airFMSysCoolSetpointC
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.13.1.4.5.10
Object
The target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heater is installed. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.13.1.4.5.10- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- airFMSysCooling
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysCoolSetpointC.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::airFMSysCoolSetpointC'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647