sPDUOutletConfigMSPgsLowBattWarning
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7
Object
column mandatory
r/w
Integer32
The amount of delay, in 6 second intervals, between
when the UPS goes on battery and the power down sequence for
the outlet is initiated.
Allowed values are:
-2 - Never initiate the power down sequence on low battery warning.
-1 - Initiate power down sequence based on remaining runtime.
1 - 9999 six second intervals (6 secs - 16hrs, 39 mins, 54 secs).
0 indicates to immediately initiate power down sequence on low
battery warning.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.6.6.2.1.1.7- Type
- column
- Access
- readwrite
- Status
- mandatory
- Parent
- sPDUOutletConfigMSPgsEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPgsLowBattWarning'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPgsLowBattWarning.<sPDUOutletConfigMSPgsIndex>.<sPDUOutletConfigMSPgsOutletIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::sPDUOutletConfigMSPgsLowBattWarning'
Syntax
Integer32
Values & Constraints
Object Constraints
range: -2-9999