rPDULoadBankConfigNearOverloadThreshold

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.12.2.4.1.1.3

Object

column mandatory r/w Integer32
A threshold that indicates the power consumption of
the load is nearing an overload condition. It is
represented in Amps.  A warning will be issued when the
load is greater than or equal to the threshold value.
              
Minimum value must be greater than the value returned by
the rPDULoadBankConfigLowLoadThreshold OID.
              
Maximum value must be less than or equal to the value
returned by the rPDULoadBankConfigOverloadThreshold OID.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.12.2.4.1.1.3
Type
column
Access
readwrite
Status
mandatory
Parent
rPDULoadBankConfigEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadBankConfigNearOverloadThreshold'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadBankConfigNearOverloadThreshold.<rPDULoadBankConfigIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::rPDULoadBankConfigNearOverloadThreshold'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647