xATSSwitchSettingsHighVoltageTransferPoint

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.17.3.2.2

Object

scalar mandatory r/w Integer32
The highest acceptable voltage condition at source 1.
When any phase of source 1 is greater than this voltage,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified in volts,  line-to-line for a 3-wire service or
line-to-neutral for a 4-wire service.
-1 if not available.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.17.3.2.2
Type
scalar
Access
readwrite
Status
mandatory
Parent
xATSSwitchSettings

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchSettingsHighVoltageTransferPoint.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::xATSSwitchSettingsHighVoltageTransferPoint'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647