isxModularDistSysPowerKwhPhaseUsage
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.22.4.3.5.1.3
Object
The energy consumed by the load equipment on this system output phase. This is the total since the date specified in the isxModularDistSysPowerKwhResetDate OID, and may be cleared using the isxModularDistSysPowerKwhReset OID. Measured in tenths of kWh.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.22.4.3.5.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- isxModularDistSysPowerEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysPowerKwhPhaseUsage'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysPowerKwhPhaseUsage.<isxModularDistSysPowerPhaseIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::isxModularDistSysPowerKwhPhaseUsage'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647