rARUStatusAruRemoteSetpoint
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.14.3.3.1.3
Object
column mandatory
Enumeration
This OID defines the desired base airflow of the ARU, or the
speed of the ARU fans when the temperature override is inactive.
See also the rARUConfigAruRemoteSetpoint OID.
NOTE: -1 will be returned if the ARU is not communicating.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.14.3.3.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- rARUStatusEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUStatusAruRemoteSetpoint'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUStatusAruRemoteSetpoint.<rARUStatusAruIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::rARUStatusAruRemoteSetpoint'
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | aruOff |
2 | aru85F-29C |
3 | aru90F-32C |
4 | aru95F-35C |
5 | aru100F-38C |
6 | aru7kW-1200cfm |
7 | aru5kW-800cfm |
8 | aru3kW-500cfm |
9 | aru2kW-300cfm |
10 | aru400cfm |
11 | aru600cfm |
12 | aru700cfm |
13 | aru900cfm |
14 | aru1000cfm |
15 | aru1400cfm |
16 | aru1600cfm |
17 | aru1800cfm |
18 | aru2000cfm |