atsConfigBankNearOverLoadThreshold

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.8.4.14.1.4

Object

column mandatory r/w Integer32
A threshold that indicates the current drawn is nearing
an overload condition. It is represented in Amps.
A warning will be issued when the load is greater than
or equal to the threshold value.
              
Minimum value must be greater than the value returned by
the atsConfigBankLowLoadThreshold OID.
              
Maximum value must be less than or equal to the value
returned by the atsConfigBankOverLoadThreshold OID.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.8.4.14.1.4
Type
column
Access
readwrite
Status
mandatory
Parent
atsConfigBankEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigBankNearOverLoadThreshold'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigBankNearOverLoadThreshold.<atsConfigBankTableIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::atsConfigBankNearOverLoadThreshold'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647