upsAdvConfigChargerRate

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.5.2.48

Object

scalar mandatory r/w Integer32
Change the maximum allowed UPS charge rate on select products where 100% represents
the manufacturer's recommended rate.  A charge/discharge rate of C/10 for a 10 Ah
battery would be 1 where C is defined as the charge or discharge rate equal to the
capacity of a battery divided by 1 hour. To increase the charge rate by a factor of
2 to C/5, this oid would be set to 200%.  This number would not change when external
packs are added or removed.  Charging at too high a rate can result in boiling and/or
venting of electrolyte and/or high gas pressure.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.5.2.48
Type
scalar
Access
readwrite
Status
mandatory
Parent
upsAdvConfig

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvConfigChargerRate.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsAdvConfigChargerRate'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647