.1.3.6.1.4.1.318.0.347
SEVERE: A Custom Event severe condition was detected.
The first variable is the custom event text message.
The second variable is the custom event number.
ceSevereConditionCleared
.1.3.6.1.4.1.318.0.348
INFORMATIONAL: A Custom Event severe condition was cleared.
The first variable is the custom event text message.
The second variable is the custom event number.
ceWarningCondition
.1.3.6.1.4.1.318.0.349
WARNING: A Custom Event warning condition was detected.
The first variable is the custom event text message.
The second variable is the custom event number.
smartAvrReducingOff
.1.3.6.1.4.1.318.0.35
INFORMATIONAL: The UPS has returned from SmartTrim(TM).
ceWarningConditionCleared
.1.3.6.1.4.1.318.0.350
INFORMATIONAL: A Custom Event warning condition was cleared.
The first variable is the custom event text message.
The second variable is the custom event number.
ceInformationalCondition
.1.3.6.1.4.1.318.0.351
INFORMATIONAL: A Custom Event informational condition was detected.
The first variable is the custom event text message.
The second variable is the custom event number.
ceInformationalConditionCleared
.1.3.6.1.4.1.318.0.352
INFORMATIONAL: A Custom Event informational condition was cleared.
The first variable is the custom event text message.
The second variable is the custom event number.
upsInternalOverTemperature
.1.3.6.1.4.1.318.0.353
WARNING: The internal over temperature condition exists.
upsInternalOverTemperatureCleared
.1.3.6.1.4.1.318.0.354
INFORMATIONAL: The internal over temperature condition cleared.
upsMpuReset
.1.3.6.1.4.1.318.0.355
INFORMATIONAL: The MPU has been reset.
upsOutputSwitchClosed
.1.3.6.1.4.1.318.0.356
INFORMATIONAL: The Output Switch is closed.
upsOutputSwitchOpened
.1.3.6.1.4.1.318.0.357
INFORMATIONAL: The Output Switch is open.
upsCalibrationStackChanged
.1.3.6.1.4.1.318.0.358
INFORMATIONAL: A calibration value in the stack was changed.
envMaxTempThresholdViolation
.1.3.6.1.4.1.318.0.359
SEVERE: Max temperature threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
upsBatteryReplaced
.1.3.6.1.4.1.318.0.36
INFORMATIONAL: A bad battery fault has been cleared.
envMaxTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.360
INFORMATIONAL: Max temperature threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envMinTempThresholdViolation
.1.3.6.1.4.1.318.0.361
SEVERE: Min temperature threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envMinTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.362
INFORMATIONAL: Min temperature threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envMaxHumidityThresholdViolation
.1.3.6.1.4.1.318.0.363
SEVERE: Max humidity threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity
The fourth argument is the probe number.
The fifth argument is the probe name.
envMaxHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.364
INFORMATIONAL: Max humidity threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity.
The fourth argument is the probe number.
The fifth argument is the probe name.
envMinHumidityThresholdViolation
.1.3.6.1.4.1.318.0.365
SEVERE: Min humidity threshold violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity
The fourth argument is the probe number.
The fifth argument is the probe name.
envMinHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.366
INFORMATIONAL: Min humidity threshold violation cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current humidity.
The fourth argument is the probe number.
The fifth argument is the probe name.
envSTIncTempRateViolation
.1.3.6.1.4.1.318.0.367
SEVERE: Short-term increasing temperature rate violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envSTIncTempRateViolationCleared
.1.3.6.1.4.1.318.0.368
INFORMATIONAL: Short-term increasing temperature rate cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envSTDecTempRateViolation
.1.3.6.1.4.1.318.0.369
SEVERE: Short-term decreasing temperature rate violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
calibrationEnd
.1.3.6.1.4.1.318.0.37
INFORMATIONAL: The UPS has finished calibrating.
envSTDecTempRateViolationCleared
.1.3.6.1.4.1.318.0.370
INFORMATIONAL: Short-term decreasing temperature rate cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLTIncTempRateViolation
.1.3.6.1.4.1.318.0.371
SEVERE: Long-term increasing temperature rate violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLTIncTempRateViolationCleared
.1.3.6.1.4.1.318.0.372
INFORMATIONAL: Long-term increasing temperature rate cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLTDecTempRateViolation
.1.3.6.1.4.1.318.0.373
SEVERE: Long-term decreasing temperature rate violated on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
envLTDecTempRateViolationCleared
.1.3.6.1.4.1.318.0.374
INFORMATIONAL: Long-term decreasing temperature rate cleared on the probe.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the current temperature.
The fourth argument is the temperature scale.
The fifth argument is the probe number.
The sixth argument is the probe name.
bmsCriticalCondition
.1.3.6.1.4.1.318.0.375
SEVERE: A Battery Management System critical condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
bmsCriticalConditionCleared
.1.3.6.1.4.1.318.0.376
INFORMATIONAL: A Battery Management System critical condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
bmsWarningCondition
.1.3.6.1.4.1.318.0.377
WARNING: A Battery Management System warning condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
bmsWarningConditionCleared
.1.3.6.1.4.1.318.0.378
WARNING: A Battery Management System warning condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
bmsInformationalCondition
.1.3.6.1.4.1.318.0.379
INFORMATIONAL: A Battery Management System informational condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
dischargeCleared
.1.3.6.1.4.1.318.0.38
INFORMATIONAL: A UPS discharge condition has been cleared.
bmsInformationalConditionCleared
.1.3.6.1.4.1.318.0.380
INFORMATIONAL: A Battery Management System informational condition was cleared.
The first variable is the error condition text message.
The second variable is the error number.
xATSOutputVoltageLowAlarm
.1.3.6.1.4.1.318.0.381
SEVERE: The device three-phase output voltage of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, from which the alarm was generated.
xATSOutputVoltageLowAlarmCleared
.1.3.6.1.4.1.318.0.382
INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
xATSOutputVoltageHighAlarm
.1.3.6.1.4.1.318.0.383
SEVERE: The device three-phase output voltage of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
The fifth argument is the threshold, in tenths of Volts, above which the alarm is generated.
xATSOutputVoltageHighAlarmCleared
.1.3.6.1.4.1.318.0.384
INFORMATIONAL: The devices three-phase output voltage is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1-N, 2=L2-N, 3=L3-N, 4=unused, 5=L1-L2, 6=L2-L3, 7=L3-L1).
The fourth argument is the measured voltage in tenths of Volts.
xATSOutputCurrentLowAlarm
.1.3.6.1.4.1.318.0.385
SEVERE: The three-phase load current of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in Amps.
The fifth argument is the threshold, in Amps, from which the alarm was generated.
xATSOutputCurrentLowAlarmCleared
.1.3.6.1.4.1.318.0.386
INFORMATIONAL: The three-phase load current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in Amps.
xATSOutputCurrentHighAlarm
.1.3.6.1.4.1.318.0.387
SEVERE: The three-phase output load current of the device is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in Amps.
The fifth argument is the threshold, in Amps, from which the alarm was generated.
xATSOutputCurrentHighAlarmCleared
.1.3.6.1.4.1.318.0.388
INFORMATIONAL: The three-phase output load current of the device is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
The fourth argument is the measured current in Amps.
xATSOutputFrequencyAlarm
.1.3.6.1.4.1.318.0.389
SEVERE: The devices output frequency is outside the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the frequency deviation from the nominal in tenths of Hertz.
The fourth argument is the frequency deviation threshold in tenths of Hertz,
from which the alarm was generated.
gracefulShutdown
.1.3.6.1.4.1.318.0.39
INFORMATIONAL: A graceful shutdown has been initiated.
xATSOutputFrequencyAlarmCleared
.1.3.6.1.4.1.318.0.390
INFORMATIONAL: The devices output frequency is back within the specified limits.
The first argument is the host device serial number.
The second argument is the host device name.
xATSInternalCommError
.1.3.6.1.4.1.318.0.391
SEVERE: There is an internal communication error in the device.
The first argument is the host device serial number.
The second argument is the host device name.
xATSInternalCommErrorCleared
.1.3.6.1.4.1.318.0.392
INFORMATIONAL: Internal communication has been restored.
The first argument is the host device serial number.
The second argument is the host device name.
xATSDataCommMismatchError
.1.3.6.1.4.1.318.0.393
SEVERE: A data incompatibility exists within the device. This
is typically the result of mismatches between firmware revisions
of the transfer switch controller and the Network Management interface.
The first argument is the host device serial number.
The second argument is the host device name.
xATSDataCommMismatchErrorCleared
.1.3.6.1.4.1.318.0.394
INFORMATIONAL: The internal data incompatibility has been resolved.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGenCommLost
.1.3.6.1.4.1.318.0.395
WARNING: The XATS cannot communicate with the generator.
This will make unavailable all the xATSGenerator OIDs.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGenCommEstablished
.1.3.6.1.4.1.318.0.396
INFORMATIONAL: The XATS has established communication with the generator.
The first argument is the host device serial number.
The second argument is the host device name.
xATSNeutralPosition
.1.3.6.1.4.1.318.0.397
WARNING: XATS has transferred to neutral position.
In this position neither Source 1 nor Source 2 is selected,
and the XATS will have no output voltage.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the mode in which the switch is operating
(1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual).
xATSSwitchTransferEvent
.1.3.6.1.4.1.318.0.398
INFORMATIONAL: XATS has transferred from one source to the other.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the mode in which the switch is operating.
(1=Auto, 2=Not-in-Auto, Abnormal Condition 3=Not-in-Auto, manual).
The fourth argument is the input source selected (1=Source 1, 2=Source 2).
The fifth argument is type of transfer that took place. (1=Closed, 2=Open, 3=Unknown)
xATSInternalATSFault
.1.3.6.1.4.1.318.0.399
SEVERE: An internal XATS fault has been detected.
The XATS may have forced itself to not-in-auto mode (abnormal condition),
as indicated by the xATSSwitchStatusAutoSwitchOperationalMode OID.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument indicates the detected fault.
1=Cannot Close S1
2=Cannot Close S2
3=Cannot Open S1
4=Cannot Open S2
5=Cannot Trip Open S1
6=Cannot Trip Open S2
7=Start Contact Failure
8=Voltage Sensing Failure
upsDischarged
.1.3.6.1.4.1.318.0.4
SEVERE: The UPS batteries are discharged; if utility power fails
an immediate low battery condition will exist. Sufficient runtime
for necessary action cannot be guaranteed.
xATSInternalATSFaultCleared
.1.3.6.1.4.1.318.0.400
INFORMATIONAL: The detected internal XATS fault has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument indicates the detected fault.
1=Cannot Close S1
2=Cannot Close S2
3=Cannot Open S1
4=Cannot Open S2
5=Cannot Trip Open S1
6=Cannot Trip Open S2
7=Start Contact Failure
8=Voltage Sensing Failure
xATSEngineStartAsserted
.1.3.6.1.4.1.318.0.401
INFORMATIONAL: The XATS has asserted the Engine Start contact.
This should result in the generator producing output voltage.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument indicates the reason that the start signal was asserted
1=Unknown, 2=S1 Low Voltage, 3=S1 High Voltage, 4=S1 Line Imbalance,
5=S1 Freq Range, 6=S1 Bad Rotation.
xATSEngineStopAsserted
.1.3.6.1.4.1.318.0.402
INFORMATIONAL: The XATS has de-asserted the Engine Start contact.
This should result in the generator shutting down, and producing no output voltage.
The first argument is the host device serial number.
The second argument is the host device name.
xATSStartFailure
.1.3.6.1.4.1.318.0.403
SEVERE: The generator failed to start. After assertion of the
Engine Start signal, the quality of Source 2 was not seen as good.
This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument indicates the line quality at S2
1=Unknown, 2=S2 Low Voltage, 3=S2 High Voltage, 4=S2 Line Imbalance,
4=S2 Freq Range, 5=S2 Bad Rotation.
xATSStopFailure
.1.3.6.1.4.1.318.0.404
WARNING: The generator failed to stop. After de-assertion of the
Engine Start signal, the quality of Source 2 continued to be seen as good.
This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
The first argument is the host device serial number.
The second argument is the host device name.
xATSNotInAutomaticMode
.1.3.6.1.4.1.318.0.405
SEVERE: Automatic Transfer Switch is not in automatic mode.
The first argument is the host device serial number.
The second argument is the host device name.
The xATSSwitchStatusAutoSwitchStatus OID and the
xATSSwitchStatusAutoSwitchOperationalMode OID
can provide more information about the state of the XATS.
xATSNotInAutomaticModeCleared
.1.3.6.1.4.1.318.0.406
INFORMATIONAL: Automatic Transfer Switch is in automatic mode.
The first argument is the host device serial number.
The second argument is the host device name.
xATSEpoTripped
.1.3.6.1.4.1.318.0.407
SEVERE: The device's Emergency Power Off (EPO) circuit is tripped.
The first argument is the host device serial number.
The second argument is the host device name.
xATSEpoReset
.1.3.6.1.4.1.318.0.408
INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
reset to the armed position.
The first argument is the host device serial number.
The second argument is the host device name.
xATSEpoTestMode
.1.3.6.1.4.1.318.0.409
WARNING: The device's Emergency Power Off (EPO) circuit has been
switched back to the test position.
The first argument is the host device serial number.
The second argument is the host device name.
outletOn
.1.3.6.1.4.1.318.0.41
WARNING: The specified PDU outlet has turned on.
If sPDUOutletControlIndex equals zero, then all outlets have
turned on.
xATSEpoArmed
.1.3.6.1.4.1.318.0.410
INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
switched back to the armed position.
The first argument is the host device serial number.
The second argument is the host device name.
xATSTestInitiated
.1.3.6.1.4.1.318.0.411
INFORMATIONAL: A scheduled test has been initiated.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the type of test initiated (1=scheduled, 2=manual).
xATSTestCanceled
.1.3.6.1.4.1.318.0.412
INFORMATIONAL: The scheduled test has been canceled
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the type of test initiated (1=scheduled, 2=manual).
xATSTestFailed
.1.3.6.1.4.1.318.0.413
SEVERE: The initiated test has failed.
This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID.
The first argument is the host device serial number.
The second argument is the host device name.
xATSTestPassed
.1.3.6.1.4.1.318.0.414
INFORMATIONAL: The initiated test has passed
switched back to the armed position.
The first argument is the host device serial number.
The second argument is the host device name.
xATSInputContactStateAbnormal
.1.3.6.1.4.1.318.0.415
SEVERE: A user input contact on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED).
xATSInputContactStateNormal
.1.3.6.1.4.1.318.0.416
INFORMATIONAL: A user input contact on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the input contact number.
The fourth argument is the input contact name.
The fifth argument is the input contact state (1=OPEN, 2=CLOSED).
The sixth argument is the configured normal input contact state (1=OPEN, 2=CLOSED).
xATSRemoteStartContactMismatch
.1.3.6.1.4.1.318.0.417
SEVERE: The state of the generator's Remote Start input
and the ATS's Engine Start output do not match.
This indicates something wrong in the Engine Start wiring,
which must be corrected. This condition will prevent the
generator from being started when needed.
(See also: xATSGeneratorStatusRemoteStart
and xATSSwitchStatusEngineStartSignal OIDs)
The first argument is the host device serial number.
The second argument is the host device name.
xATSRemoteStartContactMismatchCleared
.1.3.6.1.4.1.318.0.418
INFORMATIONAL: Mismatch in the state of the generator's
Remote Start input and the ATS's Engine Start output as been resolved.
This indicates something wrong in the Engine Start wiring,
which must be corrected. This condition will prevent the
generator from being started when needed.
(See also: xATSGeneratorStatusRemoteStart
and xATSSwitchStatusEngineStartSignal OIDs)
The first argument is the host device serial number.
The second argument is the host device name.
xATSDoorOpenAlarm
.1.3.6.1.4.1.318.0.419
WARNING: The XATS exterior panel door is open.
The first argument is the host device serial number.
The second argument is the host device name.
outletOff
.1.3.6.1.4.1.318.0.42
WARNING: The specified PDU outlet has turned off.
If sPDUOutletControlIndex equals zero, then all outlets
have turned off.
xATSDoorOpenAlarmCleared
.1.3.6.1.4.1.318.0.420
INFORMATIONAL: The external door to the device is closed.
The first argument is the host device serial number.
The second argument is the host device name.
xATSDCBackupAlarm
.1.3.6.1.4.1.318.0.421
WARNING: The XATS's DC backup has been lost. The XATS will lose power
on Source 1 failure, causing the Engine Start signal to be asserted.
The XATS will then restart from Source 2.
The first argument is the host device serial number.
The second argument is the host device name.
xATSDCBackupAlarmCleared
.1.3.6.1.4.1.318.0.422
INFORMATIONAL: DC backup alarm has been cleared in the device.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorLowCoolantLevelAlarm
.1.3.6.1.4.1.318.0.423
SEVERE: Low coolant level has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowCoolantLevelAlarmCleared
.1.3.6.1.4.1.318.0.424
INFORMATIONAL: The detected low coolant level has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorVeryLowCoolantLevelAlarm
.1.3.6.1.4.1.318.0.425
SEVERE: Very low coolant level has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorVeryLowCoolantLevelAlarmCleared
.1.3.6.1.4.1.318.0.426
INFORMATIONAL: The detected Very low coolant level has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorHighCoolantTempAlarm
.1.3.6.1.4.1.318.0.427
SEVERE: High coolant temperature has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorHighCoolantTempAlarmCleared
.1.3.6.1.4.1.318.0.428
INFORMATIONAL: The detected high coolant temperature has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorVeryHighCoolantTempAlarm
.1.3.6.1.4.1.318.0.429
SEVERE: Very high coolant temperature has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
outletReboot
.1.3.6.1.4.1.318.0.43
WARNING: The specified PDU outlet has rebooted.
If sPDUOutletControlIndex equals zero, then all outlets
have rebooted.
xATSGeneratorVeryHighCoolantTempAlarmCleared
.1.3.6.1.4.1.318.0.430
INFORMATIONAL: The Very high coolant temperature condition has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowCoolantTempAlarm
.1.3.6.1.4.1.318.0.431
WARNING: Low coolant temperature has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowCoolantTempAlarmCleared
.1.3.6.1.4.1.318.0.432
INFORMATIONAL: The low coolant temperature condition has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowOilLevelAlarm
.1.3.6.1.4.1.318.0.433
SEVERE: Low oil level has been detected in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowOilLevelAlarmCleared
.1.3.6.1.4.1.318.0.434
INFORMATIONAL: Low oil level alarm has been cleared in the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowBatteryVoltDuringCrankAlarm
.1.3.6.1.4.1.318.0.435
SEVERE: The generator's battery voltage has been detected
as low while cranking the engine.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
INFORMATIONAL: The generator's low battery voltage while
cranking condition has been cleared.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorVeryLowBatteryVoltDuringCrankAlarm
.1.3.6.1.4.1.318.0.437
SEVERE: The generator's battery voltage has been detected
as very low while cranking the engine.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
INFORMATIONAL: The generator's high battery voltage while
cranking condition has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorEStop
.1.3.6.1.4.1.318.0.439
SEVERE: The generator's emergency stop input has been activated.
After the emergency stop signal has been removed, the E-Stop condition
must be cleared before the generator can be started again.
E-Stop conditions can only be cleared via the generator front panel.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE).
configChangeSNMP
.1.3.6.1.4.1.318.0.44
WARNING: The SNMP configuration has been changed.
xATSGeneratorEStopCleared
.1.3.6.1.4.1.318.0.440
INFORMATIONAL: The generator's emergency stop condition has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
The fourth argument is the type of E-Stop (1=LOCAL, 2=REMOTE).
xATSGeneratorHighBatteryVolt
.1.3.6.1.4.1.318.0.441
WARNING: The generator's battery voltage has been detected as high.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorHighBatteryVoltCleared
.1.3.6.1.4.1.318.0.442
INFORMATIONAL: The detected high battery voltage has been cleared, on the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowBatteryVolt
.1.3.6.1.4.1.318.0.443
SEVERE: The generator's battery voltage has been detected as low.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowBatteryVoltCleared
.1.3.6.1.4.1.318.0.444
INFORMATIONAL: The detected low battery voltage has been cleared, on the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorControlSwitchNotAuto
.1.3.6.1.4.1.318.0.445
SEVERE: The control switch on the generator is not in auto position.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorControlSwitchNotAutoCleared
.1.3.6.1.4.1.318.0.446
INFORMATIONAL: The control switch on the generator is in auto position.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowOilPressure
.1.3.6.1.4.1.318.0.447
SEVERE: The generator's oil pressure has been detected as low.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowOilPressureCleared
.1.3.6.1.4.1.318.0.448
INFORMATIONAL: The detected low oil pressure has been cleared, on the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorVeryLowOilPressure
.1.3.6.1.4.1.318.0.449
SEVERE: The generator's oil pressure has been detected as very low.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
configChangeOutlet
.1.3.6.1.4.1.318.0.45
WARNING: The specified PDU outlet has changed configuration.
If sPDUOutletConfigIndex equals zero, then the Master outlet
has changed configuration.
xATSGeneratorVeryLowOilPressureCleared
.1.3.6.1.4.1.318.0.450
INFORMATIONAL: The detected v.low oil pressure has been cleared, on the generator.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOverload
.1.3.6.1.4.1.318.0.451
SEVERE: The generator is overloaded.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOverloadCleared
.1.3.6.1.4.1.318.0.452
INFORMATIONAL: The generator is running within loading limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowACVEvent
.1.3.6.1.4.1.318.0.453
SEVERE: The generator AC voltage is outside the acceptable bounds.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowACVEventCleared
.1.3.6.1.4.1.318.0.454
INFORMATIONAL: The generator AC voltage is within normal bounds.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorHighACVEvent
.1.3.6.1.4.1.318.0.455
SEVERE: The generator AC voltage is outside the acceptable bounds.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorHighACVEventCleared
.1.3.6.1.4.1.318.0.456
INFORMATIONAL: The generator AC voltage is within normal bounds.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOverspeed
.1.3.6.1.4.1.318.0.457
SEVERE: The generator is running over the acceptable RPM.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOverspeedCleared
.1.3.6.1.4.1.318.0.458
INFORMATIONAL: The generator overspeed shutdown has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorEngineCold
.1.3.6.1.4.1.318.0.459
SEVERE: The generator engine is cold, may not start.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
accessViolationConsole
.1.3.6.1.4.1.318.0.46
WARNING: Someone has attempted to login via the console with the incorrect password.
xATSGeneratorEngineColdCleared
.1.3.6.1.4.1.318.0.460
INFORMATIONAL: The engine is not cold to start.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOutputBreakerOpen
.1.3.6.1.4.1.318.0.461
SEVERE: The generators output breaker has been detected as open.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorOutputBreakerOpenCleared
.1.3.6.1.4.1.318.0.462
INFORMATIONAL: The engine is not cold to start.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorLowFuelLevelAlarm
.1.3.6.1.4.1.318.0.463
WARNING: The tank fuel level is below the limits specified
in the xATSGeneratorFuelSystemLowFuelLevelThreshold OID.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured fuel level in percent of full.
xATSGeneratorLowFuelLevelAlarmCleared
.1.3.6.1.4.1.318.0.464
INFORMATIONAL: The tank fuel level is back above the specified limit.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorVeryLowFuelLevelAlarm
.1.3.6.1.4.1.318.0.465
SEVERE: The tank fuel level is below the low threshold limits.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the measured tank fuel level in percent of full.
xATSGeneratorVeryLowFuelLevelAlarmCleared
.1.3.6.1.4.1.318.0.466
INFORMATIONAL: The detected low tank level has been cleared in the device.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorLowRunTimeAlarm
.1.3.6.1.4.1.318.0.467
WARNING: The estimated runtime is below the limits specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the estimated runtime in hours.
xATSGeneratorLowRunTimeAlarmCleared
.1.3.6.1.4.1.318.0.468
INFORMATIONAL: The detected low runtime has been cleared in the device.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorVeryLowRunTimeAlarm
.1.3.6.1.4.1.318.0.469
SEVERE: The estimated runtime is below the limits specified
in the xATSGeneratorFuelSystemVeryLowRunTimeThreshold OID.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the estimated runtime in hours.
accessViolationHTTP
.1.3.6.1.4.1.318.0.47
WARNING: Someone has attempted to login via HTTP with the incorrect password.
xATSGeneratorVeryLowRunTimeAlarmCleared
.1.3.6.1.4.1.318.0.470
INFORMATIONAL: The detected low runtime has been cleared in the device.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorServiceDueAlarm
.1.3.6.1.4.1.318.0.471
WARNING: The generator is due for scheduled service.
Generation of this alarm is based on calendar days since
and/or actual generator run-hours since last service.
This alarm is cleared using the xATSGeneratorServiceResetRecord OID.
(See also: xATSGeneratorServiceCalendarIntervalThreshold
and xATSGeneratorServiceRunHoursThreshold OIDs)
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorServiceDueAlarmCleared
.1.3.6.1.4.1.318.0.472
INFORMATIONAL: The generator's service registers have been reset.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorShutdown
.1.3.6.1.4.1.318.0.473
SEVERE: The generator is shutdown.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorShutdownCleared
.1.3.6.1.4.1.318.0.474
INFORMATIONAL: The generator shutdown alarm is cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorBatteryCharger
.1.3.6.1.4.1.318.0.475
SEVERE: The generator battery charger is nonfunctional.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorBatteryChargerCleared
.1.3.6.1.4.1.318.0.476
INFORMATIONAL: Fault in the generator battery charger is cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorGenericEvent
.1.3.6.1.4.1.318.0.477
WARNING: Any generic generator event.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorGenericEventCleared
.1.3.6.1.4.1.318.0.478
INFORMATIONAL: Generated generic generator event is cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xPDUInternalCommErrorCleared
.1.3.6.1.4.1.318.0.479
INFORMATIONAL: Internal communication has been restored.
The first argument is the host device serial number.
The second argument is the host device name.
passwordChange
.1.3.6.1.4.1.318.0.48
WARNING: The password for the device has been changed.
xPDUSystemStateAlarm
.1.3.6.1.4.1.318.0.480
SEVERE: The PDU's breakers (Q1, Q2 & Q3) are in a configuration that might lead
to system unavailability. it may signify a temporary condition, when the breakers
are placed in an atypical manner as the user transitions to (UPS OPERATION or MAINTENANCE BYPASS)
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass.
xPDUSystemStateAlarmCleared
.1.3.6.1.4.1.318.0.481
INFORMATIONAL: The PDU's breakers (Q1, Q2 & Q3) are set in a configuration
that is a non-alarm state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the type of state change (1=NO UPS INPUT, 2=NO PANEL FEED, 3=ATYPICAL BYPASS MODE).
note: The NO_PANEL_FEED alarm is applicable only for PDUs with system bypass.
xPDUEpoTestMode
.1.3.6.1.4.1.318.0.482
WARNING: The device's Emergency Power Off (EPO) circuit has been
switched back to the test position.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUEpoArmed
.1.3.6.1.4.1.318.0.483
INFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been
switched back to the armed position.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUFuseBlownAlarm
.1.3.6.1.4.1.318.0.484
SEVERE: One or more fuses in this PDU have been detected as open.
These fuses are in the feed to the UPS associated with this PDU.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
xPDUFuseBlownAlarmCleared
.1.3.6.1.4.1.318.0.485
INFORMATIONAL: A previous check fuse alarm in this PDU has cleared.
These fuses are in the feed to the UPS associated with this PDU.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase (1=L1, 2=L2, 3=L3).
xPDUBreakerPositionAlarm
.1.3.6.1.4.1.318.0.486
SEVERE: A PDU breaker is in a state that compromises system availability.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
note: The OUTPUT breaker position alarm is applicable only for PDUs with no system bypass.
The fourth argument is the breaker position (1=OPEN, 2=CLOSED).
xPDUBreakerPositionAlarmCleared
.1.3.6.1.4.1.318.0.487
INFORMATIONAL: A PDU breaker is no longer in a state that compromises system availability.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the breaker (1=MAIN INPUT, 2=BYPASS INPUT, 3=CROSS TIE, 4=OUTPUT).
note: The OUTPUT breaker position alarm cleared is applicable only for PDUs with no system bypass.
xPDUBreakerChangeEvent
.1.3.6.1.4.1.318.0.488
INFORMATIONAL: A system breaker or switch within the device has changed state.
They are generated when any of the Q1, Q2 or Q3 breakers have changed states.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the breaker that has changed
(1=UPS FEED (Q1), 2=UPS OUTPUT(Q2), 3=MAINTENANCE BYPASS (Q3).
The fourth argument is the state of the breaker that has changed (1=OPEN, 2=CLOSED).
The fifth argument is a 8-bit field representing the state of all breakers in the system,
when any of one of the Q1, Q2 or Q3 breakers have changed state.
The bit map is represented in the following manner (b7, b6 ... b0)
b0 - UPS FEED (Q1)
b1 - MAINTENANCE BYPASS (Q3)
b2 - UPS OUTPUT (Q2)
b3 - MAIN INPUT
b4 - BYPASS INPUT
b5 - CROSS-TIE OUTPUT
Example: value of 60 (0x3C) indicates that the CROSS_TIE, BYPASS and MAIN INPUT, and Q2 breakers
are CLOSED and Q3, Q1 breakers are OPEN.
xPDUDataCommMismatchError
.1.3.6.1.4.1.318.0.489
SEVERE: A data incompatibility exists within the device. This
is typically the result of mismatches between firmware revisions
of the transfer switch controller and the Network Management interface.
The first argument is the host device serial number.
The second argument is the host device name.
badVoltage
.1.3.6.1.4.1.318.0.49
WARNING: The output voltage is not within acceptable range.
xPDUDataCommMismatchErrorCleared
.1.3.6.1.4.1.318.0.490
INFORMATIONAL: The internal data incompatibility has been resolved.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUSystemInMaintenanceBypassMode
.1.3.6.1.4.1.318.0.491
WARNING: The PDU state has changed to maintenance bypass mode.
The first argument is the host device serial number.
The second argument is the host device name.
xPDUSystemInUPSOperationalMode
.1.3.6.1.4.1.318.0.492
INFORMATIONAL: The PDU state has changed to UPS operational mode.
The first argument is the host device serial number.
The second argument is the host device name.
xATSGeneratorFuelTankRuptureAlarm
.1.3.6.1.4.1.318.0.493
WARNING: Detected a rupture in the inner wall of the generator fuel tank.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorFuelTankRuptureAlarmCleared
.1.3.6.1.4.1.318.0.494
INFORMATIONAL: The rupture in the inner wall of the generator is not detected.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorGroundFaultAlarm
.1.3.6.1.4.1.318.0.495
SEVERE: Generator ground fault alarm.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSGeneratorGroundFaultAlarmCleared
.1.3.6.1.4.1.318.0.496
INFORMATIONAL: Generator ground fault alarm cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the OEM's fault/event code.
xATSOutputLoadPoweredByGeneratorAlarm
.1.3.6.1.4.1.318.0.497
WARNING: The system load on the output of the ATS is being powered by source 2 (generator).
The first argument is the host device serial number.
The second argument is the host device name.
The third argument indicates if the load is powered by the generator,
when 'load testing' the generator (1 = LIVE, 2 = TEST).
xATSOutputLoadPoweredByGeneratorAlarmCleared
.1.3.6.1.4.1.318.0.498
INFORMATIONAL: The system load on the output of the ATS is no longer being powered by source 2 (generator).
The first argument is the host device serial number.
The second argument is the host device name.
xAPCControllerFirmwareUpdateTransferStart
.1.3.6.1.4.1.318.0.499
INFORMATIONAL: Start controller firmware transfer in the device.
The first argument is the host device serial number.
The second argument is the host model name that initiated the transfer.
The third argument is the name of the file that is transferred.
The fourth argument is the updated revision of the file, if available
The fifth argument is the reason for the update, if available
(1=User request, 2=Automatic upgrade by NMC, 3=Unknown).
upsOnBattery
.1.3.6.1.4.1.318.0.5
WARNING: The UPS has switched to battery backup power.
badVoltageCleared
.1.3.6.1.4.1.318.0.50
INFORMATIONAL: The output voltage has returned to an acceptable level.
xAPCControllerFirmwareUpdateTransferComplete
.1.3.6.1.4.1.318.0.500
INFORMATIONAL: Transfer of controller firmware was completed in the device.
The first argument is the host device serial number.
The second argument is the host device model name that completed the transfer.
The third argument is the name of the file that was transferred.
The fourth argument is the revision of the file that was transferred, if available.
xAPCControllerFirmwareUpdateTransferFailed
.1.3.6.1.4.1.318.0.501
SEVERE: Transfer of controller firmware failed.
The first argument is the host device serial number.
The second argument is the host device model name that failed to transfer.
The third argument is the name of the file that failed the transfer, if available.
The fourth argument is the reason for failure.
upsPfcInputRelayFailure
.1.3.6.1.4.1.318.0.502
WARNING: The PFC (Power Factor Correction) input relay failure exists.
upsPfcInputRelayFailureCleared
.1.3.6.1.4.1.318.0.503
INFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared.
upsInverterOverTemperature
.1.3.6.1.4.1.318.0.504
WARNING: The inverter over temperature condition exists.
upsInverterOverTemperatureCleared
.1.3.6.1.4.1.318.0.505
INFORMATIONAL: The inverter over temperature condition cleared.
upsBatteryOverVoltage
.1.3.6.1.4.1.318.0.506
WARNING: The battery over voltage condition exists.
upsBatteryOverVoltageCleared
.1.3.6.1.4.1.318.0.507
INFORMATIONAL: The battery over voltage condition cleared.
upsEepromFault
.1.3.6.1.4.1.318.0.508
WARNING: The EEPROM fault exists.
upsEepromFaultCleared
.1.3.6.1.4.1.318.0.509
INFORMATIONAL: The EEPROM fault cleared.
chargerFailure
.1.3.6.1.4.1.318.0.51
WARNING: The battery charger has failed.
aruFanRuntimeAlarm
.1.3.6.1.4.1.318.0.510
WARNING: The total running hours for a fan has exceeded
the run hour threshold.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
The fifth argument indicates which fan in the ARU.
aruFanRuntimeAlarmCleared
.1.3.6.1.4.1.318.0.511
INFORMATIONAL: The total running hours for a fan is no longer
above the fan runhour threshold.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
The fifth argument indicates which fan in the ARU.
aruFanPoorPerformanceAlarm
.1.3.6.1.4.1.318.0.512
WARNING: Poor fan performance has been detected in the ARU,
indicating that the fan may be close to failing.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
The fifth argument indicates which fan in the ARU.
aruFanPoorPerformanceAlarmCleared
.1.3.6.1.4.1.318.0.513
INFORMATIONAL: Fan performance is no longer degraded.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
The fifth argument indicates which fan in the ARU.
aruRedundantPowerLostAlarm
.1.3.6.1.4.1.318.0.514
WARNING: One of the redundant line cords on the ARU is no longer receiving AC power.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
aruRedundantPowerLostAlarmCleared
.1.3.6.1.4.1.318.0.515
INFORMATIONAL: Line-cord redundancy has been restored to the ARU.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the ARU number.
The fourth argument is the ARU name.
apcDeviceConfigChange
.1.3.6.1.4.1.318.0.516
INFORMATIONAL: A device configuration change has been made on the device.
The first argument is the device serial number.
The second argument is the device name.
The third argument is a secondary device id number.
apcEnvSensorConnected
.1.3.6.1.4.1.318.0.517
INFORMATIONAL: A sensor has been connected to the host device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvSensorDisconnected
.1.3.6.1.4.1.318.0.518
SEVERE: A sensor has been disconnected from the device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMaxTempThresholdViolation
.1.3.6.1.4.1.318.0.519
SEVERE: Max temperature threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
chargerFailureCleared
.1.3.6.1.4.1.318.0.52
INFORMATIONAL: The battery charger failure condition has been cleared.
apcEnvMaxTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.520
INFORMATIONAL: Max temperature threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvHighTempThresholdViolation
.1.3.6.1.4.1.318.0.521
WARNING: High temperature threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvHighTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.522
INFORMATIONAL: High temperature threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLowTempThresholdViolation
.1.3.6.1.4.1.318.0.523
WARNING: Low temperature threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLowTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.524
INFORMATIONAL: Low temperature threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMinTempThresholdViolation
.1.3.6.1.4.1.318.0.525
SEVERE: Min temperature threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMinTempThresholdViolationCleared
.1.3.6.1.4.1.318.0.526
INFORMATIONAL: Min temperature threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The sixth argument is the sensor number.
The seventh argument is the sensor name.
apcEnvSTIncTempRateViolation
.1.3.6.1.4.1.318.0.527
SEVERE: Short-term increasing temperature rate violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvSTIncTempRateViolationCleared
.1.3.6.1.4.1.318.0.528
INFORMATIONAL: Short-term increasing temperature rate cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvSTDecTempRateViolation
.1.3.6.1.4.1.318.0.529
SEVERE: Short-term decreasing temperature rate violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
batteryOverTemperature
.1.3.6.1.4.1.318.0.53
WARNING: The battery temperature threshold has been violated.
apcEnvSTDecTempRateViolationCleared
.1.3.6.1.4.1.318.0.530
INFORMATIONAL: Short-term decreasing temperature rate cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLTIncTempRateViolation
.1.3.6.1.4.1.318.0.531
SEVERE: Long-term increasing temperature rate violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLTIncTempRateViolationCleared
.1.3.6.1.4.1.318.0.532
INFORMATIONAL: Long-term increasing temperature rate cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLTDecTempRateViolation
.1.3.6.1.4.1.318.0.533
SEVERE: Long-term decreasing temperature rate violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLTDecTempRateViolationCleared
.1.3.6.1.4.1.318.0.534
INFORMATIONAL: Long-term decreasing temperature rate cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMaxHumidityThresholdViolation
.1.3.6.1.4.1.318.0.535
SEVERE: Max humidity threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMaxHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.536
INFORMATIONAL: Max humidity threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvHighHumidityThresholdViolation
.1.3.6.1.4.1.318.0.537
WARNING: High humidity threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvHighHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.538
INFORMATIONAL: High humidity threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvLowHumidityThresholdViolation
.1.3.6.1.4.1.318.0.539
WARNING: Low humidity threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
batteryOverTemperatureCleared
.1.3.6.1.4.1.318.0.54
INFORMATIONAL: The battery over temperature has been cleared.
apcEnvLowHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.540
INFORMATIONAL: Low humidity threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMinHumidityThresholdViolation
.1.3.6.1.4.1.318.0.541
SEVERE: Min humidity threshold violated on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcEnvMinHumidityThresholdViolationCleared
.1.3.6.1.4.1.318.0.542
INFORMATIONAL: Min humidity threshold violation cleared on the sensor.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the sensor number.
The fifth argument is the sensor name.
apcBeaconConnected
.1.3.6.1.4.1.318.0.543
INFORMATIONAL: A beacon has been connected to the device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
apcBeaconDisconnected
.1.3.6.1.4.1.318.0.544
SEVERE: A beacon has been disconnected from the device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
apcBeaconOn
.1.3.6.1.4.1.318.0.545
INFORMATIONAL: A beacon has gone on (activated).
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
apcBeaconOff
.1.3.6.1.4.1.318.0.546
INFORMATIONAL: A beacon has gone off (deactivated).
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
apcOutletStateAbnormal
.1.3.6.1.4.1.318.0.547
WARNING: An outlet on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the outlet number.
The fifth argument is the outlet name.
The sixth argument is the current outlet state (1=ON, 2=OFF).
The seventh argument is the configured normal outlet state (1=ON, 2=OFF).
apcOutletStateNormal
.1.3.6.1.4.1.318.0.548
INFORMATIONAL: An outlet on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the outlet number.
The fifth argument is the outlet name.
The sixth argument is the current outlet state (1=ON, 2=OFF).
The seventh argument is the configured normal outlet state (1=ON, 2=OFF).
apcOutputRelayStateAbnormal
.1.3.6.1.4.1.318.0.549
WARNING: An output relay on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the output relay number.
The fifth argument is the output relay name.
The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN).
smartRelayFault
.1.3.6.1.4.1.318.0.55
WARNING: SmartBoost(TM) or SmartTrim(TM) relay fault.
apcOutputRelayStateNormal
.1.3.6.1.4.1.318.0.550
INFORMATIONAL: An output relay on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the output relay number.
The fifth argument is the output relay name.
The sixth argument is the current output relay state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal output relay state (1=CLOSED, 2=OPEN).
apcHardwareStateAbnormal
.1.3.6.1.4.1.318.0.551
SEVERE: The device's hardware is improperly configured and operating outside
normal bounds for the hardware. This can be caused by improper devices being
connected to device ports or Alink Current limit detection.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is a hardware specific state code.
apcHardwareStateNormal
.1.3.6.1.4.1.318.0.552
INFORMATIONAL: The device's hardware is in its normal operational state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
apcCriticalDiscreteInputContactStateAbnormal
.1.3.6.1.4.1.318.0.553
SEVERE: A discrete input contact on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcCriticalDiscreteInputContactStateNormal
.1.3.6.1.4.1.318.0.554
INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcWarningDiscreteInputContactStateAbnormal
.1.3.6.1.4.1.318.0.555
WARNING: A discrete input contact on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcWarningDiscreteInputContactStateNormal
.1.3.6.1.4.1.318.0.556
INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcInformationalDiscreteInputContactStateAbnormal
.1.3.6.1.4.1.318.0.557
INFORMATIONAL: A discrete input contact on the device has changed to its abnormal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcInformationalDiscreteInputContactStateNormal
.1.3.6.1.4.1.318.0.558
INFORMATIONAL: A discrete input contact on the device has changed to its normal state.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input contact number.
The fifth argument is the input contact name.
The sixth argument is the input contact state (1=CLOSED, 2=OPEN).
The seventh argument is the configured normal input contact state (1=CLOSED, 2=OPEN).
apcAnalogInputMaxThresholdViolation
.1.3.6.1.4.1.318.0.559
SEVERE: Maximum threshold violated on an analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
smartRelayFaultCleared
.1.3.6.1.4.1.318.0.56
INFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared.
apcAnalogInputMaxThresholdViolationCleared
.1.3.6.1.4.1.318.0.560
INFORMATIONAL: Maximum threshold violation cleared on the analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputHighThresholdViolation
.1.3.6.1.4.1.318.0.561
WARNING: High threshold violated on an analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputHighThresholdViolationCleared
.1.3.6.1.4.1.318.0.562
INFORMATIONAL: High threshold violation cleared on the analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputLowThresholdViolation
.1.3.6.1.4.1.318.0.563
WARNING: Low threshold violated on an analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputLowThresholdViolationCleared
.1.3.6.1.4.1.318.0.564
INFORMATIONAL: Low threshold violation cleared on the analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputMinThresholdViolation
.1.3.6.1.4.1.318.0.565
SEVERE: Minimum threshold violated on an analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcAnalogInputMinThresholdViolationCleared
.1.3.6.1.4.1.318.0.566
INFORMATIONAL: Minimum threshold violation cleared on the analog input.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is a secondary device id number.
The fourth argument is the input number.
The fifth argument is the input name.
apcDeviceClearLostComms
.1.3.6.1.4.1.318.0.567
INFORMATIONAL: Lost communications reset command has been issued.
The first argument is the device serial number.
The second argument is the device name.
The third argument is a secondary device id number.
apcDeviceConnected
.1.3.6.1.4.1.318.0.568
INFORMATIONAL: A device has been connected to the host.
The first argument is the host serial number.
The second argument is the host name.
The third argument is the device number.
The fourth argument is the device name.
apcDeviceDisconnected
.1.3.6.1.4.1.318.0.569
SEVERE: A device has been disconnected from the host.
The first argument is the host serial number.
The second argument is the host name.
The third argument is the device number.
The fourth argument is the device name.
humidityThresholdViolation1
.1.3.6.1.4.1.318.0.57
SEVERE: Probe 1 humidity threshold violated. The
first variable is the current humidity.
apcUnregisteredUserAccessDenied
.1.3.6.1.4.1.318.0.570
INFORMATIONAL: An unregistered user has tried to access the device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argumant is the door identifier.
The fifth argument is the unregistered user's RFID.
apcRegisteredUserAccessDenied
.1.3.6.1.4.1.318.0.571
INFORMATIONAL: A registered user has been denied access to the device.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argumant is the door identifier.
The fifth argument is the user name.
apcRegisteredUserConfigChange
.1.3.6.1.4.1.318.0.572
INFORMATIONAL: Registered user configuration change.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the user name.
apcDoorUnlocked
.1.3.6.1.4.1.318.0.573
INFORMATIONAL: A door has been unlocked.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier.
The fifth argument is the door access user.
The sixth argument is the door access type.
apcDoorLocked
.1.3.6.1.4.1.318.0.574
INFORMATIONAL: A door has been locked.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier.
The fifth argument is the door access user.
The sixth argument is the door access type.
apcHandleOpened
.1.3.6.1.4.1.318.0.575
INFORMATIONAL: A door handle has been opened.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcHandleClosed
.1.3.6.1.4.1.318.0.576
INFORMATIONAL: A door handle has been closed.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorOpened
.1.3.6.1.4.1.318.0.577
INFORMATIONAL: A door has been opened.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorClosed
.1.3.6.1.4.1.318.0.578
INFORMATIONAL: A door has been closed.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
humidityThresholdViolationCleared1
.1.3.6.1.4.1.318.0.58
INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 1.
apcKeyOverrideUnlocked
.1.3.6.1.4.1.318.0.580
SEVERE: Key override unlock has occurred.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcKeyOverrideLocked
.1.3.6.1.4.1.318.0.581
INFORMATIONAL: Key override lock has occurred.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcForcedEntry
.1.3.6.1.4.1.318.0.582
SEVERE: A forced entry condition has occurred.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcForcedEntryCleared
.1.3.6.1.4.1.318.0.583
INFORMATIONAL: A forced entry condition has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcRelockTimeout
.1.3.6.1.4.1.318.0.584
SEVERE: A relock timout has occurred.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcRelockTimeoutCleared
.1.3.6.1.4.1.318.0.585
INFORMATIONAL: A relock timout has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorSenseDisconnected
.1.3.6.1.4.1.318.0.586
SEVERE: A door sensor was disconnected.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorSenseConnected
.1.3.6.1.4.1.318.0.587
INFORMATIONAL: A forced entry condition has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorLostComms
.1.3.6.1.4.1.318.0.588
SEVERE: Communications have been lost with the door.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorEstablishedComms
.1.3.6.1.4.1.318.0.589
INFORMATIONAL: Communications have been established with the door.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
temperatureThresholdViolation1
.1.3.6.1.4.1.318.0.59
SEVERE: An Environmental Monitor temperature threshold has been violated on probe 1.
The first variable is the current temperature.
apcRegisteredUserAccessChange
.1.3.6.1.4.1.318.0.590
INFORMATIONAL: Registered user access changed.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the user name.
apcUnregisteredUserStatusChange
.1.3.6.1.4.1.318.0.591
INFORMATIONAL: Unregistered user status changed.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the user name.
apcDeviceClearUserConfigs
.1.3.6.1.4.1.318.0.592
INFORMATIONAL: User configurations reset command has been issued.
The first argument is the device serial number.
The second argument is the device name.
The third argument is a secondary device id number.
smartBoostOn
.1.3.6.1.4.1.318.0.6
WARNING: The UPS has enabled SmartBoost(TM).
temperatureThresholdViolationCleared1
.1.3.6.1.4.1.318.0.60
INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 1.
upsBatteryTempSensorFault
.1.3.6.1.4.1.318.0.600
WARNING: The battery temperature sensor fault exists.
upsBatteryTempSensorFaultCleared
.1.3.6.1.4.1.318.0.601
INFORMATIONAL: The battery temperature sensor fault cleared.
upsBatterySoftBusStartFault
.1.3.6.1.4.1.318.0.602
WARNING: A battery bus soft start fault exists.
upsBatterySoftBusStartFaultCleared
.1.3.6.1.4.1.318.0.603
INFORMATIONAL: A battery bus soft start fault exists cleared.
apcOutputShortCircuit
.1.3.6.1.4.1.318.0.604
WARNING: An output short circuit condition exists.
apcOutputShortCircuitCleared
.1.3.6.1.4.1.318.0.605
INFORMATIONAL: An output short circuit condition cleared.
apcOutputRelayFault
.1.3.6.1.4.1.318.0.606
WARNING: An output relay (or its driver) fault exists.
apcOutputRelayFaultCleared
.1.3.6.1.4.1.318.0.607
INFORMATIONAL: An output relay (or its driver) fault cleared.
upsPfcFault
.1.3.6.1.4.1.318.0.608
WARNING: A PFC fault exists.
upsPfcFaultCleared
.1.3.6.1.4.1.318.0.609
INFORMATIONAL: The PFC fault cleared.
humidityThresholdViolation2
.1.3.6.1.4.1.318.0.61
SEVERE: An Environmental Monitor humidity threshold has been violated on probe 2.
The first variable is the current humidity.
apcDcBusOverVoltage
.1.3.6.1.4.1.318.0.610
WARNING: The DC bus voltage is too high.
apcDcBusOverVoltageCleared
.1.3.6.1.4.1.318.0.611
INFORMATIONAL: The DC bus voltage is too high cleared.
upsInverterFault
.1.3.6.1.4.1.318.0.612
WARNING: The inverter fault exists.
upsInverterFaultCleared
.1.3.6.1.4.1.318.0.613
INFORMATIONAL: The inverter fault cleared.
apcAdConverterFault
.1.3.6.1.4.1.318.0.614
WARNING: The A/D converter fault exists.
apcAdConverterFaultCleared
.1.3.6.1.4.1.318.0.615
INFORMATIONAL: The A/D converter fault cleared.
apcLogicPowerSupplyFault
.1.3.6.1.4.1.318.0.616
WARNING: A logic power supply fault exists.
apcLogicPowerSupplyFaultCleared
.1.3.6.1.4.1.318.0.617
INFORMATIONAL: A logic power supply fault cleared.
apcTransformerDCImbalanceFault
.1.3.6.1.4.1.318.0.618
WARNING: The DC component of the transformer's current is too high.
apcTransformerDCImbalanceFaultCleared
.1.3.6.1.4.1.318.0.619
WARNING: The DC component of the transformer's current is normal.
humidityThresholdViolationCleared2
.1.3.6.1.4.1.318.0.62
INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 2.
upsBackfeedRelayFault
.1.3.6.1.4.1.318.0.620
WARNING: The backfeed relay (or its driver) has a fault.
upsBackfeedRelayFaultCleared
.1.3.6.1.4.1.318.0.621
WARNING: The backfeed relay (or its driver) has a fault cleared.
upsBypassRelayFault
.1.3.6.1.4.1.318.0.622
WARNING: A bypass relay (or its driver) has a fault.
upsBypassRelayFaultCleared
.1.3.6.1.4.1.318.0.623
WARNING: A bypass relay (or its driver) has a fault cleared.
xPDUBranchCurrentMinAlarm
.1.3.6.1.4.1.318.0.626
SEVERE: The current in a branch circuit is outside the limits specified for that
branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
xPDUBranchCurrentMinAlarmCleared
.1.3.6.1.4.1.318.0.627
INFORMATIONAL: The current in a branch circuit is back within the limits
specified for that branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
xPDUBranchCurrentMaxAlarm
.1.3.6.1.4.1.318.0.628
SEVERE: The current in a branch circuit is outside the limits specified for that
branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
The fifth argument is the threshold, in tenths of Amps, above which the alarm was generated.
xPDUBranchCurrentMaxAlarmCleared
.1.3.6.1.4.1.318.0.629
INFORMATIONAL: The current in a branch circuit is back within the limits
specified for that branch circuit.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the panel position of the branch circuit (1-based index).
The fourth argument is the measured current in tenths of Amps.
temperatureThresholdViolation2
.1.3.6.1.4.1.318.0.63
SEVERE: An Environmental Monitor temperature threshold has been violated on probe 2.
The first variable is the current temperature.
rPDUOutletLowLoad
.1.3.6.1.4.1.318.0.630
WARNING: A Rack PDU has violated the outlet low load threshold.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
rPDUOutletLowLoadCleared
.1.3.6.1.4.1.318.0.631
INFORMATIONAL: The outlet low load condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
rPDUOutletNearOverload
.1.3.6.1.4.1.318.0.632
WARNING: A Rack PDU is near an outlet overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
rPDUOutletNearOverloadCleared
.1.3.6.1.4.1.318.0.633
INFORMATIONAL: The outlet near overload condition on a Rack PDU has
been cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
rPDUOutletOverload
.1.3.6.1.4.1.318.0.634
SEVERE: A Rack PDU is in an overload condition.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
rPDUOutletOverloadCleared
.1.3.6.1.4.1.318.0.635
INFORMATIONAL: The outlet overload condition on a Rack PDU has been
cleared.
The first argument is the serial number.
The second argument is the device name.
The third argument is the outlet number.
apcTestTrap
.1.3.6.1.4.1.318.0.636
INFORMATIONAL: Trap used to test SNMP trap functionality.
The first argument is a place holder for test variables.
baseFanFailureCleared
.1.3.6.1.4.1.318.0.637
INFORMATIONAL: Base module fan has been repaired
atsLowLoad
.1.3.6.1.4.1.318.0.638
WARNING: ATS has violated the bank or phase low load threshold.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number
The fourth argument is the bank number. -1 is returned if bank does not exist.
atsLowLoadCleared
.1.3.6.1.4.1.318.0.639
INFORMATIONAL: The bank or phase low load condition on an ATS has been
cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number
The fourth argument is the bank number. -1 is returned if bank does not exist.
temperatureThresholdViolationCleared2
.1.3.6.1.4.1.318.0.64
INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 2.
atsNearOverload
.1.3.6.1.4.1.318.0.640
WARNING: ATS has violated the bank or phase near overload threshold.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number
The fourth argument is the bank number. -1 is returned if bank does not exist.
atsNearOverloadCleared
.1.3.6.1.4.1.318.0.641
INFORMATIONAL: The bank or phase near overload condition on an ATS has
been cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number
The fourth argument is the bank number. -1 is returned if bank does not exist.
atsOverload
.1.3.6.1.4.1.318.0.642
SEVERE: ATS is in an overload condition.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number.
The fourth argument is the bank number. -1 is returned if bank does not exist.
atsOverloadCleared
.1.3.6.1.4.1.318.0.643
INFORMATIONAL: The bank or phase overload condition on an ATS has been
cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is the phase number.
The fourth argument is the bank number. -1 is returned if bank does not exist.
atsRMSOverVoltage
.1.3.6.1.4.1.318.0.644
SEVERE: Overvoltage condition violated.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSOverVoltageCleared
.1.3.6.1.4.1.318.0.645
INFORMATIONAL: Overvoltage condition cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSUnderVoltage
.1.3.6.1.4.1.318.0.646
SEVERE: Undervoltage condition violated.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSUnderVoltageCleared
.1.3.6.1.4.1.318.0.647
INFORMATIONAL: Undervoltage condition cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSOverFrequency
.1.3.6.1.4.1.318.0.648
SEVERE: OverFrequency condition violated.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSOverFrequencyCleared
.1.3.6.1.4.1.318.0.649
INFORMATIONAL: OverFrequency condition cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
mupsCommunicationEstablished
.1.3.6.1.4.1.318.0.65
INFORMATIONAL: Communication with the Environmental Monitor has been established.
atsRMSUnderFrequency
.1.3.6.1.4.1.318.0.650
SEVERE: UnderFrequency condition violated.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsRMSUnderFrequencyCleared
.1.3.6.1.4.1.318.0.651
INFORMATIONAL: UnderFrequency condition cleared.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
isxModularDistributionCommLost
.1.3.6.1.4.1.318.0.652
SEVERE: Communication with a metering segment of the modular
distribution system has been lost.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the segment number.
The fourth argument describes the modules served by this metering segment.
isxModularDistributionCommEstablished
.1.3.6.1.4.1.318.0.653
INFORMATIONAL: Communication with a metering segment of the modular
distribution system has been restored.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the segment number.
The fourth argument describes the modules served by this metering segment.
isxModularDistributionModuleInserted
.1.3.6.1.4.1.318.0.654
INFORMATIONAL: A distribution module has been inserted into the system.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module location number.
isxModularDistributionModuleRemoved
.1.3.6.1.4.1.318.0.655
INFORMATIONAL: A distribution module has been removed from the system.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module location number.
isxModularBreakerOpenAlarm
.1.3.6.1.4.1.318.0.656
SEVERE: A distribution module breaker is open and in an alarm condition.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the module breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularBreakerOpenAlarmCleared
.1.3.6.1.4.1.318.0.657
INFORMATIONAL: An alarm caused by a distribution breaker being open has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker(s) (1=L1, 2=L2, 3=L3, 4=L12, 5=L23, 6=L123).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularMinCurrentThresholdViolation
.1.3.6.1.4.1.318.0.658
SEVERE: The current in a distribution module is below the minimum/critical
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularMinCurrentThresholdViolationCleared
.1.3.6.1.4.1.318.0.659
INFORMATIONAL: The current in a distribution module is no longer below the minimum/critical
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
mupsCommunicationLost
.1.3.6.1.4.1.318.0.66
SEVERE: Communication to the Environmental Monitor has been lost. Steps
to reestablish communication are in progress.
isxModularLowCurrentThresholdViolation
.1.3.6.1.4.1.318.0.660
WARNING: The current in a distribution module is below the low/warning
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularLowCurrentThresholdViolationCleared
.1.3.6.1.4.1.318.0.661
INFORMATIONAL: The current in a distribution module is no longer below the low/warning
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularHighCurrentThresholdViolation
.1.3.6.1.4.1.318.0.662
WARNING: The current in a distribution module is above the high/warning
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularHighCurrentThresholdViolationCleared
.1.3.6.1.4.1.318.0.663
INFORMATIONAL: The current in a distribution module is no longer above the high/warning
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularMaxCurrentThresholdViolation
.1.3.6.1.4.1.318.0.664
SEVERE: The current in a distribution module is above the maximum/critical
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularMaxCurrentThresholdViolationCleared
.1.3.6.1.4.1.318.0.665
INFORMATIONAL: The current in a distribution module is no longer above the maximum/critical
limit specified for the circuit/cable.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the module number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the circuit/cable fed by this breaker.
isxModularSubfeedBreakerOpenAlarm
.1.3.6.1.4.1.318.0.666
SEVERE: A distribution subfeed breaker is open and in an alarm condition.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the load name associated with the subfeed.
isxModularSubfeedBreakerOpenAlarmCleared
.1.3.6.1.4.1.318.0.667
INFORMATIONAL: An alarm caused by a distribution subfeed breaker being open has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the load name associated with the subfeed.
isxModularSubfeedMinCurrentThresholdViolation
.1.3.6.1.4.1.318.0.668
SEVERE: The current in a distribution subfeed is below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the subfeed.
INFORMATIONAL: The current in a distribution subfeed is no longer below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the subfeed.
batteryIncrease
.1.3.6.1.4.1.318.0.67
INFORMATIONAL: The number of batteries has increased.
isxModularSubfeedLowCurrentThresholdViolation
.1.3.6.1.4.1.318.0.670
WARNING: The current in a distribution subfeed is below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the subfeed.
INFORMATIONAL: The current in a distribution subfeed is no longer below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the subfeed.
isxModularSubfeedHighCurrentThresholdViolation
.1.3.6.1.4.1.318.0.672
WARNING: The current in a distribution subfeed is above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the subfeed.
INFORMATIONAL: The current in a distribution subfeed is no longer above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the subfeed.
isxModularSubfeedMaxCurrentThresholdViolation
.1.3.6.1.4.1.318.0.674
SEVERE: The current in a distribution subfeed is above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the threshold, in tenths of Amps, from which the alarm was generated.
The sixth argument is the load name associated with the subfeed.
INFORMATIONAL: The current in a distribution subfeed is no longer above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the subfeed number.
The fourth argument is the breaker/phase index (1=L1, 2=L2, 3=L3).
The fifth argument is the load name associated with the subfeed.
isxModularTotalOutputCurrentMinThresholdViolation
.1.3.6.1.4.1.318.0.676
SEVERE: The total output current of the distribution is below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated.
INFORMATIONAL: The total output current of the distribution is no longer below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
isxModularTotalOutputCurrentLowThresholdViolation
.1.3.6.1.4.1.318.0.678
WARNING: The total output current of the distribution is below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated.
INFORMATIONAL: The total output current of the distribution is no longer below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
batteryDecrease
.1.3.6.1.4.1.318.0.68
INFORMATIONAL: The number of batteries has decreased.
WARNING: The total output current of the distribution is above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated.
INFORMATIONAL: The total output current of the distribution is no longer above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
isxModularTotalOutputCurrentMaxThresholdViolation
.1.3.6.1.4.1.318.0.682
SEVERE: The total output current of the distribution is above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Amps, from which the alarm was generated.
INFORMATIONAL: The total output current of the distribution is no longer above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
isxModularOutputVoltageMinThresholdViolation
.1.3.6.1.4.1.318.0.684
SEVERE: The distribution output voltage is below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated.
INFORMATIONAL: The distribution output voltage is no longer below the minimum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
isxModularOutputVoltageLowThresholdViolation
.1.3.6.1.4.1.318.0.686
WARNING: The distribution output voltage is below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated.
INFORMATIONAL: The distribution output voltage is no longer below the low/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
isxModularOutputVoltageHighThresholdViolation
.1.3.6.1.4.1.318.0.688
WARNING: The distribution output voltage is above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated.
INFORMATIONAL: The distribution output voltage is no longer above the high/warning limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
powerModuleIncrease
.1.3.6.1.4.1.318.0.69
INFORMATIONAL: The number of power modules has increased.
isxModularOutputVoltageMaxThresholdViolation
.1.3.6.1.4.1.318.0.690
SEVERE: The distribution output voltage is above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
The fourth argument is the threshold, in tenths of Volts, from which the alarm was generated.
INFORMATIONAL: The distribution output voltage is no longer above the maximum/critical limit specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the phase index (1=L1, 2=L2, 3=L3).
apcDoorClosedImproperly
.1.3.6.1.4.1.318.0.692
SEVERE: A door has been closed improperly.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcDoorClosedImproperlyCleared
.1.3.6.1.4.1.318.0.693
INFORMATIONAL: A door is no longer closed improperly.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcUserScheduleViolation
.1.3.6.1.4.1.318.0.694
SEVERE: A user has had a door opened past the scheduled access period.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
apcUserScheduleViolationCleared
.1.3.6.1.4.1.318.0.695
INFORMATIONAL: User schedule violation has been cleared.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the host device location.
The fourth argument is the door identifier, (1=front, 2=rear).
isxModularOutputFrequencyThresholdViolation
.1.3.6.1.4.1.318.0.696
SEVERE: The distribution output frequency is outside of the operating range specified.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the threshold, in tenths of Hertz, from which the alarm was generated.
isxModularOutputFrequencyViolationCleared
.1.3.6.1.4.1.318.0.697
INFORMATIONAL: The distribution output frequency is no longer out of range.
The first argument is the host device serial number.
The second argument is the host device name.
atsSourceStatusFail
.1.3.6.1.4.1.318.0.698
SEVERE: ATS Source failed.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
atsSourceStatusOk
.1.3.6.1.4.1.318.0.699
INFORMATIONAL: ATS Source OK.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the source: 0=A, 1=B.
lowBattery
.1.3.6.1.4.1.318.0.7
SEVERE: The UPS batteries are low and will soon be exhausted.
If utility power is not restored the UPS will put itself
to 'sleep' and immediately cut power to the load.
powerModuleDecrease
.1.3.6.1.4.1.318.0.70
INFORMATIONAL: The number of power modules has decreased.
atsHardwareStatusFail
.1.3.6.1.4.1.318.0.700
SEVERE: ATS display board hardware failed.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the failed hardware:
0= Phase LEDs/Push-button hardware failure
1= Seven-segment display hardware failure.
atsHardwareStatusOk
.1.3.6.1.4.1.318.0.701
INFORMATIONAL: ATS display board hardware ok.
The first argument is the serial number.
The second argument is the product name.
The third argument is an integer representing the hardware:
0= Phase LEDs/Push-button hardware failure
1= Seven-segment display hardware failure.
atsControllerRestart
.1.3.6.1.4.1.318.0.702
INFORMATIONAL: ATS Controller restarted.
inputWarningError
.1.3.6.1.4.1.318.0.703
WARNING: Input warning error has been detected.
The first variable is the fault condition.
inputOK
.1.3.6.1.4.1.318.0.704
INFORMATIONAL: Input warning error has been cleared.
The first variable is the fault condition.
bypassWarningError
.1.3.6.1.4.1.318.0.705
WARNING: Bypass warning error has been detected.
The first variable is the fault condition.
bypassOK
.1.3.6.1.4.1.318.0.706
INFORMATIONAL: Bypass warning error has been cleared.
The first variable is the fault condition.
communicationWarningError
.1.3.6.1.4.1.318.0.707
WARNING: Communication warning error has been detected.
The first variable is the fault condition.
communicationOK
.1.3.6.1.4.1.318.0.708
INFORMATIONAL: Communication warning error has been cleared.
The first variable is the fault condition.
powerModuleSevereError
.1.3.6.1.4.1.318.0.709
SEVERE: Power module severe error has been detected.
The first variable is the fault condition.
intelligenceModuleInserted
.1.3.6.1.4.1.318.0.71
INFORMATIONAL: An intelligence module has been inserted.
powerModuleOK
.1.3.6.1.4.1.318.0.710
INFORMATIONAL: Power module severe error has been cleared.
The first variable is the fault condition.
outputVoltageWaveformError
.1.3.6.1.4.1.318.0.711
SEVERE: Output voltage waveform error has been detected.
outputVoltageWaveformOK
.1.3.6.1.4.1.318.0.712
INFORMATIONAL: Output voltage waveform is OK.
bypassStaticSwitchOverload
.1.3.6.1.4.1.318.0.713
SEVERE: Overload on bypass static switch has been detected.
noOverloadOnBypassStaticSwitch
.1.3.6.1.4.1.318.0.714
INFORMATIONAL: Overload on static bypass switch no longer present.
batteryVoltageCollapse
.1.3.6.1.4.1.318.0.715
SEVERE: Battery voltage collapse has been detected.
batteryVoltageOK
.1.3.6.1.4.1.318.0.716
INFORMATIONAL: Battery voltage OK.
overloadOnInstallation
.1.3.6.1.4.1.318.0.717
SEVERE: Overload on installation has been detected.
noOverloadOnInstallation
.1.3.6.1.4.1.318.0.718
INFORMATIONAL: Overload on installation no longer present.
bypassStaticSwitchError
.1.3.6.1.4.1.318.0.719
SEVERE: Bypass static switch error, module has critical error.
intelligenceModuleRemoved
.1.3.6.1.4.1.318.0.72
INFORMATIONAL: An intelligence module has been removed.
bypassStaticSwitchOK
.1.3.6.1.4.1.318.0.720
INFORMATIONAL: Bypass static switch OK.
forcedBypassSwitchActivated
.1.3.6.1.4.1.318.0.721
SEVERE: Forced bypass switch has been activated.
forcedBypassSwitchReleased
.1.3.6.1.4.1.318.0.722
INFORMATIONAL: Forced bypass switch has been released.
epoActivated
.1.3.6.1.4.1.318.0.723
SEVERE: Emergency Power Off (EPO) switch has been activated.
xATSS1BadPhaseRotation
.1.3.6.1.4.1.318.0.724
SEVERE: The device's source 1 phase rotation is bad.
The first argument is the host device serial number.
The second argument is the host device name.
xATSS1BadPhaseRotationCleared
.1.3.6.1.4.1.318.0.725
INFORMATIONAL: The device's source 1 phase rotation is back to normal.
The first argument is the host device serial number.
The second argument is the host device name.
xATSS1BadPhaseBalance
.1.3.6.1.4.1.318.0.726
SEVERE: The device's source 1 phase balance is out of bounds.
The first argument is the host device serial number.
The second argument is the host device name.
The third argument is the minimum phase balance as a percentage.
xATSS1BadPhaseBalanceCleared
.1.3.6.1.4.1.318.0.727
INFORMATIONAL: The device's source 1 phase balance is back to normal.
The first argument is the host device serial number.
The second argument is the host device name.
isxModularTransformerOverheating
.1.3.6.1.4.1.318.0.728
SEVERE: The distribution transformer temperature is too hot.
The first argument is the host device serial number.
The second argument is the host device name.
isxModularTransformerOverheatingCleared
.1.3.6.1.4.1.318.0.729
INFORMATIONAL: The distribution transformer temperature has returned to normal.
The first argument is the host device serial number.
The second argument is the host device name.
rintelligenceModuleInserted
.1.3.6.1.4.1.318.0.73
INFORMATIONAL: A redundant intelligence module has been inserted.
apcInternalCommunicationFault
.1.3.6.1.4.1.318.0.730
SEVERE: An internal UPS communication fault exists.
apcInternalCommunicationFaultCleared
.1.3.6.1.4.1.318.0.731
INFORMATIONAL: An internal UPS communication fault no longer exists.
upsOutletGroupCommand
.1.3.6.1.4.1.318.0.732
WARNING: The specified Outlet Group command has been issued.
onbatterycommunicationLost
.1.3.6.1.4.1.318.0.733
SEVERE: Communication to the UPS when the UPS is on Battery. Steps
to reestablish communication are in progress.
upsCriticalCondition
.1.3.6.1.4.1.318.0.734
SEVERE: A UPS critical condition was detected.
The first variable is the error condition text message.
The second variable is the error number.
upsCriticalConditionCleared
.1.3.6.1.4.1.318.0.735
INFORMATIONAL: A UPS critical condition has been cleared.
The first variable is the fault condition.
upsWarningCondition
.1.3.6.1.4.1.318.0.736
WARNING: A UPS warning condition has been detected.
The first variable is the fault condition.
upsWarningConditionCleared
.1.3.6.1.4.1.318.0.737
WARNING: A UPS warning condition has been cleared.
The first variable is the fault condition.
upsInformationalCondition
.1.3.6.1.4.1.318.0.738
INFORMATIONAL: A UPS informational condition has been detected.
The first variable is the fault condition.
upsInformationalConditionCleared
.1.3.6.1.4.1.318.0.739
INFORMATIONAL: A UPS informational condition has been cleared.
The first variable is the fault condition.
rintelligenceModuleRemoved
.1.3.6.1.4.1.318.0.74
INFORMATIONAL: A redundant intelligence module has been removed.
isxcInformationalAlarm
.1.3.6.1.4.1.318.0.740
INFORMATIONAL: An ISXC Alarm exists.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcInformationalAlarmCleared
.1.3.6.1.4.1.318.0.741
INFORMATIONAL: An ISXC Alarm has been cleared.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcWarningAlarm
.1.3.6.1.4.1.318.0.742
WARNING: An ISXC Alarm exists.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcWarningAlarmCleared
.1.3.6.1.4.1.318.0.743
WARNING: An ISXC Alarm has been cleared.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcErrorAlarm
.1.3.6.1.4.1.318.0.744
ERROR: An ISXC Alarm exists.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcErrorAlarmCleared
.1.3.6.1.4.1.318.0.745
ERROR: An ISXC Alarm has been cleared.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcCriticalAlarm
.1.3.6.1.4.1.318.0.746
CRITICAL: An ISXC Alarm exists.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcCriticalAlarmCleared
.1.3.6.1.4.1.318.0.747
CRITICAL: An ISXC Alarm has been cleared.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcFailureAlarm
.1.3.6.1.4.1.318.0.748
FAILURE: An ISXC Alarm exists.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
isxcFailureAlarmCleared
.1.3.6.1.4.1.318.0.749
FAILURE: An ISXC Alarm has been cleared.
The first argument is the unique ISXC alarm ID.
The second argument is the ISXC alarm label as a UTF8 string.
The third argument is the ISXC alarm code.
The fourth argument is the unique ISXC device ID.
The fifth argument is the ISXC device label as a UTF8 string.
The sixth argument is the ISXC parent host.
The seventh argument is the ISXC device type as a UTF8 string.
The eighth argument is the device serial number.
The ninth argument is the device model number.
The tenth argument is the device host.
The eleventh argument is the device location as a UTF8 string.
The twelfth argument is the device contact as a UTF8 string.
The thirteenth argument is the unique ISXC sensor ID.
The fourteenth argument is the ISXC sensor label as a UTF8 string.
The fifteenth argument is the sensor value as a UTF8 string.
The sixteenth argument is the ISXC alarm start time.
The seventeenth argument is the ISXC alarm resolution time.
The eighteenth argument is the description as a UTF8 string.
extBatteryFrameIncease
.1.3.6.1.4.1.318.0.75
INFORMATIONAL: An external battery frame has been added.
rpduCriticalCondition
.1.3.6.1.4.1.318.0.750
SEVERE: A RPDU critical condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
rpduCriticalConditionCleared
.1.3.6.1.4.1.318.0.751
INFORMATIONAL: A RPDU critical condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
rpduWarningCondition
.1.3.6.1.4.1.318.0.752
WARNING: A RPDU warning condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
rpduWarningConditionCleared
.1.3.6.1.4.1.318.0.753
WARNING: A RPDU warning condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
rpduInformationalCondition
.1.3.6.1.4.1.318.0.754
INFORMATIONAL: A RPDU informational condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
rpduInformationalConditionCleared
.1.3.6.1.4.1.318.0.755
INFORMATIONAL: A RPDU informational condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the error number.
The fourth variable is the device number.
The fifth variable is the instance number.
The sixth variable is the trap text message.
isxModularCoolingFanAlarm
.1.3.6.1.4.1.318.0.756
SEVERE: The device's internal cooling fans have failed.
The first argument is the host device serial number.
The second argument is the host device name.
isxModularCoolingFanAlarmCleared
.1.3.6.1.4.1.318.0.757
INFORMATIONAL: The device's internal cooling fans are now functioning properly.
The first argument is the host device serial number.
The second argument is the host device name.
upsFirmwareUpdateStarted
.1.3.6.1.4.1.318.0.758
WARNING: Updating UPS firmware.
upsFirmwareUpdateFinished
.1.3.6.1.4.1.318.0.759
INFORMATIONAL: Finished updating UPS firmware.
extBatteryFrameDecrease
.1.3.6.1.4.1.318.0.76
INFORMATIONAL: An external battery frame has been removed.
upsFirmwareUpdateSucceeded
.1.3.6.1.4.1.318.0.760
INFORMATIONAL: UPS firmware update succeeded.
upsFirmwareUpdateFailed
.1.3.6.1.4.1.318.0.761
WARNING: UPS firmware update failed.
upsHasNoValidFirmware
.1.3.6.1.4.1.318.0.762
SEVERE: UPS has no valid firmware.
upsHasNoValidFirmwareCleared
.1.3.6.1.4.1.318.0.763
INFORMATIONAL: UPS now has a valid firmware.
upsLocalDisplayButtonFault
.1.3.6.1.4.1.318.0.767
WARNING: A local display button fault exists.
upsLocalDisplayButtonFaultCleared
.1.3.6.1.4.1.318.0.768
INFORMATIONAL: A local display button fault no longer exists.
upsNeedsFactorySetupFault
.1.3.6.1.4.1.318.0.769
SEVERE: UPS needs factory setup.
abnormalCondition
.1.3.6.1.4.1.318.0.77
SEVERE: An abnormal condition has been detected.
The first variable is the fault condition.
upsNeedsFactorySetupFaultCleared
.1.3.6.1.4.1.318.0.770
INFORMATIONAL: UPS no longer needs factory setup.
upsEPOActive
.1.3.6.1.4.1.318.0.771
SEVERE: Emergency Power Off (EPO) active.
upsEPOActiveCleared
.1.3.6.1.4.1.318.0.772
INFORMATIONAL: Emergency Power Off (EPO) now inactive.
upsFirmwareMismatch
.1.3.6.1.4.1.318.0.773
SEVERE: A firmware mismatch error exists.
upsFirmwareMismatchCleared
.1.3.6.1.4.1.318.0.774
INFORMATIONAL: A firmware mismatch error no longer exists.
upsOscillatorFailed
.1.3.6.1.4.1.318.0.775
SEVERE: An oscillator error exists.
upsOscillatorFailedCleared
.1.3.6.1.4.1.318.0.776
INFORMATIONAL: An oscillator error no longer exists.
upsOnBatteryDueToFault
.1.3.6.1.4.1.318.0.777
SEVERE: The UPS is on battery due to an error.
Symmetra UPS devices: Intelligence module has reported being in self-test for
too long. When this happens, the UPS is not usually in self-test, but the
batteries are draining slowly. If left uncorrected, the batteries will
become depleted and the UPS will not be able to turn on. If the UPS has at
least N+1 redundancy, check power modules one by one to determine which
keeps the UPS in self-test. Once identified, replace the module.
upsOnBatteryDueToFaultCleared
.1.3.6.1.4.1.318.0.778
INFORMATIONAL: The UPS is no longer on battery due to an error.
pcnsCriticalEventActive
.1.3.6.1.4.1.318.0.779
SEVERE: PowerChute Network Shutdown has begun a safe shutdown of the host.
abnormalConditionCleared
.1.3.6.1.4.1.318.0.78
INFORMATIONAL: An abnormal condition has been cleared.
The first variable is the fault condition.
INFORMATIONAL: PowerChute can communicate with NMC again.
pcnsNMCComsLost
.1.3.6.1.4.1.318.0.783
SEVERE: NMC cannot communicate with UPS.
pcnsNMCComsLostResolved
.1.3.6.1.4.1.318.0.784
INFORMATIONAL: NMC can communicate with UPS again.
pcnsTest
.1.3.6.1.4.1.318.0.785
INFORMATIONAL: PowerChute has sent a test trap.
pcnsUpdateAvailable
.1.3.6.1.4.1.318.0.786
INFORMATIONAL: PowerChute has detected that a newer version is available.
temporaryBypass
.1.3.6.1.4.1.318.0.787
WARNING: UPS on temporary bypass
deviceStatusChange
.1.3.6.1.4.1.318.0.79
INFORMATIONAL: The status of the device being monitored has changed.
pcbeCriticalEventActive
.1.3.6.1.4.1.318.0.790
SEVERE: PowerChute Business Edition has begun a safe shutdown of the host.
pcbeCriticalEventResolved
.1.3.6.1.4.1.318.0.791
INFORMATIONAL: PowerChute Business Edition critical event resolved. Safe shutdown will continue.
pcbeComsLost
.1.3.6.1.4.1.318.0.792
SEVERE: PowerChute cannot communicate with UPS
pcbeComsLostResolved
.1.3.6.1.4.1.318.0.793
INFORMATIONAL: PowerChute can communicate with UPS again.
pcbeTest
.1.3.6.1.4.1.318.0.794
INFORMATIONAL: PowerChute has sent a test trap.
pcbeUpdateAvailable
.1.3.6.1.4.1.318.0.795
INFORMATIONAL: PowerChute has detected that a newer version is available.
pmmCriticalCondition
.1.3.6.1.4.1.318.0.796
SEVERE: A PMM critical condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
pmmCriticalConditionCleared
.1.3.6.1.4.1.318.0.797
INFORMATIONAL: A PMM critical condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
pmmWarningCondition
.1.3.6.1.4.1.318.0.798
WARNING: A PMM warning condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
pmmWarningConditionCleared
.1.3.6.1.4.1.318.0.799
WARNING: A PMM warning condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
communicationEstablished
.1.3.6.1.4.1.318.0.8
INFORMATIONAL: Communication with the UPS has been established.
noBatteries
.1.3.6.1.4.1.318.0.80
WARNING: The UPS has no batteries attached.
pmmInformationalCondition
.1.3.6.1.4.1.318.0.800
INFORMATIONAL: A PMM informational condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
pmmInformationalConditionCleared
.1.3.6.1.4.1.318.0.801
INFORMATIONAL: A PMM informational condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
upsInputContactOutputRelayFault
.1.3.6.1.4.1.318.0.802
SEVERE: A fault exists in the UPS input contact / output relay hardware.
upsInputContactOutputRelayFaultCleared
.1.3.6.1.4.1.318.0.803
INFORMATIONAL: Fault no longer exists in the UPS input contact / output relay hardware.
upsAirFilterWarning
.1.3.6.1.4.1.318.0.804
WARNING: Air filter requires service.
upsAirFilterWarningCleared
.1.3.6.1.4.1.318.0.805
INFORMATIONAL: Air filter no longer requires service.
upsBatteryPackIncompatible
.1.3.6.1.4.1.318.0.806
SEVERE: Incompatible battery pack.
upsBatteryPackIncompatibleCleared
.1.3.6.1.4.1.318.0.807
INFORMATIONAL: Incompatible battery pack no longer present.
upsInputContactAbnormal
.1.3.6.1.4.1.318.0.808
WARNING: UPS input contact is in the abnormal state.
upsInputContactAbnormalCleared
.1.3.6.1.4.1.318.0.809
INFORMATIONAL: UPS input contact has returned to its normal
state.
noBatteriesCleared
.1.3.6.1.4.1.318.0.81
INFORMATIONAL: The UPS device's batteries have been attached.
upsOutputRelayAbnormal
.1.3.6.1.4.1.318.0.810
WARNING: A UPS output relay has switched to the abnormal state.
upsOutputRelayAbnormalCleared
.1.3.6.1.4.1.318.0.811
INFORMATIONAL: A UPS output relay has returned to its normal
state.
ePDUCriticalCondition
.1.3.6.1.4.1.318.0.812
SEVERE: A EPDU critical condition has been detected.
ePDUCriticalConditionCleared
.1.3.6.1.4.1.318.0.813
INFORMATIONAL: A EPDU critical condition has been cleared.
ePDUWarningCondition
.1.3.6.1.4.1.318.0.814
SEVERE: A Easy PDU warning condition has been detected.
ePDUWarningConditionCleared
.1.3.6.1.4.1.318.0.815
SEVERE: A Easy PDU warning condition has been cleared.
userAdded
.1.3.6.1.4.1.318.0.82
INFORMATIONAL: A new user has been added.
upsBreakerQ2Open
.1.3.6.1.4.1.318.0.822
SEVERE: The UPS breaker Q2 (UOB) is open.
upsBreakerQ2Closed
.1.3.6.1.4.1.318.0.823
INFORMATIONAL: The UPS breaker Q2 (UOB) is closed.
bypassPowerSupplyFailureCleared
.1.3.6.1.4.1.318.0.824
INFORMATIONAL: Base module bypass power supply needs repair condition has been cleared
atsCriticalCondition
.1.3.6.1.4.1.318.0.825
SEVERE: A ATS critical condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
atsCriticalConditionCleared
.1.3.6.1.4.1.318.0.826
INFORMATIONAL: A ATS critical condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
atsWarningCondition
.1.3.6.1.4.1.318.0.827
WARNING: A ATS warning condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
atsWarningConditionCleared
.1.3.6.1.4.1.318.0.828
WARNING: A ATS warning condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
atsInformationalCondition
.1.3.6.1.4.1.318.0.829
INFORMATIONAL: A ATS informational condition has been detected.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
userDeleted
.1.3.6.1.4.1.318.0.83
INFORMATIONAL: A user has been deleted.
atsInformationalConditionCleared
.1.3.6.1.4.1.318.0.830
INFORMATIONAL: A ATS informational condition has been cleared.
The first variable is the serial number.
The second variable is the device name.
The third variable is the event ID.
The fourth variable is the instance number.
The fifth variable is the trap text message.
userModified
.1.3.6.1.4.1.318.0.84
INFORMATIONAL: A user has been modified.
msvmCommunicationEstablished
.1.3.6.1.4.1.318.0.85
INFORMATIONAL: Communications with the MasterSwitch VM has been established.
msvmCommunicationLost
.1.3.6.1.4.1.318.0.86
SEVERE: Communications with the MasterSwitch VM has been lost.
msvmOverload
.1.3.6.1.4.1.318.0.87
SEVERE: The MasterSwitch VM in an overload condition.
msvmOverloadCleared
.1.3.6.1.4.1.318.0.88
INFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared.
msvmOutletOn
.1.3.6.1.4.1.318.0.89
INFORMATIONAL: An outlet on the MasterSwitch VM has turned on.
powerRestored
.1.3.6.1.4.1.318.0.9
INFORMATIONAL: Utility power has been restored.
msvmOutletOff
.1.3.6.1.4.1.318.0.90
INFORMATIONAL: An outlet on the MasterSwitch VM has turned off.
msvmDeviceConfigChange
.1.3.6.1.4.1.318.0.91
INFORMATIONAL: A device configuration change has been made on a MasterSwitch VM.
msvmOutletConfigChange
.1.3.6.1.4.1.318.0.92
INFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM.
msvmLowLoad
.1.3.6.1.4.1.318.0.93
INFORMATIONAL: The MasterSwitch VM has violated the low load threshold.
msvmLowLoadCleared
.1.3.6.1.4.1.318.0.94
INFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared.
msvmNearOverload
.1.3.6.1.4.1.318.0.95
SEVERE: The MasterSwitch VM is approaching an overload condition.
msvmNearOverloadCleared
.1.3.6.1.4.1.318.0.96
INFORMATIONAL: The near overload condition on the MasterSwitch VM has been cleared.
msvmPowerSupplyStatusChange
.1.3.6.1.4.1.318.0.97
WARNING: The power supply status of the MasterSwitch VM has changed.
mspCommunicationEstablished
.1.3.6.1.4.1.318.0.98
INFORMATIONAL: Communications with the MasterSwitch plus has been established.
mspCommunicationLost
.1.3.6.1.4.1.318.0.99
SEVERE: Communications with the MasterSwitch plus has been lost.