pmmOutputHighVoltThreshold

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.28.3.2.2.1.14

Object

column mandatory r/w Integer32
Threshold above which an output high voltage condition
will be generated. Specified as percent deviation from
nominal voltage represented in the OID pmmDeviceNominalOutputVoltage.
A value of zero indicates that the threshold is disabled.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.28.3.2.2.1.14
Type
column
Access
readwrite
Status
mandatory
Parent
pmmOutputEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmOutputHighVoltThreshold'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmOutputHighVoltThreshold.<pmmOutputMeterIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::pmmOutputHighVoltThreshold'

Syntax

Integer32

Values & Constraints

Object Constraints
range: 0-120