atsConfigBankOverLoadThreshold
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.8.4.14.1.5
Object
A threshold that indicates the current drawn has entered
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than or
equal to the threshold value.
Minimum value must be greater than or equal to the value
returned by the atsConfigBankNearOverLoadThreshold OID.
Maximum value must be less than or equal to the value returned by
atsIdentDeviceRating OID.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.8.4.14.1.5- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- atsConfigBankEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigBankOverLoadThreshold'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigBankOverLoadThreshold.<atsConfigBankTableIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::atsConfigBankOverLoadThreshold'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647