isxModularDistSysPowerKwhUsage

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.22.4.3.2

Object

scalar mandatory Integer32
The total system energy consumed by the load equipment.
This is the total since the date specified in the isxModularDistSysOutputKwhResetDate
OID, and may be cleared using the isxModularDistSysOutputKwhReset OID.
Measured in tenths of kWh.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.22.4.3.2
Type
scalar
Access
readonly
Status
mandatory
Parent
isxModularDistSysPower

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysPowerKwhUsage.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::isxModularDistSysPowerKwhUsage'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647