upsBasicSystemStatus

OBS ✓
PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.4.1.3

Object

scalar mandatory Enumeration
Current state for the whole system (UPS and surrounding breakers).
If the UPS is unable to determine the state of the system, this
variable is set to unknown(1).
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in: Status
Explore Observium network monitoring

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.4.1.3
Type
scalar
Access
readonly
Status
mandatory
Parent
upsBasicOutput

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBasicSystemStatus.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsBasicSystemStatus'

Syntax

Enumeration

Values & Constraints

Enumerated Values
1unknown
2onLine
3onBattery
4onSmartBoost
5timedSleeping
6softwareBypass
7off
8rebooting
9switchedBypass
10hardwareFailureBypass
11sleepingUntilPowerReturn
12onSmartTrim
13ecoMode
14inverter
15eConversion
16staticBypassStandby
17efficiencyBoosterMode