The positive values represent efficiency of the UPS in tenths of percent. -1 If UPS supports this OID but the result is not available -2 Load is too low to report efficiency -3 Output off and efficiency is 0 -4 On battery, efficiency is not measured or calculated in this mode -5 In Bypass, efficiency is not measured or calculated in this mode -6 Battery charging, battery is charging and adversely affecting efficiency -7 Poor AC input, the main input is outside the optimum efficiency range
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in:
Sensors
Explore Observium network monitoring
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.4.3.5- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- upsHighPrecOutput
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecOutputEfficiency.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsHighPrecOutputEfficiency'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647