upsAdvConfigLowBatteryRunTime
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.5.2.8
Object
The desired run time of the UPS, in seconds, once the
low battery condition is reached. During this time the UPS may
produce a constant warning tone, which cannot be disabled,
depending on the UPS model.
For a list of allowed values supported by your UPS model,
see the UPS User's Manual.
If a value other than a supported value is provided in a set
request, the UPS interprets the value as the next higher
acceptable value. If the provided value is higher than the
highest acceptable value, the highest acceptable value is used.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.5.2.8- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsAdvConfig
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvConfigLowBatteryRunTime.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsAdvConfigLowBatteryRunTime'
Syntax
- Source
- RFC1155-SMITimeTicks
- Base type
Unsigned32
Values & Constraints
Type Constraints
range: 0..4294967295