xATSSwitchSettingsHighVoltageTransferPoint
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.17.3.2.2
Object
The highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is considered bad and the generator run signal is asserted to begin generator operation. Specified in volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.17.3.2.2- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- xATSSwitchSettings
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchSettingsHighVoltageTransferPoint.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::xATSSwitchSettingsHighVoltageTransferPoint'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647