isxModularDistSysPowerKwhUsage
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.22.4.3.2
Object
The total system energy consumed by the load equipment. This is the total since the date specified in the isxModularDistSysOutputKwhResetDate OID, and may be cleared using the isxModularDistSysOutputKwhReset OID. Measured in tenths of kWh.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.22.4.3.2- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- isxModularDistSysPower
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysPowerKwhUsage.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::isxModularDistSysPowerKwhUsage'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647