PowerNet-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
369
Rows
369
Columns
2,817
.1.3.6.1.4.1.318.1.1.1.2.2.12
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvBatteryActualVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvBatteryActualVoltageTable'
A list of battery table entries. The number of battery frames present in UPS.
Information applicable to
each of the Battery frames.
each of the Battery frames.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsAdvBatteryActualVoltageTableIndexmandatory The Battery Frame identifier. Battery Frame index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.12.1.1 | ||||
upsAdvBatteryActualVoltagePolaritymandatory The selected Battery Voltage Polarity.0 indicates positive polarity. 1 indicates negative polarity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.2.12.1.2 | ||||
upsAdvBatteryFrameActualVoltagemandatory The actual battery bus voltage in Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.12.1.3 |
.1.3.6.1.4.1.318.1.1.1.2.2.13
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvTotalDCCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvTotalDCCurrentTable'
A list of Battery Frame table entries. The number of entries is given by the value of Number of Battery Frames.
An entry containing information applicable to a
particular Battery Frame.
particular Battery Frame.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsAdvTotalDCCurrentTableIndexmandatory The Battery Frame identifier. Total DC CurrentTable Index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.13.1.1 | ||||
upsAdvTotalDCCurrentPolaritymandatory The selected Battery Current Polarity.0 indicates positive polarity. 1 indicates negative polarity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.2.13.1.2 | ||||
upsAdvTotalFrameDCCurrentmandatory The Total DC Current of battery in Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.13.1.3 |
.1.3.6.1.4.1.318.1.1.1.2.2.14
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvBatteryCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvBatteryCurrentTable'
A list of Battery Frame table entries. The number of entries is given by number of Battery frames present.
An entry containing information applicable to a
particular battery frame.
particular battery frame.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsAdvBatteryCurrentTableIndexmandatory The Battery Frame identifier. Battery CurrentTable Index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.14.1.1 | ||||
upsAdvBatteryCurrentIndexmandatory The battery frame identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.14.1.2 | ||||
upsAdvBatteryCurrentPolaritymandatory The selected Battery current polarity.0 indicates positive polarity. 1 indicates negative polarity | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.2.14.1.3 | ||||
upsAdvBatteryFrameCurrentmandatory The Battery current measured in Amperes | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.2.14.1.4 |
.1.3.6.1.4.1.318.1.1.1.2.3.7
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsHighPrecBatteryActualVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecBatteryActualVoltageTable'
A list of Battery frame table entries. The number of entries is given by the number of Battery frames.
An entry containing information applicable to a
particular battery frame.
particular battery frame.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The Battery Frame identifier. High Precision Actual Voltage Table Index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.7.1.1 | ||||
| The selected Battery Voltage polarity. 0 indicates positive polarity. 1 indicates negative polarity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.3.7.1.2 | ||||
upsHighPrecBatteryVoltagemandatory The actual battery bus voltage expressed as tenths of Volts.If not supported, return -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.7.1.3 |
.1.3.6.1.4.1.318.1.1.1.2.3.8
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsHighPrecTotalDCCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecTotalDCCurrentTable'
A list of Battery Frame table entries. The number of entries is given by the number of battery frames.
An entry containing information applicable to a
particular battery frame.
particular battery frame.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsHighPrecTotalDCCurrentTableIndexmandatory The Battery Frame identifier.High precision Total DC Current index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.8.1.1 | ||||
upsHighPrecTotalDCCurrentPolaritymandatory The selected Battery Current polarity.0 indicates positive polarity. 1 indicates negative polarity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.3.8.1.2 | ||||
upsHighPrecTotalDCFrameCurrentmandatory The total DC current in tenths of Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.8.1.3 |
.1.3.6.1.4.1.318.1.1.1.2.3.9
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsHighPrecBatteryCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecBatteryCurrentTable'
A list of Battery Frame table entries. The number of entries is given by the number of battery frames.
An entry containing information applicable to a
particular battery frame.
particular battery frame.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsHighPrecBatteryCurrentTableIndexmandatory The Battery frame identifier.Battery Frame index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.9.1.1 | ||||
upsHighPrecBatteryCurrentIndexmandatory The Battery frame identifier.Battery Index for each frame. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.9.1.2 | ||||
upsHighPrecBatteryCurrentPolaritymandatory The selected Battery Current polarity.0 indicates positive polarity. 1 indicates negative polarity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.3.9.1.3 | ||||
upsHighPrecBatteryFrameCurrentmandatory The Battery current in tenths of Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.9.1.4 |
.1.3.6.1.4.1.318.1.1.1.2.3.10.2
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsHighPrecBatteryPackTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecBatteryPackTable'
A list of Battery Pack table entries. The number of entries is given by number of Battery Packs present.
An entry containing information applicable to a
particular battery pack.
particular battery pack.
| Column | Syntax | OID |
|---|---|---|
upsHighPrecBatteryPackIndexmandatory The battery pack identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1 |
upsHighPrecBatteryCartridgeIndexmandatory The battery cartridge identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2 |
| The battery pack firmware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3 |
upsHighPrecBatteryPackSerialNumbermandatory The battery pack serial number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4 |
upsHighPrecBatteryPackTemperaturemandatory The battery pack temperature measured in 10ths of degree Celcius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5 |
upsHighPrecBatteryPackStatusmandatory The battery status for the pack only.bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8… | OctetString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6 |
| The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order… | OctetString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7 |
| The battery cartridge estimated battery replace date. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8 |
| The battery cartridge install date. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9 |
| The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 General… | OctetString | .1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10 |
.1.3.6.1.4.1.318.1.1.1.2.3.10.4
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsHighPrecBatteryPackOnlyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsHighPrecBatteryPackOnlyTable'
A list of Battery Pack table entries. The number of entries is given by number of Battery Packs present.
An entry containing information applicable to a
particular battery pack.
particular battery pack.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsHighPrecBatteryPackOnlyIndexmandatory The battery pack identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1 |
| The battery pack firmware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2 |
| The battery pack serial number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3 |
| The battery pack temperature measured in 10ths of degree Celcius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4 |
upsHighPrecBatteryPackOnlyStatusmandatory The battery status for the pack only.bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8… | OctetString | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5 |
upsHighPrecBatteryPackOnlyHealthmandatory The battery pack health.bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement pack bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replaceme… | OctetString | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6 |
| The battery pack estimated battery replace date. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7 |
| The battery pack install date. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8 |
| The battery pack manufacture date. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.9 |
upsHighPrecBatteryPackOnlySKUmandatory The battery pack SKU. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.10 |
.1.3.6.1.4.1.318.1.1.1.2.5
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBatteryCabinetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabinetTable'
Table of battery cabinets
An entry containing information applicable to a
particular battery cabinet.
particular battery cabinet.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
upsBatteryCabinetIndexoptional The Battery Cabinet identifier. Battery CabinetTable Index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.1 | ||||||||
upsBatteryCabinetLocalIndexoptional The identification number for the actual battery cabinet in the system.0 corresponds to the internal batteries 1 and higher corresponds to external battery cabinets | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.2 | ||||||||
| The value indicates the wiring configuration, whether the battery is 2-wire or 3-wire. If it's a 3-wire battery system, the system can have two voltages and currents per cabinet. 1 = 2-wire (a non-split battery) 2 = 3-w… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.5.1.3 | ||||||||
| The battery voltage. For a non-split battery, it is the full voltage. For a split battery, the value is the voltage for one side/half of the battery | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.4 | ||||||||
| The voltage for the second side/half of the battery in a split battery system. If it is not a split battery, this reports -1 | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.5 | ||||||||
| The battery current. For a non-split battery, it is the full current. For a split battery, the value is the current for one side/half of the battery | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.6 | ||||||||
| The current for the second side/half of the battery in a split battery system. If it is not a split battery, this reports -1 | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.7 | ||||||||
upsBatteryCabinetTemperatureoptional The measured temperature of the battery cabinet in tenths of degrees Celcius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.8 | ||||||||
upsBatteryCabinetMaxTemperatureoptional The highest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.If there are multiple sensors in the battery cabinet, it is the selected highest actual value of measured temperature… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.9 | ||||||||
upsBatteryCabinetMinTemperatureoptional The lowest temperature measured for the battery in the battery cabinet in tenths of degrees Celcius.If there are multiple sensors in the battery cabinet, it is the selected lowest actual value of measured temperatures.… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.10 | ||||||||
| The average temperature for all the battery sensors in the battery cabinet and for the battery strings, if battery strings are present. Measured in tenths of degrees Celcius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.11 | ||||||||
upsBatteryCabinetFuseoptional If the battery cabinet has a common fuse, the status is given by this value.1 = Fuse open 2 = Fuse OK 3 = Not present | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.5.1.12 | ||||||||
upsBatteryCabinetBreakeroptional The value indicates the battery cabinet breaker status. Reports 1 if no breaker is present.1 = No breaker 2 = Unknown 3 = Breaker open 4 = Breaker closed | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.5.1.13 | ||||||||
upsBatteryCabinetNumberOfStringsoptional The number of battery strings in the battery cabinet. The value can be 0,meaning that no additional information on the battery string is available. 1 and higher means data in the table is provided. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.14 | ||||||||
| The number of vertical levels or shelves for battery blocks/modules. The levels are indexed from the bottom up | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.15 | ||||||||
| The number of horizontal positions for battery blocks/modules. The levels are indexed from left to right | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.5.1.16 |
.1.3.6.1.4.1.318.1.1.1.2.6
·
1 row entry
·
9 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBatteryCabStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabStringTable'
Table of battery strings in the complete battery solution
An entry containing information applicable to a particular battery string
in the battery cabinet.
in the battery cabinet.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
upsBatteryCabStringIndexoptional The battery cabinet string identifier. Battery cabinet string or halfstringtable index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.1 | ||||||
upsBatteryCabStringCabReferenceoptional Reference to the global battery cabinet index where the battery string is placed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.2 | ||||||
upsBatteryCabStringLocalIndexoptional Local battery string identification index in the actual battery cabinet (e.g. String 2 in cabinet) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.3 | ||||||
upsBatteryCabStringCurrentoptional The current in a battery string or battery halfstring, in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.4 | ||||||
| Temperature of the battery string or the average of the aggregated temperature of each battery block/module (in tenths of degrees Celcius). If not available, this variable is set to (-1999). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.5 | ||||||
| The actual highest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.6 | ||||||
| The actual lowest battery temperature measurement for the battery blocks/modules (in tenths of degrees Celcius). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.7 | ||||||
upsBatteryCabStringFuseStatusoptional If the battery string has a common fuse, the status is given by this value.1 = Fuse open 2 = Fuse OK 3 = Not present | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.6.1.8 | ||||||
| The number of battery blocks/modules in a battery string. Can be 0, if no data is available in the table of individual battery blocks/cartridges | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.6.1.9 |
.1.3.6.1.4.1.318.1.1.1.2.7
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBatteryCabBlockTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabBlockTable'
Table of battery blocks/modules in the complete battery solution.
An entry containing information applicable to a particular battery block
in the battery cabinet.
in the battery cabinet.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
upsBatteryCabBlockIndexoptional The battery cabinet block identifier. Global battery cabinet blocktable index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.1 | ||||||
| Reference to the specific global battery string index | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.2 | ||||||
upsBatteryCabBlockLocalIndexoptional Local battery block/module identification index in the actual battery string (e.g. Battery block 3 in the battery string) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.3 | ||||||
upsBatteryCabBlockPresentoptional Value indicates if battery block/module is present in the system.Typically battery modules are removable and battery blocks are static. Reports notAvailable(3) if data is not available | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.7.1.4 | ||||||
upsBatteryCabBlockTypeoptional Text string value, showing the vendor and model of the battery in the battery block/module | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.2.7.1.5 | ||||||
upsBatteryCabBlockTemperatureoptional The temperature for the battery block/module in tenths of degrees Celcius.If multiple sensors are available it is the highest temperature in the battery block/module | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.6 | ||||||
upsBatteryCabBlockFuseStatusoptional If the battery module has a fuse, the status is given by this value.1 = Fuse open 2 = Fuse OK 3 = Not present | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.2.7.1.7 | ||||||
upsBatteryCabBlockVoltageoptional The voltage of the battery block/module | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.8 | ||||||
upsBatteryCabBlockNumberOfCellsoptional The number of cells in the battery block/module | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.9 | ||||||
| The vertical position of the battery block/module in the actual battery cabinet (e.g. 4, if it is the 4th shelf counting from the bottom) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.10 | ||||||
| The horizontal position of the battery block/module in the actual battery cabinet (e.g. 3, if it is the 3rd position counting from the left) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.7.1.11 |
.1.3.6.1.4.1.318.1.1.1.2.8
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBatteryCabBlockCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabBlockCellTable'
Table of battery cells in a battery block/module in the complete battery solution
An entry containing information applicable to a particular battery cell
inside the battery block.
inside the battery block.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsBatteryCabBlockCellIndexoptional The battery block cell identifier. Global battery block celltable index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.8.1.1 |
upsBatteryCabBlockCellReferenceoptional Reference to the specific global battery block/module index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.8.1.2 |
upsBatteryCabBlockCellLocalIndexoptional Local battery block/module identification index in the actual battery block (e.g. battery cell 5 in the battery block) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.8.1.3 |
upsBatteryCabBlockCellVoltageoptional The measured battery cell voltage | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.8.1.4 |
| The temperature for the battery cell in tenths of degrees Celcius. If there is not a temperature sensor for each battery cell, then report -1 for those, which are not present. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.2.8.1.5 |
.1.3.6.1.4.1.318.1.1.1.3.2.10
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvInputStatisticsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvInputStatisticsTable'
A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs.
An entry containing information applicable to a
particular input.
particular input.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsAdvInputStatisticsIndexmandatory The input identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.1 |
upsAdvInputApparentPowermandatory The input apparent power(sum of all of the three phases) measured in kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.2 |
upsAdvInputVoltageTHDmandatory The input voltage Total Harmonic Distortion in percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.3 |
upsAdvInputBypassVoltageTHDmandatory The bypass input voltage Total Harmonic Distortion in percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.4 |
upsAdvInputPeakCurrentmandatory The input peak current in Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.5 |
upsAdvInputBypassPeakCurrentmandatory The bypass input peak current in Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.6 |
upsAdvInputActivePowermandatory The input active power measured in kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.3.2.10.1.7 |
.1.3.6.1.4.1.318.1.1.1.4.2.10
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvOutputStatisticsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvOutputStatisticsTable'
A list of input table entries. The number of entries is given by the value of upsPhaseNumOutputs.
An entry containing information applicable to a
particular output.
particular output.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsAdvOutputStatisticsIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.4.2.10.1.1 |
upsAdvOutputPeakCurrentmandatory The output peak current in Amperes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.4.2.10.1.2 |
upsAdvOutputCurrentTHDmandatory The output current Total Harmonic Distortion in percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.4.2.10.1.3 |
upsAdvOutputCrestFactormandatory The output current crest factor expressed in tenths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.4.2.10.1.4 |
.1.3.6.1.4.1.318.1.1.1.5.1.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBasicConfigDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBasicConfigDeviceTable'
A list of devices that are plugged into the UPS. The number of entries is given by the value of upsBasicConfigNumDevices.
The devices plugged in to the UPS.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
deviceIndexmandatory The index of the device that is plugged into the UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.5.1.2.1.1 | ||||
deviceNamemandatory The name/description of the device plugged into the UPS. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.5.1.2.1.2 | ||||
vaRatingmandatory The volt-amp rating of the device plugged into the UPS. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.5.1.2.1.3 | ||||
acceptThisDevicemandatory An entry is added if yes, the entry is deleted if no. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.5.1.2.1.4 |
.1.3.6.1.4.1.318.1.1.1.5.2.13
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvConfigDipSwitchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvConfigDipSwitchTable'
Current settings of UPS dip switches.
The current setting of one dip switch.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dipSwitchIndexmandatory The index of a UPS dip switch. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.5.2.13.1.1 | ||||
dipSwitchStatusmandatory The setting of a UPS dip switch. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.5.2.13.1.2 |
.1.3.6.1.4.1.318.1.1.1.5.2.16
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsAdvConfigAllowedSetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsAdvConfigAllowedSetTable'
The table listing the allowed values for all discrete configurable UPS variables.
The table entry for a configurable UPS variable.
Indexes
| Column | Syntax | OID |
|---|---|---|
apcUpsConfigFieldIndexmandatory The index to an eeprom field entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.5.2.16.1.1 |
apcUpsConfigFieldOIDmandatory The OID of the current configurable value. | ObjectIdentifier | .1.3.6.1.4.1.318.1.1.1.5.2.16.1.2 |
apcUpsConfigFieldValueRangemandatory The discrete set of allowed values of a configurableregister. Individual values are delimited by a comma. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.5.2.16.1.3 |
.1.3.6.1.4.1.318.1.1.1.9.2.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsPhaseInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsPhaseInputTable'
A list of input table entries. The number of entries is given by the value of upsPhaseNumInputs.
An entry containing information applicable to a
particular input.
particular input.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsPhaseInputTableIndexmandatory The input identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.1 | ||||||||||
upsPhaseNumInputPhasesmandatory The number of input phases utilized in thisdevice. The sum of all the upsPhaseNumInputPhases variable indicates the number of rows in the input phase table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.2 | ||||||||||
upsPhaseInputVoltageOrientationmandatory The input voltage orientation:1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2 … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.9.2.2.1.3 | ||||||||||
upsPhaseInputFrequencymandatory The input frequency in 0.1 Hertz, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.4 | ||||||||||
upsPhaseInputTypemandatory The input type. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.9.2.2.1.5 | ||||||||||
upsPhaseInputNamemandatory A name given to a particular input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.9.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.1.9.2.3
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsPhaseInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsPhaseInputPhaseTable'
A list of input table entries. The number of entries is given by the sum of the upsPhaseNumInputPhases.
An entry containing information applicable to a
particular input phase.
particular input phase.
| Column | Syntax | OID |
|---|---|---|
upsPhaseInputPhaseTableIndexmandatory The input identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.1 |
upsPhaseInputPhaseIndexmandatory The input phase identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.2 |
upsPhaseInputVoltagemandatory The input voltage in VAC, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.3 |
upsPhaseInputMaxVoltagemandatory The maximum input voltage in VAC measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.4 |
upsPhaseInputMinVoltagemandatory The minimum input voltage in VAC measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.5 |
upsPhaseInputCurrentmandatory The input current in 0.1 amperes, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.6 |
upsPhaseInputMaxCurrentmandatory The maximum input current in 0.1 amperes measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.7 |
upsPhaseInputMinCurrentmandatory The minimum input current in 0.1 amperes measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.8 |
upsPhaseInputPowermandatory The input power in Watts, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.9 |
upsPhaseInputMaxPowermandatory The maximum input power in Watts measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.10 |
upsPhaseInputMinPowermandatory The minimum input power in Watts measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.11 |
upsPhaseInputApparentPowermandatory The input apparent power of the UPS in kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.12 |
upsPhaseInputPowerFactormandatory The input power factor measured in hundredth. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.13 |
upsPhaseInputVoltagePNmandatory The input voltage measured across Phase to Neutral in VAC, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.2.3.1.14 |
.1.3.6.1.4.1.318.1.1.1.9.3.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsPhaseOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsPhaseOutputTable'
A list of output table entries. The number of entries is given by the value of upsOutputNumPhases.
An entry containing information applicable to a
particular output.
particular output.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsPhaseOutputTableIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.2.1.1 | ||||||||||
upsPhaseNumOutputPhasesmandatory The number of output phases utilized in thisdevice. The sum of all the upsPhaseNumOutputPhases variable indicates the number of rows in the output phase table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.2.1.2 | ||||||||||
upsPhaseOutputVoltageOrientationmandatory The output voltage orientation:1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.9.3.2.1.3 | ||||||||||
upsPhaseOutputFrequencymandatory The output frequency in 0.1 Hertz, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.2.1.4 |
.1.3.6.1.4.1.318.1.1.1.9.3.3
·
1 row entry
·
23 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsPhaseOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsPhaseOutputPhaseTable'
A list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases.
An entry containing information applicable to a
particular output phase.
particular output phase.
| Column | Syntax | OID |
|---|---|---|
upsPhaseOutputPhaseTableIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.1 |
upsPhaseOutputPhaseIndexmandatory The output phase identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.2 |
upsPhaseOutputVoltagemandatory The output voltage in VAC, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.3 |
upsPhaseOutputCurrentmandatory The output current in 0.1 amperes drawnby the load on the UPS, or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.4 |
upsPhaseOutputMaxCurrentmandatory The maximum output current in 0.1 amperes measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.5 |
upsPhaseOutputMinCurrentmandatory The minimum output current in 0.1 amperes measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.6 |
upsPhaseOutputLoadmandatory The output load in VA, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.7 |
upsPhaseOutputMaxLoadmandatory The maximum output load in VA measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.8 |
upsPhaseOutputMinLoadmandatory The minimum output load in VA measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.9 |
upsPhaseOutputPercentLoadmandatory The percentage of the UPS load capacity in VA atredundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.10 |
upsPhaseOutputMaxPercentLoadmandatory The maximum percentage of the UPS load capacity inVA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. S… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.11 |
upsPhaseOutputMinPercentLoadmandatory The minimum percentage of the UPS load capacity inVA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. S… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.12 |
upsPhaseOutputPowermandatory The output power in Watts, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.13 |
upsPhaseOutputMaxPowermandatory The maximum output power in Watts measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.14 |
upsPhaseOutputMinPowermandatory The minimum output power in Watts measuredsince the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.15 |
upsPhaseOutputPercentPowermandatory The percentage of the UPS power capacity in Watts atredundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.16 |
upsPhaseOutputMaxPercentPowermandatory The maximum percentage of the UPS power capacityin Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UP… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.17 |
upsPhaseOutputMinPercentPowermandatory The maximum percentage of the UPS power capacityin Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UP… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.18 |
upsPhaseOutputPowerFactormandatory The Output power factor of the UPS in hundredth. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.19 |
upsPhaseOutputApparentPowermandatory Apparent power in kVA | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.20 |
upsPhaseOutputInverterVoltagemandatory Output voltage in VAC measured at the output of inverter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.21 |
upsPhaseOutputVoltagePNmandatory The output voltage measured across Phase to Neutral in VAC, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.22 |
upsPhaseOutputEnergyUsagemandatory The output energy usage of the phase in hundredths of kWh. | Unsigned32 Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.1.9.3.3.1.23 |
.1.3.6.1.4.1.318.1.1.1.10.2.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsSCGStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsSCGStatusTable'
A list of SCG status table entries. The number of entries is given by the value of upsSCGNumOfGroupMembers.
An entry containing information applicable to a
particular SCG Member.
particular SCG Member.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsSCGStatusTableIndexmandatory The index of a status entry for an active, communicating SCG member. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.10.2.2.1.1 | ||||
upsSCGMemberIPmandatory The IP address of an active, communicating SCG Member. | RFC1155-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.1.10.2.2.1.2 | ||||
upsSCGACInputStatusmandatory This OID indicates the AC Input Status of the SCG Member.acInGood(1) indicates the AC Input is within tolerance. acInBad(2) indicates the AC Input is not within tolerance. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.10.2.2.1.3 | ||||
upsSCGACOutputStatusmandatory This OID indicates the AC Output Status of the SCG Member.acOutOn(1) indicates the UPS output is providing power to the load. acOutOff(2) indicates the UPS output is not providing power to the load. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.10.2.2.1.4 |
.1.3.6.1.4.1.318.1.1.1.12.1.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsOutletGroupStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsOutletGroupStatusTable'
Allows for getting status of the outlet groups. The number of entries is contained in the upsOutletGroupStatusTableSize OID.
The outlet group status to get.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
upsOutletGroupStatusIndexmandatory The index to the outlet group entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.1.2.1.1 | ||||||
upsOutletGroupStatusNamemandatory The name of the outlet group. This OID is providedfor informational purposes only. This value is set by the upsOutletGroupConfigName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.12.1.2.1.2 | ||||||
upsOutletGroupStatusGroupStatemandatory Getting this variable will return the outlet group state. If the outletgroup is on, the upsOutletGroupStatusOn (1) value will be returned. If the outlet group is off, the upsOutletGroupStatusOff (2) value will be retur… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.1.2.1.3 | ||||||
upsOutletGroupStatusCommandPendingmandatory Getting this variable will return the command pendingstate of the outlet group. If a command is pending on the outlet group, the upsOutletGroupCommandPending (1) value will be returned. If there is not a command pendin… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.1.2.1.4 | ||||||
upsOutletGroupStatusOutletTypemandatory Getting this variable will return the type of outlet group.If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.1.2.1.5 | ||||||
upsOutletGroupStatusGroupFullStatemandatory An ASCII string containing the 32 flags representing thecurrent state(s) of the outlet group. If the Network Card is unable to determine the state of the outlet group, this variable is set to 'UNKNOWN'. … | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.12.1.2.1.6 |
.1.3.6.1.4.1.318.1.1.1.12.2.2
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsOutletGroupConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsOutletGroupConfigTable'
The list of outlet groups to configure. The number of entries is defined by the upsOutletGroupConfigTableSize OID.
The outlet groups to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsOutletGroupConfigIndexmandatory The index to the outlet group entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.1 | ||||
upsOutletGroupConfigNamemandatory The name of the outlet group. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.2 | ||||
upsOutletGroupConfigPowerOnDelaymandatory The amount of time (seconds) the outlet group will delaypowering on when the delayed on, reboot, or shutdown command is applied. Allowed values vary by UPS model. The value of -1 is used for Never if supported by the U… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.3 | ||||
upsOutletGroupConfigPowerOffDelaymandatory The amount of time (seconds) the outlet group will delaypowering off when the delayed off, reboot, or shutdown command is applied. Allowed values vary by UPS model. The value of -1 is used for Never if supported by the… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.4 | ||||
upsOutletGroupConfigRebootDurationmandatory During a reboot sequence, power is turned off and thenback on. This OID defines the amount of time to wait (seconds) after turning the power off, at the start of the sequence, before initiating the power on sequence. A… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.5 | ||||
upsOutletGroupConfigMinReturnRuntimemandatory In an Outlet Group shutdown sequence, the Outlet Group cyclespower off then on. This OID defines the minimum amount of UPS runtime (seconds) that is required in order to power the Outlet Group on. Allowed values vary b… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.6 | ||||
upsOutletGroupConfigOutletTypemandatory Getting this variable will return the type of outlet group.If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.7 | ||||
| Configures whether the outlet group's off delay setting (upsOutletGroupConfigPowerOffDelay) will be used in a load shedding situation, where applicable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.8 | ||||
| Configures whether the outlet group will automatically restart after a load shedding situation, where applicable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.9 | ||||
| Configures whether the outlet group will load shed (turn off) after the UPS device's time on battery has exceeded the upsOutletGroupConfigLoadShedTimeOnBattery OID setting. The settings for upsOutletGroupConfigLoadShedC… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.10 | ||||
| Configures whether the outlet group will load shed (turn off) when the UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShedRuntimeRemaining OID setting. The settings for upsOutletGro… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.11 | ||||
| Configures whether the outlet group will load shed (turn off) when the UPS is in an overload condition. The setting for upsOutletGroupConfigLoadShedControlSkipOffDelay is valid for this load shed condition. Returns -1 i… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.2.2.1.12 | ||||
| When the UPS has been on battery for more time than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlTimeOnBattery OID. Allowed values vary by UPS model. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.13 | ||||
| When the runtime remaining is less than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlRuntimeRemaining OID. Allowed values vary by UPS model. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.2.2.1.14 |
.1.3.6.1.4.1.318.1.1.1.12.3.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsOutletGroupControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsOutletGroupControlTable'
Allows for control of individual outlet groups. The number of entries is contained in the upsOutletGroupControlTableSize OID.
The outlet group to control.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsOutletGroupControlIndexmandatory The index to the outlet group entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.12.3.2.1.1 | ||||||||||||||||||||
upsOutletGroupControlNamemandatory The name of the outlet group. This OID is providedfor informational purposes only. This value is set by the upsOutletGroupConfigName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.12.3.2.1.2 | ||||||||||||||||||||
upsOutletGroupControlCommandmandatory Getting this variable will return the outlet group state. If the outletgroup is on, the upsOutletGroupImmediateOn (1) value will be returned. If the outlet group is off, the upsOutletGroupImmediateOff (2) value will be… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.3.2.1.3 | ||||||||||||||||||||
upsOutletGroupControlOutletTypemandatory Getting this variable will return the type of outlet group.If present in the system, the main outlet group is 'unswitched' and must be on in order for any of the switched outlet groups to be on. Conversely, if the main… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.12.3.2.1.4 |
.1.3.6.1.4.1.318.1.1.1.13.1.2
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagIMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagIMTable'
Allows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagIMTableSize OID.
The diagnostics and information of an Intelligence Module.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagIMIndexmandatory The index to the Intelligence Module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.1 | ||||||||||||||
upsDiagIMTypemandatory The type of the Intelligence Module.imUnknown(1) indicates the IM type is unknown. imMIM(2) indicates the IM type is a Main Intelligence Module. imRIM(3) indicates the IM type is Redundant Intelligence Module. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.1.2.1.2 | ||||||||||||||
upsDiagIMStatusmandatory The status of the Intelligence Module.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.1.2.1.3 | ||||||||||||||
upsDiagIMFirmwareRevmandatory The firmware revision of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.4 | ||||||||||||||
upsDiagIMSlaveFirmwareRevmandatory The slave firmware revision of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.5 | ||||||||||||||
upsDiagIMHardwareRevmandatory The hardware revision of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.6 | ||||||||||||||
upsDiagIMSerialNummandatory The serial number of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.7 | ||||||||||||||
upsDiagIMManufactureDatemandatory The manufacture date of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.8 | ||||||||||||||
upsDiagIMInControlmandatory The Intelligence Module state.activeInControl(1) indicates the IM is active and in control. passive(2) indicates the IM is in passive state. unknown(3) indicates the IM is in unknown state. fault(4) indicates the IM is… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.1.2.1.9 | ||||||||||||||
upsDiagIMSKUmandatory The SKU of the Intelligence Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.1.2.1.10 |
.1.3.6.1.4.1.318.1.1.1.13.2.2
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagPMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagPMTable'
Allows for diagnostics of Individual Power modules. The number of entries is contained in the upsDiagPMTableSize OID.
The diagnostics of a Power Module.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagPMIndexmandatory The index to the Power Module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.1 | ||||||||||||||
upsDiagPMStatusmandatory The status of the Power Module.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.2.2.1.2 | ||||||||||||||
upsDiagPMFirmwareRevmandatory The firmware revision of the Power Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.3 | ||||||||||||||
upsDiagPMHardwareRevmandatory The hardware revision of the Power Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.4 | ||||||||||||||
upsDiagPMSerialNummandatory The serial number of the Power Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.5 | ||||||||||||||
upsDiagPMManufactureDatemandatory The manufacture date of the Power Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.6 | ||||||||||||||
upsDiagPMModelNummandatory The model number of the Power Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.7 | ||||||||||||||
upsDiagPMRatingoptional The power rating (in kVA) of the Power Module | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.8 | ||||||||||||||
upsDiagPMSKUoptional The SKU of the Power Module | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.9 | ||||||||||||||
upsDiagPMAverageFanSpeedoptional The average fan speed of the working fans in the Power Module in revolutions per minute (RPM).Returns (-1) if not set. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.10 | ||||||||||||||
upsDiagPMAmbientTemperatureoptional The ambient temperature inside the Power Module in tenths of degrees celsius.If not available, this variable is set to (-1999). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.2.1.11 |
.1.3.6.1.4.1.318.1.1.1.13.2.3
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagPMLifetimeInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagPMLifetimeInfoTable'
Allows for diagnostics of individual power module's lifetime information. The number of entries is contained in the upsDiagPMTableSize OID.
The diagnostics of a Power Module lifetime information.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
upsDiagPMLifetimeInfoIndexmandatory The index to the Power Module lifetime information entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.1 | ||||||||
upsDiagPMLifetimeStatusmandatory The status of the Power Module lifetime information.ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exc… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.2.3.1.2 | ||||||||
upsDiagPMEstmtdLifetimeRmngmandatory Displays the time remaining for the module before it should be replaced.Measured in months. This value is set when you originally install the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.3 | ||||||||
upsDiagPMEstmtdLifetimeRmngPctmandatory Displays the percentage of the total lifetime remaining for the modulebefore it should be replaced. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.4 | ||||||||
upsDiagPMFanLifetimeStatusmandatory The status of the Power Module Fan lifetime information.ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.2.3.1.5 | ||||||||
upsDiagPMFanEstmtdLifetimeRmngmandatory Displays the time remaining, measured in months, before the module'sfan should be replaced. It is reset by the field service engineer when a new fan is installed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.6 | ||||||||
upsDiagPMFanEstmtdLifetimeRmngPctmandatory Displays the percentage of the total lifetime remainingbefore the module's fan should be replaced. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.3.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.2.5
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagPMEnclDoorFltrTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagPMEnclDoorFltrTable'
Allows for the diagnostics of individual power module enclosure door filters. The number of entries is contained in the upsDiagPMEnclDoorFltrTableSize OID.
Power module door filter diagnostics info.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
upsDiagPMEnclIndexmandatory The index to the power module enclosure entry.Enclosure 0 indicates the Power enclosure 1. Enclosure 1 indicates the Power enclosure 2. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.5.1.1 | ||||||||
upsDiagPMEnclDoorFltrLifetimemandatory Door filter replacement time interval, based on the installation enivironment.heavyFiltration15days (1) indicates door filter needs to be replaced within 15 days. normalFiltration30days (2) indicates door filter needs … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.2.5.1.2 | ||||||||
upsDiagPMEnclDoorFltrStatusmandatory Indicates the current status of the door filter.ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime status is exceede… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.2.5.1.3 | ||||||||
| Displays the time remaining, measured in days, before the module door filter should be replaced. This value is set when you originally install the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.5.1.4 | ||||||||
| Displays the percentage of the total lifetime remaining for the module door filter before it should be replaced. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.2.5.1.5 |
.1.3.6.1.4.1.318.1.1.1.13.3.2
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagBatteryTable'
Allows for diagnostics of individual batteries. The number of entries is contained in the upsDiagBattTableSize OID.
The diagnostics of a battery.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagBatteryFrameIndexmandatory The index to the battery frame entry.Frame 0 indicates the Main frame. Extended Run (XR) frames start from index 1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.1 | ||||||||||||||
upsDiagBatteryIndexmandatory The index to the battery entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.2 | ||||||||||||||
upsDiagBatteryStatusmandatory The status of the battery.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the battery status is OK. failed(4) indicates the battery status is fa… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.3.2.1.3 | ||||||||||||||
upsDiagBatterySerialNumbermandatory The serial number of the battery. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.4 | ||||||||||||||
upsDiagBatteryFirmwareRevmandatory The firmware revision of the battery. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.5 | ||||||||||||||
upsDiagBatteryManufactureDatemandatory The manufacture date of the battery. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.6 | ||||||||||||||
upsDiagBatteryTypemandatory The battery type or rating for the battery. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.7 | ||||||||||||||
upsDiagBatteryFramePresentmandatory The battery frame/cabinet status.0 indicates frame/cabinet is not present. 1 indicates frame/cabinet is present. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.3.2.1.8 | ||||||||||||||
upsDiagBatteryFrameTemperaturemandatory The battery frame/cabinet temperature in tenths of degrees celsius.If the frame/cabinet is not present, this variable is set to (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.9 | ||||||||||||||
upsDiagBatterySKUmandatory The SKU of the battery. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.10 | ||||||||||||||
upsDiagBatteryHealthmandatory The battery health.bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement module bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement … | OctetString | .1.3.6.1.4.1.318.1.1.1.13.3.2.1.11 |
.1.3.6.1.4.1.318.1.1.1.13.3.4
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagBatteryFrameTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagBatteryFrameTable'
Allows for diagnostics of individual battery frame. The number of entries is contained in the upsDiagBatteryFrameTableSize OID.
The diagnostics of a battery frame.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsDiagBatteryFrameTableIndexmandatory The index to the battery frame entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.4.1.1 |
upsDiagBatteryModuleStatusPerFramemandatory An ASCII string containing the 64 flags representingthe status of battery modules. 1 indicates battery module installed, 0 indicates battery module not installed. The flags are numbered from 1 to 64, and… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.3.4.1.2 |
upsDiagBatteryPositiveVoltagemandatory The battery positive voltage, in Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.4.1.3 |
upsDiagBatteryNegativeVoltagemandatory The battery negative voltage, in Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.4.1.4 |
upsDiagBatteryTemperaturemandatory The battery frame/cabinet temperature in tenths of degrees celsius.If the frame/cabinet is not present, this variable is set to (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.3.4.1.5 |
.1.3.6.1.4.1.318.1.1.1.13.4.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysFrameTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysFrameTable'
Allows for diagnostics of individual XR Frames.
The diagnostics of an XR Frame.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysFrameIndexmandatory The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.1 | ||||||||||
upsDiagSubSysFrameTypemandatory The type of Frame.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. frameTypeMain(3) indicates the frame type is the Main Frame. frameTypeXR(4) indicates the fram… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.2.1.2 | ||||||||||
upsDiagSubSysFrameFirmwareRevmandatory The firmware revision of the frame. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.3 | ||||||||||
upsDiagSubSysFrameHardwareRevmandatory The hardware revision of the frame. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.4 | ||||||||||
upsDiagSubSysFrameSerialNummandatory The serial number of the frame. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.5 | ||||||||||
upsDiagSubSysFrameManufactureDatemandatory The manufacture date of the frame. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.6 | ||||||||||
upsDiagSubSysFrameSKUmandatory The SKU of the frame. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.4
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysIntBypSwitchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysIntBypSwitchTable'
Allows for diagnostics of the Internal Bypass Switch.
The diagnostics of the Internal Bypass Switch.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysIntBypSwitchFrameIndexmandatory The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.1 | ||||||||||||||
upsDiagSubSysIntBypSwitchIndexmandatory The Internal Bypass Switch index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.2 | ||||||||||||||
upsDiagSubSysIntBypSwitchStatusmandatory The Internal Bypass Switch status.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the devi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.4.1.3 | ||||||||||||||
upsDiagSubSysIntBypSwitchFirmwareRevmandatory The firmware revision of the Internal Bypass Switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.4 | ||||||||||||||
upsDiagSubSysIntBypSwitchHardwareRevmandatory The hardware revision of the Internal Bypass Switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.5 | ||||||||||||||
upsDiagSubSysIntBypSwitchSerialNummandatory The serial number of the Internal Bypass Switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.6 | ||||||||||||||
| The manufacture date of the Internal Bypass Switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.7 | ||||||||||||||
upsDiagSubSysIntBypSwitchModelNummandatory The model number of the Internal Bypass Switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.8 | ||||||||||||||
upsDiagSubSysIntBypFanSpeedoptional The average fan speed of the working fans in the Internal Bypass Switch in revolutions per minute (RPM).Returns (-1) if not set. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.9 | ||||||||||||||
| The ambient temperature in tenths of degrees celcius inside the Internal Bypass Switch. If not available, this variable is set to (-1999). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.4.1.10 |
.1.3.6.1.4.1.318.1.1.1.13.4.6
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysBattMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysBattMonitorTable'
Allows for diagnostics of the Battery Monitor Board.
The diagnostics of the Battery Monitor Board.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysBattMonitorFrameIndexmandatory The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.1 | ||||||||||||||
upsDiagSubSysBattMonitorIndexmandatory The index of the Battery Monitor Board. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.2 | ||||||||||||||
upsDiagSubSysBattMonitorStatusmandatory The status of the Battery Monitor Board.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates th… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.6.1.3 | ||||||||||||||
upsDiagSubSysBattMonitorFirmwareRevmandatory The firmware revision of the Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.4 | ||||||||||||||
upsDiagSubSysBattMonitorHardwareRevmandatory The hardware revision of the Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.5 | ||||||||||||||
upsDiagSubSysBattMonitorSerialNummandatory The serial number of the Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.6 | ||||||||||||||
| The date of the manufacture for the Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.6.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.8
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysExternalSwitchGearTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysExternalSwitchGearTable'
Allows for diagnostics of the individual External Switch Gear.
The diagnostics of an individual External Switch Gear.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.1 | ||||||||||||||
upsDiagSubSysExternalSwitchGearIndexmandatory The index of the External Switch Gear. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.2 | ||||||||||||||
| The status of the External Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.8.1.3 | ||||||||||||||
| The firmware revision of the External Switch Gear monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.4 | ||||||||||||||
| The hardware revision of the External Switch Gear monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.5 | ||||||||||||||
| The serial number of the External Switch Gear monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.6 | ||||||||||||||
| The date of the manufacture for the External Switch Gear monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.7 | ||||||||||||||
| The temperature of the air around the External Switch Gear monitor card in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.8.1.8 |
.1.3.6.1.4.1.318.1.1.1.13.4.10
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysDisplayInterfaceCardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysDisplayInterfaceCardTable'
Allows for diagnostics of individual Display Interface Cards.
The diagnostics of a Display Interface Card.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.10.1.1 | ||||||||||||||
| The index of the Display Interface Card. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.10.1.2 | ||||||||||||||
| The status of the Display Interface Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.10.1.3 |
.1.3.6.1.4.1.318.1.1.1.13.4.12
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysDCCircuitBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysDCCircuitBreakerTable'
Allows for diagnostics of individual DC Circuit Breakers.
The diagnostics of a DC Circuit Breaker.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.12.1.1 | ||||||||
upsDiagSubSysDCCircuitBreakerIndexmandatory The index of the DC Circuit Breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.12.1.2 | ||||||||
upsDiagSubSysDCCircuitBreakerStatusmandatory The status of the DC Circuit Breaker.unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.12.1.3 |
.1.3.6.1.4.1.318.1.1.1.13.4.14
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysSystemPowerSupplyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysSystemPowerSupplyTable'
Allows for diagnostics of individual System Power Supplies.
The diagnostics of a System Power Supply.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.1 | ||||||||||||||
upsDiagSubSysSystemPowerSupplyIndexmandatory The index of a System Power Supply. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.2 | ||||||||||||||
upsDiagSubSysSystemPowerSupplyStatusmandatory The status of the System Power Supply.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.14.1.3 | ||||||||||||||
| The firmware revision of the System Power Supply monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.4 | ||||||||||||||
| The hardware revision of the System Power Supply monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.5 | ||||||||||||||
| The serial number of the System Power Supply monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.6 | ||||||||||||||
| The date of the manufacture for the System Power Supply monitor card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.14.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.16
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysXRCommunicationCardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysXRCommunicationCardTable'
Allows for diagnostics of individual XR Communication Cards.
The diagnostics of an XR Communication Card.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.16.1.1 | ||||||||||||||
| The index of an XR Communication Card. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.16.1.2 | ||||||||||||||
| The status of the XR Communication Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates th… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.16.1.3 | ||||||||||||||
| The firmware revision of the XR Communication card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.16.1.4 | ||||||||||||||
| The serial number of the XR Communication card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.16.1.5 |
.1.3.6.1.4.1.318.1.1.1.13.4.18
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysExternalPowerFrameBoardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysExternalPowerFrameBoardTable'
Allows for diagnostics of individual External Power Frame Boards.
The diagnostics of an External Power Frame Board.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.18.1.1 | ||||||||||||||
| The index of an External Power Frame Board. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.18.1.2 | ||||||||||||||
| The status of the External Power Frame Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicat… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.18.1.3 |
.1.3.6.1.4.1.318.1.1.1.13.4.20
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysChargerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysChargerTable'
Allows for diagnostics of individual chargers.
The diagnostics of a charger.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysChargerFrameIndexmandatory The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.20.1.1 | ||||||||||||||
upsDiagSubSysChargerIndexmandatory The index of a charger. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.20.1.2 | ||||||||||||||
upsDiagSubSysChargerStatusmandatory The status of the Charger.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device statu… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.20.1.3 |
.1.3.6.1.4.1.318.1.1.1.13.4.22
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysInverterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysInverterTable'
Allows for diagnostics of individual Inverters.
The diagnostics of an Inverter.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysInverterFrameIndexmandatory The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.1 | ||||||||||||||
upsDiagSubSysInverterIndexmandatory The index of an Inverter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.2 | ||||||||||||||
upsDiagSubSysInverterStatusmandatory The status of the Inverter.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the device stat… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.22.1.3 | ||||||||||||||
upsDiagSubSysInverterFirmwareRevmandatory The firmware revision of the Inverter monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.4 | ||||||||||||||
upsDiagSubSysInverterHardwareRevmandatory The hardware revision of the Inverter monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.5 | ||||||||||||||
upsDiagSubSysInverterSerialNummandatory The serial number of the Inverter monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.6 | ||||||||||||||
upsDiagSubSysInverterManufactureDatemandatory The date of manufacture for the Inverter monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.22.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.24
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysPowerFactorCorrectionTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysPowerFactorCorrectionTable'
Allows for diagnostics of individual PowerFactorCorrections.
The diagnostics of a Power Factor Correction.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The frame index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.1 | ||||||||||||||
| The index of a Power Factor Correction. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.2 | ||||||||||||||
| The status of the Power Factor Correction. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.24.1.3 | ||||||||||||||
| The firmware revision of the Power Factor Correction monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.4 | ||||||||||||||
| The hardware revision of the Power Factor Correction monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.5 | ||||||||||||||
| The serial number of the Power Factor Correction monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.6 | ||||||||||||||
| The date of the manufacture for the Power Factor Correction monitor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.24.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.26
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysNetworkComCardTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysNetworkComCardTable'
Allows for getting diagnostics information of an individual Network Communication Card.
The diagnostics of a Network Communication Card.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsDiagSubSysNetworkComCardIndexmandatory The UPS network and display interface communication card index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.1 |
| A character string identifying the model number of the UPS network and display interface communication card. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.2 |
| A character string identifying the serial number of the UPS network and display interface communication card. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.3 |
| The date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.4 |
| The hardware revision of the UPS network and display interface communication card. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.5 |
| An ID string identifying the application firmware revision of the UPS network and display interface communication card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.6 |
| An ID string identifying the application operating system firmware revision of the UPS network and display interface communication card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.26.1.7 |
.1.3.6.1.4.1.318.1.1.1.13.4.28
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysUsrSuppBattMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysUsrSuppBattMonitorTable'
Allows for diagnostics of the user supplied Battery Monitor Board.
The diagnostics of the user supplied Battery Monitor Board.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysUsrSuppBattMonitorIndexmandatory The index of the user supplied Battery Monitor Board. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.28.1.1 | ||||||||||||||
| The status of the user supplied Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.28.1.2 | ||||||||||||||
| The firmware revision of the user supplied Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.28.1.3 | ||||||||||||||
| The hardware revision of the user supplied Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.28.1.4 | ||||||||||||||
| The serial number of the user supplied Battery Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.28.1.5 | ||||||||||||||
| The temperature of the air around the user supplied Battery Monitor Board in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.28.1.6 |
.1.3.6.1.4.1.318.1.1.1.13.4.31
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysPSUTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysPSUTable'
Allows for diagnostics of individual Power Supply Units. The number of entries is contained in the upsDiagSubSysPSUTableSize OID.
The diagnostics information of a Power Supply Unit.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysPSUIndexmandatory The index to the Power Supply Unit entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.31.1.1 | ||||||||||||||
upsDiagSubSysPSUStatusmandatory The status of the Power Supply Unit.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the de… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.31.1.2 |
.1.3.6.1.4.1.318.1.1.1.13.4.33
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysIDRCTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysIDRCTable'
Allows for diagnostics of the ID and Relay Controller Card.
The diagnostics of the ID and Relay Controller Card.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagSubSysIDRCIndexmandatory The index of the ID and Relay Controller Card. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.33.1.1 | ||||||||||||||
upsDiagSubSysIDRCStatusmandatory The status of the ID and Relay Controller Card.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indic… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.33.1.2 | ||||||||||||||
upsDiagSubSysIDRCFirmwareRevmandatory The firmware revision of the ID and Relay Controller Card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.33.1.3 | ||||||||||||||
upsDiagSubSysIDRCHardwareRevmandatory The hardware revision of the ID and Relay Controller Card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.33.1.4 | ||||||||||||||
upsDiagSubSysIDRCSerialNummandatory The serial number of the IDand Relay Controller Card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.4.33.1.5 |
.1.3.6.1.4.1.318.1.1.1.13.4.36
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysBackfeedContactorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysBackfeedContactorTable'
Backfeed protection contactor table.
A list of backfeed protection contactors.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
upsDiagSubSysbackfeedContactorIndexmandatory The index of the backfeed protection contactor. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.36.1.1 | ||||||
upsDiagSubSysbackfeedContactorNamemandatory The name of the backfeed protection contactor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.13.4.36.1.2 | ||||||
upsDiagSubSysbackfeedContactorTypemandatory Indicates the backfeed protection contactor types available in the UPS system.If the UPS is unable to find any attached contactors, this variable is set to unknown(1). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.36.1.3 | ||||||
upsDiagSubSysbackfeedContactorStatusmandatory The status of backfeed protection contactor.unknown(1) indicates the contactor status is unknown. opened (2) indicates the contactor is opened. closed (3) indicates the contactor is closed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.36.1.4 |
.1.3.6.1.4.1.318.1.1.1.13.4.38
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubSysIntBypSwitchFanLifetimeInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubSysIntBypSwitchFanLifetimeInfoTable'
Allows for diagnostics of the Internal Bypass Switch life time infomation.
The diagnostics of the Internal Bypass Switch.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| The index to the Internal Bypass Switch Fan liftime information entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.38.1.1 | ||||||||
| The status of the Internal Bypass Switch Fan lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end. exceeded(3) indicates the device lifetime… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.4.38.1.2 | ||||||||
| Displays the time remaining for the module before it should be replaced. Measured in months. This value is set when you originally install the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.38.1.3 | ||||||||
| Displays the percentage of the total lifetime remaining for the module before it should be replaced. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.4.38.1.4 |
.1.3.6.1.4.1.318.1.1.1.13.5.1.7
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSwitchGearBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSwitchGearBreakerTable'
Switchgear breaker table.
A list of switchgear breakers.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
switchgearBreakerIndexmandatory The index of the switchgear breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.1 | ||||||||||||||||||||
switchgearBreakerPresentmandatory Indicates if the switchgear breaker is present.notPresent(1) indicates that the breaker is not present. present(2) indicates that the breaker is present. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.2 | ||||||||||||||||||||
switchgearBreakerNamemandatory The name of the switchgear breaker. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.3 | ||||||||||||||||||||
switchgearBreakerTypemandatory Indicates the switchgear breaker types available in the UPS system.If the UPS is unable to find any attached breakers, this variable is set to unknown(1). If the system has multiple breakers of the same type (e.g. mul… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4 | ||||||||||||||||||||
switchgearBreakerStatusmandatory The status of switchgear breaker.unknown(1) indicates the breaker status is unknown. opened (2) indicates the breaker is opened. closed (3) indicates the breaker is closed. NOTE: If there are more than one breaker of t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.5 |
.1.3.6.1.4.1.318.1.1.1.13.5.1.9
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubFeedBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubFeedBreakerTable'
Subfeed breaker table.
A list of subfeed breakers.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
subfeedBreakerIndexmandatory The index of the subfeed breakers. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.1 | ||||||||
subfeedBreakerPresentmandatory Indicates if the subfeed breaker is present.notPresent (1) indicates that the breaker is not present. present (2) indicates that the breaker is present. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.2 | ||||||||
subfeedBreakerRatingmandatory The current rating of the installed subfeed breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.3 | ||||||||
| The maximum acceptable load before warning is issued. Expressed as percent of the subfeed breaker rating. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.4 | ||||||||
| The maximum load before a critical alarm occurs. Expressed as percent of the subfeed breaker rating. | Integer32r/w Constraints: range: 0-125 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.5 | ||||||||
subfeedBreakerStatusmandatory The status of the Circuit Breaker.unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4)… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6 | ||||||||
subfeedBreakerNamemandatory The name of the subfeed breaker. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.7 | ||||||||
subfeedBreakerCurrentmandatory The subfeed current in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.8 |
.1.3.6.1.4.1.318.1.1.1.13.5.1.11
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagSubFeedPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagSubFeedPhaseTable'
A list of subfeed phase table.
An entry containing information applicable to a
particular phase.
particular phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsDiagSubFeedBreakerIndexmandatory The subfeed breaker index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.1 |
upsDiagSubFeedPhaseIndexmandatory The subfeed phase index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.2 |
upsDiagSubFeedPhaseCurrentmandatory The subfeed phase current in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.3 |
upsDiagSubFeedPhaseCurrentAlternatemandatory The subfeed phase current in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.4 |
.1.3.6.1.4.1.318.1.1.1.13.5.1.15
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagUsrSuppSwitchgearMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagUsrSuppSwitchgearMonitorTable'
Allows for diagnostics of the user supplied Switch Gear Monitor Board.
The diagnostics of the user supplied Switch Gear Monitor Board.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagUsrSuppSwitchgearMonitorIndexmandatory The index of the user supplied Switch Gear Monitor Board. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.1 | ||||||||||||||
| The status of the user supplied Switch Gear Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. on… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.2 | ||||||||||||||
| The firmware revision of the user supplied Switch Gear Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.3 | ||||||||||||||
| The hardware revision of the user supplied Switch Gear Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.4 | ||||||||||||||
| The serial number of the user supplied Switch Gear Monitor Board. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.5 | ||||||||||||||
| The temperature of the air around the user supplied Switch Gear Monitor Board in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.6 |
.1.3.6.1.4.1.318.1.1.1.13.7.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagnosticPowerCabinetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagnosticPowerCabinetTable'
Allows for diagnostics of individual Power Cabinets. The number of entries is contained in the upsDiagnosticPowerCabinetTableSize OID.
The diagnostics of a Power Cabinet.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsDiagnosticPowerCabinetIndexmandatory The index to the Power Cabinet. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.7.2.1.1 |
| The ambient temperature of Power Cabinet in tenths of degrees Celsius. If the Power Cabinet is not present, this variable is set to (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.7.2.1.2 |
.1.3.6.1.4.1.318.1.1.1.13.9.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDiagUnitControllerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagUnitControllerTable'
Allows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagUnitControllerTableSize OID.
The diagnostics and information of an Intelligence Module.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsDiagUnitControllerIndexmandatory The index to the Unit Controller entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.13.9.2.1.1 | ||||||||||||||
upsDiagUnitControllerStatusmandatory The status of the Unit Controller.unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the device status is off and OK. onOk(4) indicates the devi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.13.9.2.1.2 | ||||||||||||||
upsDiagUnitControllerFirmwareRevmandatory The firmware revision of the Unit Controller. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.9.2.1.3 | ||||||||||||||
upsDiagUnitControllerHardwareRevmandatory The hardware revision of the Unit Controller. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.9.2.1.4 | ||||||||||||||
upsDiagUnitControllerSerialNummandatory The serial number of the Unit Controller. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.9.2.1.5 | ||||||||||||||
upsDiagUnitControllerModelNummandatory The model number of the Unit Controller. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.13.9.2.1.6 |
.1.3.6.1.4.1.318.1.1.1.14.7
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelInputPhaseTable'
A list of input table entries.
An entry containing information applicable to a
particular input phase.
particular input phase.
| Column | Syntax | OID |
|---|---|---|
upsParallelInputPhaseTableIndexmandatory The parallel unit identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.1 |
upsParallelInputPhaseIndexmandatory The input phase identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.2 |
upsParallelInputCurrentmandatory The input current in amperes, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.3 |
upsParallelInputActivePowermandatory The input power in kW, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.4 |
upsParallelInputApparentPowermandatory The input apparent power in kVA, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.5 |
upsParallelInputVoltagemandatory The input voltage of UPS in volts, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.6 |
upsParallelInputMaxVoltagemandatory The peak input voltage in VAC measured since the last reset,or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.7 |
upsParallelInputMaxCurrentmandatory The peak input current in amperes measured since last reset,or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.8 |
upsParallelInputTotalActivePowermandatory Total active input power of the parallel system in kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.9 |
upsParallelInputTotalApparentPowermandatory Total apparent input power of the parallel system in kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.7.1.10 |
.1.3.6.1.4.1.318.1.1.1.14.8
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelOutputPhaseTable'
A list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases.
An entry containing information applicable to a
particular output phase.
particular output phase.
| Column | Syntax | OID |
|---|---|---|
upsParallelOutputPhaseTableIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.1 |
upsParallelOutputPhaseIndexmandatory The output phase identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.2 |
upsParallelOutputCurrentmandatory The output current in amperes drawnby the load on the UPS, or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.3 |
upsParallelOutputLoadmandatory The output load in VA, or -1 if it's unsupportedby this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.4 |
upsParallelOutputPercentLoadmandatory The percentage of the UPS load capacity in VA atpresent redundancy being used on this output phase, or -1 if it's unsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.5 |
upsParallelOutputPowermandatory The output power in Watts, or -1 if it'sunsupported by this UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.8.1.6 |
.1.3.6.1.4.1.318.1.1.1.14.9
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelOutputApparentPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelOutputApparentPowerTable'
A list of output table entries. The number of entries is given by the value of upsOutputNumPhases.
An entry containing information applicable to a
particular output.
particular output.
| Column | Syntax | OID |
|---|---|---|
| The UPS parallel output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.9.1.1 |
upsParallelOutputApparentPowermandatory The apparent power of each of UPS in kVAwhen UPS are configured in parallel. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.9.1.2 |
.1.3.6.1.4.1.318.1.1.1.14.10
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelDiagSubSysBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelDiagSubSysBreakerTable'
Allows for diagnostics of parallel Circuit Breakers.
The diagnostics of Circuit Breaker.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| The Parallel UPS index entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.10.1.1 | ||||||||
upsParallelDiagSubSysBreakerIndexmandatory The index of the Circuit Breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.10.1.2 | ||||||||
upsParallelDiagSubSysBreakerStatusmandatory The status of the Circuit Breaker.unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. opened(3) indicates the circuit breaker is opened. closed(4)… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.14.10.1.3 | ||||||||
upsParallelDiagSubSysBreakerNamemandatory The name of Circuit Breaker. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.14.10.1.4 |
.1.3.6.1.4.1.318.1.1.1.14.12
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelOutputActivePowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelOutputActivePowerTable'
A list of output table entries. The number of entries is given by the value of upsParallelSysRemoteAddress.
An entry containing information applicable to a
particular output.
particular output.
| Column | Syntax | OID |
|---|---|---|
| The UPS parallel output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.12.1.1 |
upsParallelOutputActivePowermandatory The active power of each UPS in kWwhen UPS devices are configured in parallel. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.12.1.2 |
.1.3.6.1.4.1.318.1.1.1.14.17
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsParallelSysUpsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsParallelSysUpsTable'
A list of UPS table entries. The number of entries is given by the value of upsParallelSysUpsTableize.
An entry containing information applicable to a
particular UPS in parallel.
particular UPS in parallel.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsParallelSysUpsIndexmandatory The index to the Parallel System UPS table entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.14.17.1.1 | ||||||||||||||||||||||
upsParallelSysUpsNamemandatory The UPS id as assigned by the system. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.14.17.1.2 | ||||||||||||||||||||||
upsParallelSysUpsAlarmStatusmandatory The alarm status of the UPS.unknown(1) indicates the UPS status is unknown. normal(2) indicates UPS is functioning normally. informational(3) indicates informational alarm present in the UPS. warning(4) indicates warni… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.14.17.1.3 | ||||||||||||||||||||||
upsParallelSysUpsModemandatory The current operating mode of the UPS. If the UPS is unable todetermine the state of the UPS, this variable is set to unknown(1). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.14.17.1.4 | ||||||||||||||||||||||
upsParallelSysUpsSerialNumbermandatory The Serial number of the UPS in parallel.Equivalent to OID 1.3.6.1.4.1.318.1.1.1.1.2.3 (upsAdvIdentSerialNumber). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.14.17.1.5 |
.1.3.6.1.4.1.318.1.1.1.15.5
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsBatteryFrameLayoutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryFrameLayoutTable'
Battery frame layout position ID table.
A list of layout position IDs of battery frames.
Indexes
| Column | Syntax | OID |
|---|---|---|
batteryFrameIndexmandatory The index of the battery frame. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.5.1.1 |
batteryFramePositionIDmandatory Defines the position ID of each of the battery frames in the row. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.5.1.2 |
.1.3.6.1.4.1.318.1.1.1.15.7
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsSideCarFrameLayoutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsSideCarFrameLayoutTable'
Sidecar frame layout position ID table.
A list of sidecar frame layout position IDs.
Indexes
| Column | Syntax | OID |
|---|---|---|
sideCarFrameIndexmandatory The index of the sidecar frame. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.7.1.1 |
sideCarFramePositionIDmandatory Defines the position ID of each of the sidecar frames in the row. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.7.1.2 |
.1.3.6.1.4.1.318.1.1.1.15.9
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsPowerFrameLayoutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsPowerFrameLayoutTable'
Power frame layout position ID table.
A list of power frame layout position IDs.
Indexes
| Column | Syntax | OID |
|---|---|---|
powerFrameIndexmandatory The index of the power frame. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.9.1.1 |
powerFramePositionIDmandatory Defines the position ID of each of the power frames in the row. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.15.9.1.2 |
.1.3.6.1.4.1.318.1.1.1.16.5
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsIntegratedATSSourceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsIntegratedATSSourceTable'
Allows for getting status and settings for the ATS input sources. The number of entries is contained in the upsIntegratedATSSourceTableSize OID.
The input source status to get.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
upsIntegratedATSSourceIndexmandatory The index to the input source entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.16.5.1.1 | ||||||
upsIntegratedATSSourceNamemandatory The name of the input source. This OID is providedfor informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.16.5.1.2 | ||||||
upsIntegratedATSSourceStatusmandatory Getting this variable will return the input source status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.16.5.1.3 | ||||||
upsIntegratedATSLineFailDelaymandatory The delay between a selected input source becoming bad, and the ATS switching away from that source.This delay is used to make sure that the line has truly failed before the ATS will be switched. Specified in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.16.5.1.4 | ||||||
upsIntegratedATSLineStabilityDelaymandatory The delay between an unselected input source becoming good, and the ATS switching to that source.This delay is used to make sure that the line has truly returned before the ATS will be switched. Specified in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.16.5.1.5 |
.1.3.6.1.4.1.318.1.1.1.17.1.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsDCOutputStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDCOutputStatusTable'
Provides status information on UPS DC outputs. The number of entries is contained in the upsDCOutputStatusTableSize OID.
The DC output.
Indexes
| Column | Syntax | OID |
|---|---|---|
upsDCOutputStatusTableIndexmandatory The index to the DC output status entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.1 |
upsDCOutputStatusVoltageNominalmandatory The desired voltage for this output in tenths of VDC.When the output is on and there are no fault conditions, the actual voltage should be near the nominal. If not supported, return -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.2 |
upsDCOutputStatusCurrentRatingmandatory The amount of current this output is able to supply intenths of amperes. If not supported, return -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.3 |
upsDCOutputStatusVoltagemandatory The voltage measured on this output in tenths of VDC.If not supported, return -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.4 |
upsDCOutputStatusCurrentmandatory The current drawn by the load measured on this outputin tenths of amperes. If not supported, return -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.5 |
upsDCOutputStatusAbnormalConditionsmandatory An ASCII string containing flags representing activeoutput faults. If the Network Card is unable to determine the state of the faults, this variable is set to 'UNKNOWN'. The flags are numbered 1 onward, … | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.17.1.2.1.6 |
.1.3.6.1.4.1.318.1.1.1.18.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsOutputRelayStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsOutputRelayStatusTable'
Allows for access of individual relays.
The output relays to access.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsOutputRelayIndexmandatory The index to the output relay entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.18.1.2.1.1 | ||||
upsOutputRelayStatemandatory Getting this variable will return the output relay state.1 - normal state 2 - abnormal state | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.18.1.2.1.2 | ||||
upsOutputRelayDetailedStatusmandatory An ASCII string containing the 16 flags representingthe status of the output relay. The flags are numbered from 1 to 16, and read from left to right. The bits are defined as follows: Flag … | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.1.18.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.1.18.1.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsOutputRelayConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsOutputRelayConfigTable'
Allows for access of individual relays.
The output relays to access.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsOutputRelayConfigIndexmandatory The index to the output relay entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.18.1.4.1.1 | ||||||||||||||||||||
upsOutputRelayConfigDelaymandatory Output relay delay 0 - 86400 seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.18.1.4.1.2 | ||||||||||||||||||||
upsOutputRelayConfigCausemandatory This variable sets what causes the output relay state to change.1 - none 2 - on battery power failure 3 - on battery power failure expect during peak period 4 - low battery while on battery 5 - alarm 6 - fault 7 - outp… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.18.1.4.1.3 |
.1.3.6.1.4.1.318.1.1.1.18.2.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsInputContactStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsInputContactStatusTable'
Allows for access of individual contacts.
The input contacts to access.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
upsInputContactIndexmandatory The index to the input contact entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.18.2.2.1.1 | ||||
upsInputContactStatemandatory Getting this variable will return the input contact state.1 - normal state 2 - abnormal state | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.18.2.2.1.2 |
.1.3.6.1.4.1.318.1.1.1.18.2.4
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk upsInputContactConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsInputContactConfigTable'
Allows for access of individual contacts.
The input contacts to access.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
upsInputContactConfigIndexmandatory The index to the input contact entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.1.18.2.4.1.1 | ||||||||||||
upsInputContactConfigActionmandatory When the input contact changes state, this action occurs.1 - none 2 - self test 3 - external alarm on 4 - external alarm off 5 - output off no delay 6 - output on | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.1.18.2.4.1.2 |
.1.3.6.1.4.1.318.1.1.2.2.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mUpsContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mUpsContactTable'
A list of contacts supported by the Measure-UPS.
A contact entry containing information for a given contact.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
contactNumbermandatory An index identifying the contact on the Measure-UPS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.2.2.2.1.1 | ||||||
normalStatemandatory The normal operating position of the contact. If the normaloperating position cannot be set then it is controlled via the dip switch on the Measure-UPS and is therefore read-only. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.2.2.2.1.2 | ||||||
descriptionmandatory The description of the purpose/use of the contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.2.2.2.1.3 | ||||||
monitoringStatusmandatory A flag indicating whether this contact ismonitored, or not. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.2.2.2.1.4 | ||||||
currentStatusmandatory This value indicates the current state of the contact.If the contact is not in its normal state. This value is set to fault(2). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.2.2.2.1.5 |
.1.3.6.1.4.1.318.1.1.4.4.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletControlTable'
Allows for control of individual outlet switches. The number of entries is contained in the sPDUOutletControlTableSize OID.
The outlets to control.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sPDUOutletControlIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.4.4.2.1.1 | ||||||||||||||
sPDUOutletPendingmandatory Reports whether the current outlet has a pending command.If the commandPendingUnknown (3) value is returned, all devices powered by the PDU should be shut down. The PDU's power should then be cycled to c… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.4.4.2.1.2 | ||||||||||||||
sPDUOutletCtlmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value will be returned. If the state of the outlet… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.4.4.2.1.3 | ||||||||||||||
sPDUOutletCtlNamemandatory The name of the outlet. Maximum size is 20 characters.This OID is provided for informational purposes only. This value is set by the sPDUOutletName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.4.4.2.1.4 |
.1.3.6.1.4.1.318.1.1.4.5.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigTable'
The list of outlets to configure. The number of entries is defined by the sPDUOutletConfigTableSize OID.
The outlets to control.
Indexes
| Column | Syntax | OID |
|---|---|---|
sPDUOutletConfigIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.4.5.2.1.1 |
sPDUOutletPowerOnTimemandatory The amount of time (in seconds) the outlet will delaypowering on when the MasterSwitch is powered on. Allowed values are: -1 never power on automatically. 0 power on with the Master Switc… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.4.5.2.1.2 |
sPDUOutletNamemandatory The name of the outlet. Maximum size is 20 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.4.5.2.1.3 |
sPDUOutletPowerOffTimemandatory The amount of time (in seconds) the outlet will delaypowering off. Allowed values are: -1 never power off automatically. 0 power off with the MasterSwitch. 15 power off 15 seconds after b… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.4.5.2.1.4 |
sPDUOutletRebootDurationmandatory During a reboot sequence, power is turned off and thenback on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the en… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.4.5.2.1.5 |
.1.3.6.1.4.1.318.1.1.5.1.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUIdentVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUIdentVMTable'
Allows for query of the individual MasterSwitch VMs. The number of entries is contained in the sPDUIdentVMTableSize OID.
The MasterSwitch VMs to query.
Indexes
| Column | Syntax | OID |
|---|---|---|
sPDUIdentVMIndexmandatory The index to the MasterSwitch VM entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.1.2.1.1 |
sPDUIdentNameVMmandatory A 23-character string identifying theMasterSwitch VM. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.2 |
sPDUIdentHardwareRevVMmandatory The hardware version of the MasterSwitch VM.This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.3 |
sPDUIdentFirmwareRevVMmandatory An 6-character ID string identifying the MasterSwitch VMfirmware version. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.4 |
sPDUIdentDateOfManufactureVMmandatory The date when the MasterSwitch VM was manufactured in mm/dd/yyyy format.This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.5 |
sPDUIdentModelNumberVMmandatory A 17-character string identifying the model number ofthe MasterSwitch VM. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.6 |
sPDUIdentSerialNumberVMmandatory A 17-character string identifying the serial number ofthe MasterSwitch VM. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.1.2.1.7 |
.1.3.6.1.4.1.318.1.1.5.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterControlVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterControlVMTable'
Allows for control of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterControlVMTableSize OID.
The MasterSwitch VMs to control.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sPDUMasterControlVMIndexmandatory The index to the MasterSwitch VM entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.2.2.1.1 | ||||||||||||||||||||||
sPDUMasterControlVMNamemandatory The name of the MasterSwitch VM. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigVMName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.2.2.1.2 | ||||||||||||||||||||||
sPDUMasterControlVMCommandmandatory Setting this OID to immediateAllOnVM (2) will turn all outletson immediately. Setting this OID to immediateAllOffVM (3) will turn all outlets off immediately. Setting this OID to immediate… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.5.3.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterConfigVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterConfigVMTable'
Allows for configuration of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterConfigVMTableSize OID.
The MasterSwitch VMs to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
sPDUMasterConfigVMIndexmandatory The index to the MasterSwitch VM entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.3.2.1.1 | ||||||
sPDUMasterConfigVMNamemandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.5.3.2.1.2 | ||||||
sPDUMasterConfigVMColdstartDelaymandatory The amount of delay, in seconds, between whenpower is provided to the MasterSwitch VM and when the MasterSwitch VM provides basic master power to the outlets. Allowed values are: -1 never … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.3.2.1.3 | ||||||
| Setting this OID to audioAlarmActiveNever (1) will disable the audio alarm on the MasterSwitch VM. Setting this OID to audioAlarmActiveOnOverload (2) will activate the audio alarm on the MasterSwitch VM w… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.3.2.1.4 | ||||||
| A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented as a percentage of full load. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.5.3.2.1.5 | ||||||
| A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented as a percentage of full load. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.5.3.2.1.6 | ||||||
| This OID controls the behavior of the MasterSwitch VM when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always all… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.3.2.1.7 |
.1.3.6.1.4.1.318.1.1.5.4.2
·
1 row entry
·
9 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterStatusVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterStatusVMTable'
Allows for gathering of status from the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterStatusVMTableSize OID.
The MasterSwitch VMs to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUMasterStatusVMIndexmandatory The index to the MasterSwitch VM entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.4.2.1.1 | ||||
sPDUMasterStatusVMNamemandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.4.2.1.2 | ||||
sPDUMasterStatusVMCommandPendingmandatory Getting this OID will return commandPendingMasterTrueVM (1)if the MasterSwitch VM has a pending command on any of its outlets. commandPendingMasterFalseVM (2) will be returned if there are no pending com… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.4.2.1.3 | ||||
sPDUMasterStatusVMOverloadConditionmandatory Getting this OID will return overloadConditionTrueVM (1)if the sPDUMasterConfigVMHighLoadWarningThreshold OID is violated. overloadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadW… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.4.2.1.4 | ||||
sPDUMasterStatusVMLowLoadConditionmandatory Getting this OID will return lowLoadConditionTrueVM (1)if the sPDUMasterConfigVMLowLoadWarningThreshold OID is violated. lowLoadConditionFalseVM (2) will be returned if the sPDUMasterConfigVMHighLoadWarn… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.4.2.1.5 | ||||
sPDUMasterStatusVMCurrentLoadmandatory Getting this OID will return the total amount of powerbeing consumed by the load. It is represented as a percentage of full load. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.4.2.1.6 | ||||
sPDUMasterStatusVMMaxLoadmandatory Getting this OID will return the total amount of powerthat this MasterSwitch VM can provide. It is represented in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.4.2.1.7 | ||||
sPDUMasterStatusVMOutletCountmandatory Getting this OID will return the number of controllableoutlets for this MasterSwitch VM. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.4.2.1.8 | ||||
sPDUMasterStatusVMRebootDurationmandatory Getting this OID will return the largestsPDUOutletConfigVMRebootDuration OID time for this MasterSwitch VM. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.4.2.1.9 |
.1.3.6.1.4.1.318.1.1.5.5.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletControlVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletControlVMTable'
Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
The outlets to control.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sPDUOutletControlVMIndexmandatory The index to the MasterSwitch VM. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.5.1.1.1 | ||||||||||||||
sPDUOutletControlVMNamemandatory The name of the MasterSwitch VM. Maximum size is 23 characters.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.5.1.1.2 | ||||||||||||||
sPDUOutletControlVMOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.5.1.1.3 | ||||||||||||||
sPDUOutletControlVMOutletNamemandatory The name of the outlet. Maximum size is 23 characters.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.5.1.1.4 | ||||||||||||||
sPDUOutletControlVMOutletCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOnVM (1) value will be returned. If the outlet is off, the immediateOffVM (2) value will be returned. S… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.5.1.1.5 |
.1.3.6.1.4.1.318.1.1.5.6.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigVMTable'
Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
The outlets to configure.
| Column | Syntax | OID |
|---|---|---|
sPDUOutletConfigVMIndexmandatory The index to the MasterSwitch VM. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.6.1.1.1 |
sPDUOutletConfigVMNamemandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.6.1.1.2 |
sPDUOutletConfigVMOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.6.1.1.3 |
sPDUOutletConfigVMOutletNamemandatory The name of the outlet. Maximum size is 23 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.5.6.1.1.4 |
sPDUOutletConfigVMPowerOnTimemandatory The amount of time (in seconds) the outlet will delaypowering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 never power on. 0 power on … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.6.1.1.5 |
sPDUOutletConfigVMPowerOffTimemandatory The amount of time (in seconds) the outlet will delaypowering off when a command that requires a turn-off delay is issued. Allowed values are: -1 never power off automatical… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.6.1.1.6 |
sPDUOutletConfigVMRebootDurationmandatory During a reboot sequence, power is turned off and thenback on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the en… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.6.1.1.7 |
.1.3.6.1.4.1.318.1.1.5.7.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletStatusVMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletStatusVMTable'
Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
The outlets to gather status from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletStatusVMIndexmandatory The index to the MasterSwitch VM. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.7.1.1.1 | ||||
sPDUOutletStatusVMNamemandatory The name of the MasterSwitch VM. Maximum size is 23 characters. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.7.1.1.2 | ||||
sPDUOutletStatusVMOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.5.7.1.1.3 | ||||
sPDUOutletStatusVMOutletNamemandatory The name of the outlet. Maximum size is 23 characters. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.5.7.1.1.4 | ||||
sPDUOutletStatusVMOutletStatemandatory Getting this variable will return the outlet state. Ifthe outlet is on, the outletStatusOnVM (1) value will be returned. If the outlet is off, the outletStatusOffVM (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.7.1.1.5 | ||||
sPDUOutletStatusVMCommandPendingmandatory Getting this variable will return the command pendingstate of the outlet. If a command is pending on the outlet, the outletStatusVMCommandPending (1) value will be returned. If there is not a command pending on the out… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.5.7.1.1.6 |
.1.3.6.1.4.1.318.1.1.6.1.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUIdentMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUIdentMSPTable'
Allows for query of the individual MasterSwitch pluses. The number of entries is contained in the sPDUIdentMSPTableSize OID.
The MasterSwitch pluses to query.
Indexes
| Column | Syntax | OID |
|---|---|---|
sPDUIdentMSPIndexmandatory The index to the MasterSwitch plus entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.1.2.1.1 |
sPDUIdentNameMSPmandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.2 |
sPDUIdentHardwareRevMSPmandatory The hardware version of the MasterSwitch plus.This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.3 |
sPDUIdentFirmwareRevMSPmandatory An 6-character ID string identifying the MasterSwitch plusfirmware version. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.4 |
sPDUIdentDateOfManufactureMSPmandatory The date when the MasterSwitch plus was manufactured in mm/dd/yyyy format.This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.5 |
sPDUIdentModelNumberMSPmandatory A 17-character string identifying the model number ofthe MasterSwitch plus. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.6 |
sPDUIdentSerialNumberMSPmandatory A 17-character string identifying the serial number ofthe MasterSwitch plus. This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.1.2.1.7 |
.1.3.6.1.4.1.318.1.1.6.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterControlMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterControlMSPTable'
Allows for control of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterControlMSPTableSize OID.
The MasterSwitch pluses to control.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sPDUMasterControlMSPIndexmandatory The index to the MasterSwitch plus entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.2.2.1.1 | ||||||||||||||||||||
sPDUMasterControlMSPNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.2.2.1.2 | ||||||||||||||||||||
sPDUMasterControlMSPCommandmandatory Setting this OID to immediateAllOnMSP (2) will turn all outletson immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined by each outlet's sPDUOutletConfigMSPPowerOnDel… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.6.3.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterConfigMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterConfigMSPTable'
Allows for configuration of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterConfigMSPTableSize OID.
The MasterSwitch pluses to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUMasterConfigMSPIndexmandatory The index to the MasterSwitch plus entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.3.2.1.1 | ||||
sPDUMasterConfigMSPNamemandatory The name of the MasterSwitch plus. Maximum size is 23 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.6.3.2.1.2 | ||||
sPDUMasterConfigMSPPowerOnTimeDelaymandatory The amount of delay, in seconds, between whenpower is provided to the MasterSwitch plus and when the MasterSwitch plus provides basic master power to the outlets. Allowed values are: 0 - 9… | Integer32r/w Constraints: range: 0-9999 | .1.3.6.1.4.1.318.1.1.6.3.2.1.3 | ||||
sPDUMasterConfigMSPManualButtonmandatory Setting this OID to manualButtonDisabled (1) will disablethe manual button on the MasterSwitch plus. Setting this OID to manualButtonEnabled (2) will enable the manual button on the MasterSwitch plus. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.3.2.1.4 |
.1.3.6.1.4.1.318.1.1.6.4.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUMasterStatusMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUMasterStatusMSPTable'
Allows for gathering of status from the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterStatusMSPTableSize OID.
The MasterSwitch pluses to gather status from.
Indexes
| Column | Syntax | OID |
|---|---|---|
sPDUMasterStatusMSPIndexmandatory The index to the MasterSwitch plus entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.4.2.1.1 |
sPDUMasterStatusMSPNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.4.2.1.2 |
sPDUMasterStatusMSPOutletCountmandatory Getting this OID will return the number of controllableoutlets for this MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.4.2.1.3 |
.1.3.6.1.4.1.318.1.1.6.5.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletControlMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletControlMSPTable'
Allows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
The outlets to control.
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sPDUOutletControlMSPIndexmandatory The index to the MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.5.1.1.1 | ||||||||||||||||
sPDUOutletControlMSPNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.5.1.1.2 | ||||||||||||||||
sPDUOutletControlMSPOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.5.1.1.3 | ||||||||||||||||
sPDUOutletControlMSPOutletNamemandatory The name of the outlet. The maximum size is23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.5.1.1.4 | ||||||||||||||||
sPDUOutletControlMSPOutletCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOnMSP (1) value will be returned. If the outlet is off, the immediateOffMSP (3) value will be returned. Setting this v… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.5.1.1.5 |
.1.3.6.1.4.1.318.1.1.6.6.1.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigMSPallTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPallTable'
Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
The outlets to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletConfigMSPallIndexmandatory The index to the MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.1.1.1.1 | ||||
sPDUOutletConfigMSPallNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.1.1.1.2 | ||||
sPDUOutletConfigMSPallOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.1.1.1.3 | ||||
sPDUOutletConfigMSPallOutletNamemandatory The name of the outlet. Maximum size is 23 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.6.6.1.1.1.4 | ||||
sPDUOutletConfigMSPallOutletCtrlModemandatory Setting this OID to modeGracefulShutdown (1) will put thisoutlet into the Graceful Shutdown control mode. Setting this OID to modeAnnunciator (2) will put this outlet into the Annunciator control mode. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.1.1.1.5 |
.1.3.6.1.4.1.318.1.1.6.6.2.1
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigMSPgsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPgsTable'
Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
The outlets to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletConfigMSPgsIndexmandatory The index to the MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.1 | ||||
sPDUOutletConfigMSPgsNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.2 | ||||
sPDUOutletConfigMSPgsOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.3 | ||||
sPDUOutletConfigMSPgsOutletNamemandatory The name of the outlet. The maximum size is23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.4 | ||||
sPDUOutletConfigMSPgsOutletCtrlModemandatory The Control Mode of the outlet.This OID is provided for informational purposes only. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.2.1.1.5 | ||||
sPDUOutletConfigMSPgsDeviceConfirmmandatory Setting this OID to deviceConfirmNo (1) cause the outlet toNOT wait for device confirmation while performing graceful operations. Setting this OID to deviceConfirmYes (2) cause the outlet to wait for dev… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.2.1.1.6 | ||||
sPDUOutletConfigMSPgsLowBattWarningmandatory The amount of delay, in 6 second intervals, betweenwhen the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -2 - Never initiate the power d… | Integer32r/w Constraints: range: -2-9999 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.7 | ||||
sPDUOutletConfigMSPgsLowBattMultmandatory Only applicable if sPDUOutletConfigMSPgsLowBattWarning OID isset to -1 (On Runtime Remaining). Allows you to set the value to stagger the shutdown sequence of the outlets. 1 provides the longest delay (t… | Integer32r/w Constraints: range: 1-7 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.8 | ||||
sPDUOutletConfigMSPgsRestartDelaymandatory The amount of delay, in 6 minute intervals, betweenwhen the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed values are: -1 - Never turn o… | Integer32r/w Constraints: range: -1-9999 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.9 | ||||
sPDUOutletConfigMSPgsPowerOnDelaymandatory The amount of delay, in seconds, between the UPS enteringnormal (on-line) state and the outlet being powered on. Allowed values are: -1 - Remain Off when the UPS enters the on-line state. … | Integer32r/w Constraints: range: -1-9999 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.10 | ||||
sPDUOutletConfigMSPgsPowerOffDelaymandatory The amount of delay, in seconds, between when the servershuts down and the outlet is powered off. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | Integer32r/w Constraints: range: 0-9999 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.11 | ||||
sPDUOutletConfigMSPgsBattCapThreshmandatory The minimum battery capacity, as a percent (0-100%), requiredof the UPS before an outlet will be allowed to power on. Allowed values are: 0 - 100 percent. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.12 | ||||
sPDUOutletConfigMSPgsRebootDurationmandatory The amount of delay, in seconds, from outlet off untiloutlet on during a reboot. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs). | Integer32r/w Constraints: range: 0-9999 | .1.3.6.1.4.1.318.1.1.6.6.2.1.1.13 |
.1.3.6.1.4.1.318.1.1.6.6.3.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigMSPannunTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPannunTable'
Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
The outlets to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletConfigMSPannunIndexmandatory The index to the MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.3.1.1.1 | ||||
sPDUOutletConfigMSPannunNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.3.1.1.2 | ||||
sPDUOutletConfigMSPannunOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.3.1.1.3 | ||||
sPDUOutletConfigMSPannunOutletNamemandatory The name of the outlet. The maximum size is23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.3.1.1.4 | ||||
| The Control Mode of the outlet. This OID is provided for informational purposes only. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.3.1.1.5 | ||||
sPDUOutletConfigMSPannunInitialStatemandatory Setting this OID to initialStateOff (1) causes the outletto default to off when in the non-alarmed condition. Setting this OID to initialStateOn (2) causes the outlet to default to on when in the non-ala… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.3.1.1.6 | ||||
| The amount of time, in seconds, that an enabled Measure-UPS alarm must be asserted before an alarm condition is recognized. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs… | Integer32r/w Constraints: range: 0-9999 | .1.3.6.1.4.1.318.1.1.6.6.3.1.1.7 |
.1.3.6.1.4.1.318.1.1.6.6.4.1
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletConfigMSPmupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletConfigMSPmupsTable'
Allows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
The outlets to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletConfigMSPmupsIndexmandatory The index to the MasterSwitch plus. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.4.1.1.1 | ||||
sPDUOutletConfigMSPmupsNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.4.1.1.2 | ||||
sPDUOutletConfigMSPmupsOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.6.4.1.1.3 | ||||
sPDUOutletConfigMSPmupsOutletNamemandatory The name of the outlet. The maximum size is23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.6.4.1.1.4 | ||||
sPDUOutletConfigMSPmupsZone1mandatory Setting this OID to disableAlarm (1) disables theZone 1 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 1 alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.5 | ||||
sPDUOutletConfigMSPmupsZone2mandatory Setting this OID to disableAlarm (1) disables theZone 2 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 2 alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.6 | ||||
sPDUOutletConfigMSPmupsZone3mandatory Setting this OID to disableAlarm (1) disables theZone 3 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 3 alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.7 | ||||
sPDUOutletConfigMSPmupsZone4mandatory Setting this OID to disableAlarm (1) disables theZone 4 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 4 alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.8 | ||||
sPDUOutletConfigMSPmupsP1LowHummandatory Setting this OID to disableAlarm (1) disables theProbe 1 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low humidity alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.9 | ||||
sPDUOutletConfigMSPmupsP1HiHummandatory Setting this OID to disableAlarm (1) disables theProbe 1 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high humidity alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.10 | ||||
sPDUOutletConfigMSPmupsP1LowTempmandatory Setting this OID to disableAlarm (1) disables theProbe 1 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low temperature alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.11 | ||||
sPDUOutletConfigMSPmupsP1HiTempmandatory Setting this OID to disableAlarm (1) disables theProbe 1 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high temperature alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.12 | ||||
sPDUOutletConfigMSPmupsP2LowHummandatory Setting this OID to disableAlarm (1) disables theProbe 2 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low humidity alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.13 | ||||
sPDUOutletConfigMSPmupsP2HiHummandatory Setting this OID to disableAlarm (1) disables theProbe 2 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high humidity alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.14 | ||||
sPDUOutletConfigMSPmupsP2LowTempmandatory Setting this OID to disableAlarm (1) disables theProbe 2 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low temperature alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.15 | ||||
sPDUOutletConfigMSPmupsP2HiTempmandatory Setting this OID to disableAlarm (1) disables theProbe 2 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high temperature alarm for this outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.6.4.1.1.16 |
.1.3.6.1.4.1.318.1.1.6.7.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk sPDUOutletStatusMSPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::sPDUOutletStatusMSPTable'
Allows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
The outlets to gather status from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sPDUOutletStatusMSPIndexmandatory The index to the MasterSwitch MSP. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.7.1.1.1 | ||||
sPDUOutletStatusMSPNamemandatory The name of the MasterSwitch plus. The maximumvalue is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.7.1.1.2 | ||||
sPDUOutletStatusMSPOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.6.7.1.1.3 | ||||
sPDUOutletStatusMSPOutletNamemandatory The name of the outlet. The maximum size is23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.6.7.1.1.4 | ||||
sPDUOutletStatusMSPOutletStatemandatory Getting this variable will return the outlet state. Ifthe outlet is on, the outletStatusMSPOn (1) value will be returned. If the outlet is off, the outletStatusMSPOff (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.7.1.1.5 | ||||
sPDUOutletStatusMSPCommandPendingmandatory Getting this variable will return the command pendingstate of the outlet. If a command is pending on the outlet, the outletStatusMSPCommandPending (1) value will be returned. If there is not a command pending on the ou… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.7.1.1.6 | ||||
sPDUOutletStatusMSPOutletCtrlModemandatory The Control Mode of the outlet.This OID is provided for informational purposes only. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.6.7.1.1.7 |
.1.3.6.1.4.1.318.1.1.7.1.1.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3IdentSysDescriptionTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3IdentSysDescriptionTable'
Allows for accessing description records of the powerplant. The number of entries is contained in the dm3IdentSysDescriptionTableSize OID.
The powerplant description record to reference.
Indexes
| Column | Syntax | OID |
|---|---|---|
dm3IdentSysDescriptionIndexmandatory The index to the DC powerplant description record. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.1.1.2.1.1 |
dm3IdentSysDescriptionTextmandatory A 16 character text field describing the DC power plant device.This field can be configured from the dm3ConfigSysDescriptionText OID. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.1.1.2.1.2 |
.1.3.6.1.4.1.318.1.1.7.2.1.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigSysDescriptionTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigSysDescriptionTable'
Allows for accessing description records of the powerplant. The number of entries is contained in the dm3ConfigSysDescriptionTableSize OID.
The powerplant description record to reference.
Indexes
| Column | Syntax | OID |
|---|---|---|
dm3ConfigSysDescriptionIndexmandatory The index to the DC powerplant description record. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.1.2.1.1 |
dm3ConfigSysDescriptionTextmandatory 16 character text field describing the DC power plant device. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.1.2.1.2 |
.1.3.6.1.4.1.318.1.1.7.2.2.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigLVDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigLVDTable'
Allows for accessing settings of the LVDs. The number of entries is contained in the dm3ConfigLVDTableSize OID.
The LVD to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
dm3ConfigLVDIndexmandatory The index to the DC powerplant LVD. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.2.2.1.1 | ||||||||||||||||||
dm3ConfigLVDNamemandatory The name of the LVD. The maximum value is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.2.2.1.2 | ||||||||||||||||||
dm3ConfigLVDEnablemandatory This OID is used to control and indicate if the LVD is on or off.Setting this OID to enabledYes (1) will enable (turn on) the LVD. Setting this OID to enabledNo (2) will disable (turn off) the LVD. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.2.2.1.3 | ||||||||||||||||||
dm3ConfigLVDTripThreshmandatory LVD Trip threshold. If voltage exceeds threshold, the LVD will trip.Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.2.2.1.4 | ||||||||||||||||||
dm3ConfigLVDResetThreshmandatory LVD Reset threshold. If voltage exceeds threshold, the LVD will reset.Values are represented in thousandths of Volts (mV). Attempts to set the value above or below the acceptable range of the powerplant… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.2.2.1.5 | ||||||||||||||||||
dm3ConfigLVDOpenAlarmmandatory For the LVD Open Alarm;Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to al… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.2.2.1.6 | ||||||||||||||||||
dm3ConfigLVDHWAlarmmandatory For the LVD Hardware Alarm;Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID t… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.2.2.1.7 |
.1.3.6.1.4.1.318.1.1.7.2.5.1.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigOutRlyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigOutRlyTable'
Allows for accessing settings of the Output Relays. The number of entries is contained in the dm3ConfigOutRlyTableSize OID.
The output relay to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
dm3ConfigOutRlyIndexmandatory The index to the DC powerplant output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.1 | ||||||||||||||||||
dm3ConfigOutRlyNamemandatory The name of the output relay. The maximum value is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.2 | ||||||||||||||||||
dm3ConfigOutRlyDelaymandatory Output Relay Delay. This OID represents the time delay from the initiation of anoutput relay action to when the output relay action does occur. If the alarm condition disappears before the end of the delay, no action… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.3 | ||||||||||||||||||
dm3ConfigOutRlyAlarmmandatory Output Relay Alarm. This setting indicates what action to perform in the event ofan output relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to a… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4 |
.1.3.6.1.4.1.318.1.1.7.2.5.2.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigInRlyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigInRlyTable'
Allows for accessing settings of the Input Relays. The number of entries is contained in the dm3ConfigInRlyTableSize OID.
The input relay to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
dm3ConfigInRlyIndexmandatory The index to the DC powerplant input relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.1 | ||||||||||||||||||
dm3ConfigInRlyNamemandatory The name of the input relay. The maximum value is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.2 | ||||||||||||||||||
dm3ConfigInRlyDelaymandatory Input Relay Delay. This OID represents the time delay from the initiation of aninput relay action to when the input relay action does occur. If the alarm condition disappears before the end of the delay, no action w… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.3 | ||||||||||||||||||
dm3ConfigInRlyAlarmmandatory Input Relay Alarm. This setting indicates what action to perform in the event ofan input relay alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to ala… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.4 |
.1.3.6.1.4.1.318.1.1.7.2.6.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigBreakersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigBreakersTable'
Allows for accessing settings of the circuit breakers. The number of entries is contained in the dm3ConfigBreakersTableSize OID.
The circuit breaker to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
dm3ConfigBreakersIndexmandatory The index to the DC powerplant circuit breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.1 | ||||||||||||||||||
dm3ConfigBreakersNamemandatory The name of the circuit breaker. The maximum value is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.2 | ||||||||||||||||||
dm3ConfigBreakersAlarmmandatory Circuit Breaker Alarm. This setting indicates what action to perform in the event ofa circuit breaker alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.7.2.6.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3ConfigFusesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3ConfigFusesTable'
Allows for accessing settings of the Fuses. The number of entries is contained in the dm3ConfigFusesTableSize OID.
The fuse to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
dm3ConfigFusesIndexmandatory The index to the DC powerplant fuse. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.1 | ||||||||||||||||||
dm3ConfigFusesNamemandatory The name of the fuse. The maximum value is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.2 | ||||||||||||||||||
dm3ConfigFusesAlarmmandatory Fuses Alarm. This setting indicates what action to perform in the event ofa Fuse alarm condition; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) c… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.7.3.2.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusAlarmsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusAlarmsTable'
Allows for accessing system alarms. The number of entries is contained in the dm3StatusAlarmsTableSize OID.
The alarm to display.
Indexes
| Column | Syntax | OID |
|---|---|---|
dm3StatusAlarmsIndexmandatory The index of the system alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.2.2.1.1 |
dm3StatusAlarmsTextmandatory The 16 character text describing the active alarm condition. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.2.2.1.2 |
.1.3.6.1.4.1.318.1.1.7.3.5.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusLVDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusLVDTable'
Allows for accessing settings of the LVDs. The number of entries is contained in the dm3StatusLVDTableSize OID.
The LVD to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusLVDIndexmandatory The index to the DC powerplant LVD. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.5.2.1.1 | ||||
dm3StatusLVDNamemandatory The name of the LVD. The maximum size is16 characters. The name is set by using the dm3ConfigLVDName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.5.2.1.2 | ||||
dm3StatusLVDStatemandatory Getting this OID will return statusClosed (1) if the LVD is closed.statusOpened (2) will be returned if the LVD is opened. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.5.2.1.3 | ||||
dm3StatusLVDHwFaultmandatory Getting this OID will return statusFault (1) if the LVD is faulted.statusNofault (2) will be returned if the LVD is not faulted. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.5.2.1.4 |
.1.3.6.1.4.1.318.1.1.7.3.6.1.2
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusRectTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusRectTable'
Allows for accessing settings of the rectifiers. The number of entries is contained in the dm3StatusRectTableSize OID.
The rectifier to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusRectIndexmandatory The index to the DC powerplant rectifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.1 | ||||
dm3StatusRectIDmandatory This OID shows the rectifier ID. This enumerates the number of the rectifier withina group of rectifiers. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.2 | ||||
dm3StatusRectDescmandatory This OID shows the 16-character rectifier description. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.3 | ||||
dm3StatusRectCurrentmandatory This OID shows the rectifier current in thousandths of Amps (mA). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.4 | ||||
dm3StatusRectCurrentLimitmandatory Getting this OID will return statusTrue (1) if the rectifier is in the Current Limit state.statusFalse (2) will be returned if the rectifier is not in the Current Limit state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.5 | ||||
dm3StatusRectStandbymandatory Getting this OID will return statusTrue (1) if the rectifier is in the Standby state.statusFalse (2) will be returned if the rectifier is not in the Standby state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.6 | ||||
dm3StatusRectFanFailmandatory Getting this OID will return statusTrue (1) if the rectifier Fan has failed.statusFalse (2) will be returned if the rectifier Fan has not failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.7 | ||||
dm3StatusRectFailmandatory Getting this OID will return statusTrue (1) if the rectifier has failed.statusFalse (2) will be returned if the rectifier has not failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.8 | ||||
dm3StatusRectDevTypemandatory This OID shows the rectifier device type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.9 | ||||
dm3StatusRectPhyAddrmandatory This OID shows the rectifier physical address (the address on the bus). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.10 | ||||
dm3StatusRectCfgmandatory Getting this OID will return statusTrue (1) if the rectifier is present afterpower-up or set-configuration. statusFalse (2) will be returned if the rectifier is not configured. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.11 | ||||
dm3StatusRectPcbRevmandatory This OID shows the rectifier device PCB serial number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.12 | ||||
dm3StatusRectFwVermandatory This OID shows the rectifier device firmware revision. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.13 | ||||
dm3StatusRectPresentmandatory Getting this OID will return statusTrue (1) if the rectifier is present.statusFalse (2) will be returned if the rectifier is not present. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.14 | ||||
dm3StatusRectDiagPassmandatory Getting this OID will return statusTrue (1) if the rectifier diagnostics have passed.statusFalse (2) will be returned if the rectifier diagnostics have not passed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.15 | ||||
dm3StatusRectStatemandatory This OID shows the rectifier device state as defined by the device status register. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.16 |
.1.3.6.1.4.1.318.1.1.7.3.6.2.2
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusConvTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusConvTable'
Allows for viewing status of the converters. The number of entries is contained in the dm3StatusConvTableSize OID.
The converter to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusConvIndexmandatory The index to the DC powerplant converter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.1 | ||||
dm3StatusConvIDmandatory This OID shows the converter ID. This enumerates the number of the converter withina group of converters. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.2 | ||||
dm3StatusConvDescmandatory This OID shows the 16 character converter description. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.3 | ||||
dm3StatusConvCurrentmandatory This OID shows the converter current in thousandths of Amps (mA). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.4 | ||||
dm3StatusConvCurrentLimitmandatory Getting this OID will return statusTrue (1) if the converter is in the Current Limit state.statusFalse (2) will be returned if the converter is not in the Current Limit state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.5 | ||||
dm3StatusConvStandbymandatory Getting this OID will return statusTrue (1) if the converter is in the Standby state.statusFalse (2) will be returned if the converter is not in the Standby state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.6 | ||||
dm3StatusConvFanFailmandatory Getting this OID will return statusTrue (1) if the converter Fan has failed.statusFalse (2) will be returned if the converter Fan has not failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.7 | ||||
dm3StatusConvFailmandatory Getting this OID will return statusTrue (1) if the converter has failed.statusFalse (2) will be returned if the converter has not failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.8 | ||||
dm3StatusConvDevTypemandatory This OID shows the converter device type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.9 | ||||
dm3StatusConvPhyAddrmandatory This OID shows the converter physical address (the address on the bus). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.10 | ||||
dm3StatusConvCfgmandatory Getting this OID will return statusTrue (1) if the converter is present afterpower-up or set-configuration. statusFalse (2) will be returned if the converter is not configured. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.11 | ||||
dm3StatusConvPcbRevmandatory This OID shows the converter device PCB serial number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.12 | ||||
dm3StatusConvFwVermandatory This OID shows the converter device firmware version. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.13 | ||||
dm3StatusConvPresentmandatory Getting this OID will return statusTrue (1) if the converter is present.statusFalse (2) will be returned if the converter is not present. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.14 | ||||
dm3StatusConvDiagPassmandatory Getting this OID will return statusTrue (1) if the converter diagnostics have passed.statusFalse (2) will be returned if the converter diagnostics have not passed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.15 | ||||
dm3StatusConvStatemandatory This OID shows the converter state as defined by the device status register. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.16 |
.1.3.6.1.4.1.318.1.1.7.3.7.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusOutRlyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusOutRlyTable'
Allows for viewing status of the output relays. The number of entries is contained in the dm3StatusOutRlyTableSize OID.
The output relay to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusOutRlyIndexmandatory The index to the DC powerplant output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.1 | ||||
dm3StatusOutRlyNamemandatory The name of the output relay. The maximum size is16 characters. The name is set by using the dm3ConfigOutRlyName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.2 | ||||
dm3StatusOutRlyStatusmandatory Getting this OID will return statusOn (1) if the output relay is enabled/on.statusOff (2) will be returned if the output relay is disabled/off. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.7.3.7.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusInRlyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusInRlyTable'
Allows for viewing status of the input relays. The number of entries is contained in the dm3StatusInRlyTableSize OID.
The input relays to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusInRlyIndexmandatory The index to the DC powerplant input relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.1 | ||||
dm3StatusInRlyNamemandatory The name of the input relay. The maximum size is16 characters. The name is set by using the dm3ConfigInRlyName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.2 | ||||
dm3StatusInRlyStatusmandatory Getting this OID will return statusOn (1) if the input relay is enabled/on.statusOff (2) will be returned if the input relay is disabled/off. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.7.3.8.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusBreakersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusBreakersTable'
Allows for viewing status of the circuit breakers. The number of entries is contained in the dm3StatusBreakersTableSize OID.
The circuit breaker to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusBreakersIndexmandatory The index to the DC powerplant circuit breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.1 | ||||
dm3StatusBreakersNamemandatory The name of the circuit breaker. The maximum size is16 characters. The name is set by using the dm3ConfigBreakersName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.2 | ||||
dm3StatusBreakersStatusmandatory Getting this OID will return statusClosed (1) if the circuit breaker is closed.statusOpen (2) will be returned if the circuit breaker is open. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.7.3.8.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dm3StatusFusesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dm3StatusFusesTable'
Allows for viewing status of the fuses. The number of entries is contained in the dm3StatusFusesTableSize OID.
The fuse to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dm3StatusFusesIndexmandatory The index to the DC powerplant fuse. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.1 | ||||
dm3StatusFusesNamemandatory The name of the fuse. The maximum size is16 characters. The name is set by using the dm3ConfigFuseName OID. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.2 | ||||
dm3StatusFusesStatusmandatory Getting this OID will return statusClosed (1) if the fuse is closed.statusOpen (2) will be returned if the fuse is open. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.8.2.1.3
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsCalibrationInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsCalibrationInputPhaseTable'
The number of phases per input line to this device. It is not applicable to AP44xxA units or newer.
An entry containing calibration information applicable to a
particular input phase. It is not applicable to AP44xxA units or newer.
particular input phase. It is not applicable to AP44xxA units or newer.
| Column | Syntax | OID |
|---|---|---|
atsCalibrationInputTableIndexmandatory The input identifier. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.1.3.1.1 |
atsCalibrationInputPhaseTableIndexmandatory The input phase identifier. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.1.3.1.2 |
atsLineVoltageCalibrationFactormandatory The Line Voltage Calibration factor. This value is set at the factory.It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.1.3.1.3 |
.1.3.6.1.4.1.318.1.1.8.2.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsCalibrationPowerSupplyVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsCalibrationPowerSupplyVoltageTable'
A list of Power Supply table entries. It is not applicable to AP44xxA units or newer.
An entry containing information applicable to a particular
Power Supply Voltage. It is not applicable to AP44xxA units or newer.
Power Supply Voltage. It is not applicable to AP44xxA units or newer.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The power supply voltage identifier. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.2.2.1.1 | ||||||||||
atsCalibrationPowerSupplyVoltagemandatory This value describes the power supply voltage of24V Source A, 24V Source B, +12V, -12V and 5V. It is not applicable to AP44xxA units or newer. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.2.2.2.1.2 | ||||||||||
| The Line Voltage Calibration factor. This value is set at the factory. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.8.2.2.3
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ats4gCalibrationPowerSupplyVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ats4gCalibrationPowerSupplyVoltageTable'
A list of Power Supply table entries. It is applicable only to AP44xx units.
An entry containing information applicable to a particular
Power Supply Voltage. It is applicable only to AP44xx ATS units.
Power Supply Voltage. It is applicable only to AP44xx ATS units.
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| The power supply voltage identifier. It is applicable only to AP44xx ATS units. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.2.3.1.1 | ||||||||||||
ats4gCalibrationPowerSupplyVoltagemandatory This value describes the power supply voltage of24V Source A, 24V Source B, VBoost Source A, VBoost Source B, 3.3V, 1.0V. It is applicable only to AP44xx units. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.2.2.3.1.2 | ||||||||||||
| The Line Voltage Calibration factor. This value is set at the factory. It is applicable only to AP44xx units. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.2.3.1.3 |
.1.3.6.1.4.1.318.1.1.8.2.3.3
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsCalibrationOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsCalibrationOutputTable'
A list of output table entries. It is not applicable to AP44xxA units or newer.
An entry containing information applicable to a particular output.
It is not applicable to AP44xxA units or newer.
It is not applicable to AP44xxA units or newer.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
atsCalibrationOutputTableIndexmandatory The output identifier. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.3.3.1.1 | ||||||||
atsCalibrationOutputPhasesTableIndexmandatory Description of each calibration factor for eachoutput phase utilized in this device and one for neutral. It is not applicable to AP44xxA units or newer. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.2.3.3.1.2 | ||||||||
atsOutputCurrentCalibrationFactormandatory The output current calibration factor. It is not applicable to AP44xxA units or newer. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.2.3.3.1.3 |
.1.3.6.1.4.1.318.1.1.8.4.14
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsConfigBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigBankTable'
Allows for configuration of each ATS bank.
This gives access to bank current threshold
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
atsConfigBankTableIndexmandatory An index to the bank table entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.14.1.1 | ||||||
atsConfigBankmandatory The bank number of an ATS | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.4.14.1.2 | ||||||
atsConfigBankLowLoadThresholdmandatory A threshold that indicates the current drawn is nearinga low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value o… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.14.1.3 | ||||||
atsConfigBankNearOverLoadThresholdmandatory A threshold that indicates the current drawn is nearingan overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum va… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.14.1.4 | ||||||
atsConfigBankOverLoadThresholdmandatory A threshold that indicates the current drawn has enteredan overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum v… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.14.1.5 |
.1.3.6.1.4.1.318.1.1.8.4.16
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsConfigPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsConfigPhaseTable'
Allows for configuration of each ATS phase.
This gives access to phase threshold
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
atsConfigPhaseTableIndexmandatory The index to the phase table entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.16.1.1 | ||||||
atsConfigPhasemandatory The phase number of an ATS | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.4.16.1.2 | ||||||
atsConfigPhaseLowLoadThresholdmandatory A threshold that indicates the current drawn is nearinga low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value o… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.16.1.3 | ||||||
atsConfigPhaseNearOverLoadThresholdmandatory A threshold that indicates the current drawn is nearingan overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum va… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.16.1.4 | ||||||
atsConfigPhaseOverLoadThresholdmandatory A threshold that indicates the current drawn has enteredan overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum v… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.4.16.1.5 |
.1.3.6.1.4.1.318.1.1.8.5.3.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsInputTable'
A list of input table entries. The number of entries is given by the value of atsNumInputs.
An entry containing information applicable to a
particular input.
particular input.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
atsInputTableIndexmandatory The input identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.2.1.1 | ||||||||||
atsNumInputPhasesmandatory The number of input phases utilized in thisdevice. The sum of all the atsNumInputPhases variable indicates the number of rows in the input phase table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.2.1.2 | ||||||||||
atsInputVoltageOrientationmandatory The input voltage orientation:1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.3.2.1.3 | ||||||||||
atsInputFrequencymandatory The input frequency in Hertz, or -1 if it's unsupportedby this Source. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.2.1.4 | ||||||||||
atsInputTypemandatory The input type. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.3.2.1.5 | ||||||||||
atsInputNamemandatory A name given to a particular input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.8.5.3.2.1.6 |
.1.3.6.1.4.1.318.1.1.8.5.3.3
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsInputPhaseTable'
A list of input table entries. The number of entries is given by the sum of the atsNumInputPhases.
An entry containing information applicable to a
particular input phase.
particular input phase.
| Column | Syntax | OID |
|---|---|---|
atsInputPhaseTableIndexmandatory The input identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.1 |
atsInputPhaseIndexmandatory The input phase identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.2 |
atsInputVoltagemandatory The input voltage in VAC, or -1 if it's unsupportedby this Source. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.3 |
atsInputMaxVoltagemandatory The maximum input voltage in VAC measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.4 |
atsInputMinVoltagemandatory The minimum input voltage in VAC measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.5 |
atsInputCurrentmandatory The input current in amperes, or -1 if it'sunsupported by this Source. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.6 |
atsInputMaxCurrentmandatory The maximum input current in amperes measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.7 |
atsInputMinCurrentmandatory The minimum input current in amperes measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.8 |
atsInputPowermandatory The input power in Watts, or -1 if it's unsupportedby this Source. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.9 |
atsInputMaxPowermandatory The maximum input power in Watts measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.10 |
atsInputMinPowermandatory The minimum input power in Watts measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.3.3.1.11 |
.1.3.6.1.4.1.318.1.1.8.5.4.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsOutputTable'
A list of output table entries. The number of entries is given by the value of atsOutputNumPhases.
An entry containing information applicable to a
particular output.
particular output.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
atsOutputTableIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.2.1.1 | ||||||||||
atsNumOutputPhasesmandatory The number of output phases utilized in thisdevice. The sum of all the atsNumOutputPhases variable indicates the number of rows in the output phase table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.2.1.2 | ||||||||||
atsOutputVoltageOrientationmandatory The output voltage orientation:1: unknown for this ATS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is between Phase 1 and Neutral; phase 2 voltage is between Phase 2… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.2.1.3 | ||||||||||
atsOutputFrequencymandatory The output frequency in Hertz, or -1 if it'sunsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.2.1.4 |
.1.3.6.1.4.1.318.1.1.8.5.4.3
·
1 row entry
·
19 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsOutputPhaseTable'
A list of output table entries. The number of entries is given by the sum of the atsNumOutputPhases.
An entry containing information applicable to a
particular output phase.
particular output phase.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
atsOutputPhaseTableIndexmandatory The output identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.1 | ||||||||
atsOutputPhaseIndexmandatory Description of each output phase utilized inthis device and one for neutral. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.3.1.2 | ||||||||
atsOutputVoltagemandatory The output voltage in VAC, or -1 if it's unsupportedby this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.3 | ||||||||
atsOutputCurrentmandatory The output current in 0.1 amperes drawnby the load on the ATS, or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.4 | ||||||||
atsOutputMaxCurrentmandatory The maximum output current in 0.1 amperes measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.5 | ||||||||
atsOutputMinCurrentmandatory The minimum output current in 0.1 amperes measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.6 | ||||||||
atsOutputLoadmandatory The output load in VA, or -1 if it's unsupportedby this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.7 | ||||||||
atsOutputMaxLoadmandatory The maximum output load in VA measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.8 | ||||||||
atsOutputMinLoadmandatory The minimum output load in VA measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.9 | ||||||||
atsOutputPercentLoadmandatory The percentage of the ATS load capacity in VA atredundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.10 | ||||||||
atsOutputMaxPercentLoadmandatory The maximum percentage of the ATS load capacity inVA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.11 | ||||||||
atsOutputMinPercentLoadmandatory The minimum percentage of the ATS load capacity inVA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.12 | ||||||||
atsOutputPowermandatory The output apparent power in VA, or-1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.13 | ||||||||
atsOutputMaxPowermandatory The maximum output power in VAs measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.14 | ||||||||
atsOutputMinPowermandatory The minimum output power in VA measuredsince the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.15 | ||||||||
atsOutputPercentPowermandatory The percentage of the ATSpower capacity in VA atredundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.16 | ||||||||
atsOutputMaxPercentPowermandatory The maximum percentage of the ATSpower capacityin VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.17 | ||||||||
atsOutputMinPercentPowermandatory The minimum percentage of the ATSpower capacityin VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.3.1.18 | ||||||||
atsOutputPhaseStatemandatory Getting this OID will return the phase load state.normal(1) indicates that the bank is operating properly within the atsConfigPhaseLowLoadThreshold and atsConfigPhaseNearOverLoadThreshold OID values. … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.3.1.19 |
.1.3.6.1.4.1.318.1.1.8.5.4.5
·
1 row entry
·
20 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk atsOutputBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::atsOutputBankTable'
Allows for getting table entries.
This gives access to bank table entries
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
atsOutputBankTableIndexmandatory The index to the bank table entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.1 | ||||||||
atsOutputPhasemandatory The phase number of an ATS | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.5.1.2 | ||||||||
atsOutputBankmandatory The bank number of an ATS | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.5.1.3 | ||||||||
atsOutputBankCurrentmandatory Getting this OID will return the bank current measuredin tenths of Amps. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.4 | ||||||||
atsOutputBankStatemandatory Getting this OID will return the bank load state.normal(1) indicates that the bank is operating properly within the atsConfigBankLowLoadThreshold and atsConfigBankNearOverLoadThreshold OID values. … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.8.5.4.5.1.5 | ||||||||
atsOutputBankOutputVoltagemandatory The output voltage in VAC, or -1 if it's unsupportedby this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.6 | ||||||||
atsOutputBankMaxCurrentmandatory The maximum output current, on the bank represented byOID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.7 | ||||||||
atsOutputBankMinCurrentmandatory The minimum output current, on the bank represented byOID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.8 | ||||||||
atsOutputBankLoadmandatory The output load, on the bank represented byOID atsOutputBank, in VA, or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.9 | ||||||||
atsOutputBankMaxLoadmandatory The maximum output load, on the bank represented byOID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.10 | ||||||||
atsOutputBankMinLoadmandatory The minimum output load, on the bank represented byOID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.11 | ||||||||
atsOutputBankPercentLoadmandatory The percentage of the ATS load capacity in VA atredundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank. Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.12 | ||||||||
atsOutputBankMaxPercentLoadmandatory The maximum percentage of the ATS load capacity inVA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusR… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.13 | ||||||||
atsOutputBankMinPercentLoadmandatory The minimum percentage of the ATS load capacity inVA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusR… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.14 | ||||||||
atsOutputBankPowermandatory The output apparent power in VA on the bank represented byOID atsOutputBank or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.15 | ||||||||
atsOutputBankMaxPowermandatory The maximum output power in VA measured on the bankrepresented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.16 | ||||||||
atsOutputBankMinPowermandatory The minimum output power in VA measured on the bankrepresented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.17 | ||||||||
atsOutputBankPercentPowermandatory The percentage of the ATSpower capacity in Watts atredundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, or -1 if it's unsupported by this ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.18 | ||||||||
atsOutputBankMaxPercentPowermandatory The maximum percentage of the ATSpower capacityin VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, since the last time this variable was read or reset (atsStatusR… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.19 | ||||||||
atsOutputBankMinPercentPowermandatory The minimum percentage of the ATSpower capacityin VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusRe… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.8.5.4.5.1.20 |
.1.3.6.1.4.1.318.1.1.9.3.3.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dcmim2ConfigLVDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dcmim2ConfigLVDTable'
Allows for accessing settings of the LVDs. The number of entries is contained in the dcmim2ConfigLVDTableSize OID.
The LVD to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dcmim2ConfigLVDIndexmandatory The index to the DC powerplant LVD. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.1 | ||||
dcmim2ConfigLVDTripmandatory LVD Trip threshold. System bus voltage at which LVD will trip (open)during a battery backup operation. Values are represented in thousandths of Volts (mV). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.2 | ||||
dcmim2ConfigLVDResetmandatory LVD Reset threshold. System bus voltage at which LVD will reset (close)after AC power has been restored. Values are represented in thousandths of Volts (mV). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.3.3.2.1.3 | ||||
dcmim2ConfigLVDStatemandatory Getting this OID will return statusClosed (1) if the LVD is closed.statusOpened (2) will be returned if the LVD is opened. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.9.3.3.2.1.4 |
.1.3.6.1.4.1.318.1.1.9.4.2.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dcmim2StatusRectTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dcmim2StatusRectTable'
Allows for accessing settings of the rectifiers. The number of entries is contained in the dcmim2StatusRectTableSize OID.
The rectifier to gather status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dcmim2StatusRectIndexmandatory The index to the DC powerplant rectifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.2.2.1.1 | ||||
dcmim2StatusRectDevTypemandatory This OID shows the rectifier device type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.2.2.1.2 | ||||
dcmim2StatusRectIDmandatory This OID shows the rectifier ID. This enumerates the number of the rectifier withina group of rectifiers. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.2.2.1.3 | ||||
dcmim2StatusRectPhyAddrmandatory This OID shows the rectifier physical address (the address on the bus). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.2.2.1.4 | ||||
dcmim2StatusRectFailmandatory Getting this OID will return statusTrue (1) if the rectifier has failed.statusFalse (2) will be returned if the rectifier has not failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.9.4.2.2.1.5 | ||||
dcmim2StatusRectCurrentmandatory This OID shows the individual rectifier current in thousandths of Amps (mA). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.9.4.4.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dcmim2StatusLVDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dcmim2StatusLVDTable'
Allows for accessing the LVDs. The number of entries is contained in the dcmim2StatusLVDTableSize OID.
The LVD to access.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
dcmim2StatusLVDIndexmandatory The index to the DC powerplant LVD. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.4.2.1.1 | ||||
dcmim2StatusLVDStatemandatory Getting this OID will return statusClosed (1) if the LVD is closed.statusOpened (2) will be returned if the LVD is opened. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.9.4.4.2.1.2 |
.1.3.6.1.4.1.318.1.1.9.4.5.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk dcmim2StatusAlarmsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::dcmim2StatusAlarmsTable'
Allows for accessing system alarms. The number of entries is contained in the dcmim2StatusAlarmsTableSize OID.
The alarm to display.
Indexes
| Column | Syntax | OID |
|---|---|---|
dcmim2StatusAlarmsIndexmandatory The index of the system alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.9.4.5.2.1.1 |
dcmim2StatusAlarmsTextmandatory The 16 character text describing the active alarm condition. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.9.4.5.2.1.2 |
.1.3.6.1.4.1.318.1.1.10.1.2.2
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emConfigProbesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emConfigProbesTable'
A list of probes supported by the Environmental Monitor and their configurations.
The Environmental Monitor probe configurations.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emConfigProbeNumbermandatory The index into an Environmental Monitor probe entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.1 | ||||
emConfigProbeNamemandatory A descriptive name of the probe set by the user,possibly denoting its location or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.2 | ||||
emConfigProbeHighTempThresholdmandatory The high temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.3 | ||||
emConfigProbeLowTempThresholdmandatory The low temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.4 | ||||
emConfigProbeTempUnitsmandatory The temperature scale used to display the temperaturethresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.5 | ||||
emConfigProbeHighHumidThresholdmandatory The high humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.6 | ||||
emConfigProbeLowHumidThresholdmandatory The low humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.7 | ||||
emConfigProbeHighTempEnablemandatory The high temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.8 | ||||
emConfigProbeLowTempEnablemandatory The low temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.9 | ||||
emConfigProbeHighHumidEnablemandatory The high humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.10 | ||||
emConfigProbeLowHumidEnablemandatory The low humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.11 | ||||
emConfigProbeMaxTempThresholdmandatory The maximum temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.12 | ||||
emConfigProbeMinTempThresholdmandatory The minimum temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.13 | ||||
emConfigProbeMaxHumidThresholdmandatory The maximun humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.14 | ||||
emConfigProbeMinHumidThresholdmandatory The minimum humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.15 | ||||
emConfigProbeMaxTempEnablemandatory The maximum temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been viola… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.16 | ||||
emConfigProbeMinTempEnablemandatory The minimum temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been viola… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.17 | ||||
emConfigProbeMaxHumidEnablemandatory The maximum humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.18 | ||||
emConfigProbeMinHumidEnablemandatory The minimum humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.2.1.19 | ||||
emConfigProbeTempHysteresismandatory The number of degrees beyond the temperature thresholdsat which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in the scale selected i… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.20 | ||||
emConfigProbeHumidHysteresismandatory The number of percent RH points beyond the humiditythresholds at which an active humidity alarm will be cleared. This configuration setting applies to all humidity thresholds. Units are displayed in the scale selected … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.21 | ||||
emConfigProbeLocationmandatory A string describing the location of the probe. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.1.2.2.1.22 |
.1.3.6.1.4.1.318.1.1.10.1.2.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emConfigContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emConfigContactsTable'
A list of contacts supported by the Environmental Monitor and their configurations.
The Environmental Monitor contact configurations.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emConfigContactNumbermandatory The index of an Environmental Monitor contact. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.2.4.1.1 | ||||||
emConfigContactNamemandatory A descriptive name for an Environmental Monitorcontact set by the user, possibly denoting its location or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.1.2.4.1.2 | ||||||
emConfigContactEnablemandatory An Environmental Monitor contact alarm enable/disable.No alarm will be generated if the contact is disabled(1). An alarm will be generated if the contact is enabled(2) and the contact has been faulted. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.4.1.3 | ||||||
emConfigContactSeveritymandatory The severity of the alarm that will be triggered whenthe input contact is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.4.1.4 | ||||||
emConfigContactNormalStatemandatory The contact state that will be considered normal, i.e.will not trigger an alarm. The states are open(1) or closed(2). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.2.4.1.5 | ||||||
emConfigContactLocationmandatory A descriptive label for the contact denoting itslocation or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.1.2.4.1.6 |
.1.3.6.1.4.1.318.1.1.10.1.3.3
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emStatusProbesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emStatusProbesTable'
A list of probes supported by the Environmental Monitor and their status.
The status of the probe.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emStatusProbeNumbermandatory The index of the probe. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.3.3.1.1 | ||||||
emStatusProbeNamemandatory A descriptive name for the probe set by the user,possibly denoting its location or purpose. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.1.3.3.1.2 | ||||||
emStatusProbeStatusmandatory The connected status of the probe, eitherdisconnected(1) or connected(2). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.3 | ||||||
emStatusProbeCurrentTempmandatory The current temperature reading from the probe displayedin the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.3.3.1.4 | ||||||
emStatusProbeTempUnitsmandatory The temperature scale used to display the temperaturethresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.5 | ||||||
emStatusProbeCurrentHumidmandatory The current humidity reading from the probe inpercent relative humidity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.3.3.1.6 | ||||||
emStatusProbeHighTempViolationmandatory The high temperature violation status of the probetemperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.7 | ||||||
emStatusProbeLowTempViolationmandatory The high temperature violation status of the probetemperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to th… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.8 | ||||||
emStatusProbeHighHumidViolationmandatory The high humidity violation status of the probe humidityreading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is greater than or equal to the hi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.9 | ||||||
emStatusProbeLowHumidViolationmandatory The low humidity violation status of the probe humidityreading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is less than or equal to the low hum… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.10 | ||||||
emStatusProbeMaxTempViolationmandatory The max temperature violation status of the probetemperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is greater than or equal to … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.11 | ||||||
emStatusProbeMinTempViolationmandatory The minimum temperature violation status of the probetemperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in the 'emStatusProbeCurrentTemp' OID is less than or equal to… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.12 | ||||||
emStatusProbeMaxHumidViolationmandatory The maximum humidity violation status of the probe humidityreading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is greater than or equal to the … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.13 | ||||||
emStatusProbeMinHumidViolationmandatory The minimum humidity violation status of the probe humidityreading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'emStatusProbeCurrentHumid' OID is less than or equal to the min… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.3.1.14 |
.1.3.6.1.4.1.318.1.1.10.1.3.5
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emStatusContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emStatusContactsTable'
A list of contacts supported by the Environmental Monitor and their status.
The status of the contact.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emStatusContactNumbermandatory The index of the Environmental Monitor contact. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.1.3.5.1.1 | ||||||
emStatusContactNamemandatory A descriptive name for the Environmental Monitor contactset by the user, possibly denoting its location or purpose. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.1.3.5.1.2 | ||||||
emStatusContactStatusmandatory The status of the Environmental Monitor contact. The statuswill show noFault(1) if the contact is in the normal state and the 'emConfigContactEnable' OID is enabled. The status will show a fault(2) if the contact is fa… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.1.3.5.1.3 |
.1.3.6.1.4.1.318.1.1.10.2.2.2
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemConfigProbesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemConfigProbesTable'
A list of probes supported by the Environmental Monitor and their configurations.
The Environmental Monitor probe configurations.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
iemConfigProbeNumbermandatory The index to a Environmental Monitor probe entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.1 | ||||
iemConfigProbeNamemandatory A descriptive name for the probe set by the user,possibly denoting its location or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.2 | ||||
iemConfigProbeHighTempThresholdmandatory The high temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.3 | ||||
iemConfigProbeLowTempThresholdmandatory The low temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.4 | ||||
iemConfigProbeTempUnitsmandatory The temperature scale used to display the temperaturethresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.5 | ||||
iemConfigProbeHighHumidThresholdmandatory The high humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.6 | ||||
iemConfigProbeLowHumidThresholdmandatory The low humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.7 | ||||
iemConfigProbeHighTempEnablemandatory The high temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.8 | ||||
iemConfigProbeLowTempEnablemandatory The low temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.9 | ||||
iemConfigProbeHighHumidEnablemandatory The high humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.10 | ||||
iemConfigProbeLowHumidEnablemandatory The low humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.11 | ||||
iemConfigProbeMaxTempThresholdmandatory The maximun temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.12 | ||||
iemConfigProbeMinTempThresholdmandatory The minimun temperature alarm threshold for the probe.Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.13 | ||||
iemConfigProbeMaxHumidThresholdmandatory The maximum humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.14 | ||||
iemConfigProbeMinHumidThresholdmandatory The minimum humidity alarm threshold for the probe inpercent relative humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.15 | ||||
iemConfigProbeMaxTempEnablemandatory The maximum temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been viola… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.16 | ||||
iemConfigProbeMinTempEnablemandatory The low temperature alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.17 | ||||
iemConfigProbeMaxHumidEnablemandatory The maximum humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.18 | ||||
iemConfigProbeMinHumidEnablemandatory The minimum humidity alarm enable/disable for theprobe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value is set to enabled(2) and the threshold has been violated. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.2.1.19 | ||||
iemConfigProbeTempHysteresismandatory The number of degrees beyond the temperature thresholdsat which an active temperature alarm will be cleared. This configuration setting applies to all temperature thresholds. Units are displayed in the scale selected i… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.20 | ||||
iemConfigProbeHumidHysteresismandatory The number of percent RH points beyond the humiditythresholds at which an active humidity alarm will be cleared. This configuration setting applies to all humidity thresholds. Units are displayed in the scale selected … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.21 | ||||
iemConfigProbeLocationmandatory A string describing the location of the probe. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.2.2.2.1.22 |
.1.3.6.1.4.1.318.1.1.10.2.2.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemConfigContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemConfigContactsTable'
A list of contacts supported by the Environmental Monitor and their configurations.
The Environmental Monitor contact configurations.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
iemConfigContactNumbermandatory The index of an Environmental Monitor contact. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.4.1.1 | ||||||
iemConfigContactNamemandatory A descriptive name for the Environmental Monitor contactset by the user, possibly denoting its location or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.2.2.4.1.2 | ||||||
iemConfigContactEnablemandatory An Environmental Monitor contact alarm enable/disable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.4.1.3 | ||||||
iemConfigContactSeveritymandatory The severtity of the alarm that will be triggered whenthe input contact is activated. The alarms can be critical(1), warning(2) or informational(3). NOTE: informational(3) is deprecated (and no longer valid) for this O… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.4.1.4 | ||||||
iemConfigContactNormalStatemandatory The contact state that will be considered normal, i.e.will not trigger an alarm. The states are open(1) or closed(2). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.4.1.5 | ||||||
iemConfigContactLocationmandatory A descriptive label for the contact denoting itslocation or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.2.2.4.1.6 |
.1.3.6.1.4.1.318.1.1.10.2.2.6
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemConfigRelaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemConfigRelaysTable'
A list of output relays supported by the Environmental Monitor and their configurations.
The Environmental Monitor output relay configurations.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
iemConfigRelayNumbermandatory The index of an Environmental Monitor output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.6.1.1 | ||||
iemConfigRelayNamemandatory A descriptive name of an Environmental Monitor output relay,set by the user, describing its location or purpose. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.2.2.6.1.2 | ||||
iemConfigRelayNormalStatemandatory The normal state (non-fault state) of an EnvironmentalMonitor output relay, either open(1) or closed(2). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.2.6.1.3 | ||||
iemConfigRelayFaultConditionmandatory The fault condition used to activate the output relay. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.2.6.1.4 |
.1.3.6.1.4.1.318.1.1.10.2.3.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemStatusProbesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemStatusProbesTable'
A list of probes supported by the Environmental Monitor and their status.
The status of the probe.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
iemStatusProbeNumbermandatory The index of the probe. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.3.2.1.1 | ||||||
iemStatusProbeNamemandatory A descriptive name for the probe set by the user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.3.2.1.2 | ||||||
iemStatusProbeStatusmandatory The connected status of the probe, eitherdisconnected(1) or connected(2). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 | ||||||
iemStatusProbeCurrentTempmandatory The current temperature reading from the probe displayedin the units shown in the 'iemStatusProbeTempUnits' OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.3.2.1.4 | ||||||
iemStatusProbeTempUnitsmandatory The temperature scale used to display the temperaturethresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration in the agent. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.5 | ||||||
iemStatusProbeCurrentHumidmandatory The current humidity reading from the probe in percentrelative humidity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.3.2.1.6 | ||||||
iemStatusProbeHighTempViolationmandatory The high temperature violation status of the probetemperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is greater than or equal … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.7 | ||||||
iemStatusProbeLowTempViolationmandatory The high temperature violation status of the probetemperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is less than or equal to t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.8 | ||||||
iemStatusProbeHighHumidViolationmandatory The high humidity violation status of the probe humidityreading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is greater than or equal to the h… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.9 | ||||||
iemStatusProbeLowHumidViolationmandatory The low humidity violation status of the probe humidityreading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is less than or equal to the low hu… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.10 | ||||||
iemStatusProbeMaxTempViolationmandatory The max temperature violation status of the probetemperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is greater than or equal to… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.11 | ||||||
iemStatusProbeMinTempViolationmandatory The minimum temperature violation status of the probetemperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in the 'iemStatusProbeCurrentTemp' OID is less than or equal t… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.12 | ||||||
iemStatusProbeMaxHumidViolationmandatory The maximum humidity violation status of the probe humidityreading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is greater than or equal to the… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.13 | ||||||
iemStatusProbeMinHumidViolationmandatory The minimum humidity violation status of the probe humidityreading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'iemStatusProbeCurrentHumid' OID is less than or equal to the mi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.2.1.14 | ||||||
iemStatusProbeLocationmandatory A descriptive location for the probe set by the user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.3.2.1.15 |
.1.3.6.1.4.1.318.1.1.10.2.3.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemStatusContactsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemStatusContactsTable'
A list of contacts supported by the Environmental Monitor and their status.
The status of the contact.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
iemStatusContactNumbermandatory The index of the Environmental Monitor contact. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.3.4.1.1 | ||||||
iemStatusContactNamemandatory A descriptive name for the Environmental Monitor contactset by the user, denoting its location or purpose. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.3.4.1.2 | ||||||
iemStatusContactStatusmandatory The status of the Environmental Monitor contact. The statuswill show noFault(1) if the contact is in the normal state and the 'iemConfigContactEnable' OID is enabled. The status will show a fault(2) if the contact is f… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.4.1.3 |
.1.3.6.1.4.1.318.1.1.10.2.3.7
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk iemStatusRelaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::iemStatusRelaysTable'
A list of output relays supported by the Environmental Monitor and their status.
The status of the relay.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
iemStatusRelayNumbermandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.2.3.7.1.1 | ||||
iemStatusRelayNamemandatory A descriptive name for the output relay set by theuser, denoting its location or purpose. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.2.3.7.1.2 | ||||
iemStatusRelayStatusmandatory The status of the output relay, either faultState(1) ornormalState(2). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.2.3.7.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.2.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutputRelayControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutputRelayControlTable'
Allows for control of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
The output relays to control.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The index to the output relay entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.2.1.1.1 | ||||
emsOutputRelayControlOutputRelayNamemandatory The name of the output relay.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.2.1.1.2 | ||||
| Getting this variable will return the output relay state. If the output relay is closed, the immediateCloseEMS (1) value will be returned. If the output relay is open, the immediateOpenEMS (2) value will be returned. … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.2.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.3.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutletControlTable'
Allows for control of individual outlet switches. The number of entries is contained in the emsStatusOutletCount OID.
The outlets to control.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsOutletControlOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.3.1.1.1 | ||||
emsOutletControlOutletNamemandatory The name of the outlet.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.3.1.1.2 | ||||
emsOutletControlOutletCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOnEMS (1) value will be returned. If the outlet is off, the immediateOffEMS (2) value will be returned. Setting this v… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.3.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.4.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsSensorControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsSensorControlTable'
Allows for control/reset of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
The sensors to control/reset.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsSensorControlSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.4.1.1.1 | ||||
emsSensorControlSensorSystemNamemandatory The system name of the sensor. This describes the hardware systemintent of this sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.4.1.1.2 | ||||
emsSensorControlSensorUserNamemandatory The name of the sensor as given by the system user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.4.1.1.3 | ||||
emsSensorControlSensorCommandmandatory Getting this variable will return noCommandEMS(1).Setting this variable to resetCommandEMS(2) will issue a reset command to the sensor. Some sensors cannot be manually reset and will not be affected by … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.4.1.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.5.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsAlarmDeviceControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsAlarmDeviceControlTable'
Allows for control of individual alarm devices. Note: Some alarm devices are not controllable. The number of entries is contained in the emsStatusAlarmDeviceCount OID.
The alarm devices to control.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsAlarmDeviceControlDeviceIndexmandatory The index to the alarm device entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.5.1.1.1 | ||||||
emsAlarmDeviceControlDeviceNamemandatory The name of the alarm device.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.5.1.1.2 | ||||||
emsAlarmDeviceControlDeviceCommandmandatory Getting this variable will return the device state. Ifthe device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the alarmDeviceOffEMS (2) value will be returned. If the device is… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.5.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.7.1
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsProbeConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsProbeConfigTable'
Allows for configuration of individual probes. The number of entries is contained in the emsStatusProbeCount OID.
The probes to configure.
Indexes
| Column | Syntax | OID |
|---|---|---|
emsProbeConfigProbeIndexmandatory The index to the probe entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.1 |
emsProbeConfigProbeNamemandatory The name of the probe. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.2 |
emsProbeConfigProbeHighTempThreshmandatory Probe high temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.3 |
emsProbeConfigProbeLowTempThreshmandatory Probe low temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.4 |
| Probe high humidity threshold. Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.5 |
emsProbeConfigProbeLowHumidityThreshmandatory Probe low humidity threshold.Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.6 |
emsProbeConfigProbeMaxTempThreshmandatory Probe maximum temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.7 |
emsProbeConfigProbeMinTempThreshmandatory Probe minimum temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.8 |
emsProbeConfigProbeDeltaTempmandatory Probe delta temperature.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.9 |
emsProbeConfigProbeMaxHumidityThreshmandatory Probe maximum humidity threshold.Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.10 |
emsProbeConfigProbeMinHumidityThreshmandatory Probe minimum humidity threshold.Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.11 |
emsProbeConfigProbeDeltaHumiditymandatory Probe delta humidity.Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.12 |
emsProbeConfigProbeSTIncTempVariancemandatory Probe short-term increasing temperature variance used for rate of change alarms.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Ce… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.13 |
emsProbeConfigProbeSTIncTempTimemandatory Probe short-term increasing temperature time used for rate of change alarms.Values are represented in whole number minutes. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.14 |
emsProbeConfigProbeSTDecTempVariancemandatory Probe short-term decreasing temperature variance used for rate of change alarms.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Ce… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.15 |
emsProbeConfigProbeSTDecTempTimemandatory Probe short-term decreasing temperature time used for rate of change alarms.Values are represented in whole number minutes. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.16 |
emsProbeConfigProbeLTIncTempVariancemandatory Probe long-term increasing temperature variance used for rate of change alarms.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Cel… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.17 |
emsProbeConfigProbeLTIncTempTimemandatory Probe long-term increasing temperature time used for rate of change alarms.Values are represented in whole number hours. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.18 |
emsProbeConfigProbeLTDecTempVariancemandatory Probe long-term decreasing temperature variance used for rate of change alarms.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Cel… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.19 |
emsProbeConfigProbeLTDecTempTimemandatory Probe long-term decreasing temperature time used for rate of change alarms.Values are represented in whole number hours. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.20 |
emsProbeConfigProbeMaxVoltThreshmandatory Probe maximum voltage threshold in tenths of Volts. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.21 |
emsProbeConfigProbeMinVoltThreshmandatory Probe minimum voltage threshold in tenths of Volts. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.7.1.1.22 |
.1.3.6.1.4.1.318.1.1.10.3.8.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsInputContactConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsInputContactConfigTable'
Allows for configuration of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID.
The input contacts to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The index to the input contact entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.8.1.1.1 | ||||
| The name of the input contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.8.1.1.2 | ||||
| Getting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.8.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.9.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutputRelayConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutputRelayConfigTable'
Allows for configuration of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
The output relays to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsOutputRelayConfigOutputRelayIndexmandatory The index to the output relay entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.9.1.1.1 | ||||
emsOutputRelayConfigOutputRelayNamemandatory The name of the output relay. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.9.1.1.2 | ||||
| Getting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.9.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.10.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutletConfigTable'
Allows for configuration of individual outlets. The number of entries is contained in the emsStatusOutletCount OID.
The outlets to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsOutletConfigOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.10.1.1.1 | ||||
emsOutletConfigOutletNamemandatory The name of the outlet. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.10.1.1.2 | ||||
emsOutletConfigOutletNormalStatemandatory Getting this variable will return the normal state of the outlet. Ifthe normal state is on, the normallyOnEMS (1) value will be returned. If the normal state is off, the normallyOffEMS (2) value will be returned. … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.10.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.11.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsSensorConfigTable'
Allows for configuration of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
The sensors to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.11.1.1.1 | ||||
emsSensorConfigSensorSystemNamemandatory The system name of the sensor. This describes the hardware systemintent of this sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.11.1.1.2 | ||||
emsSensorConfigSensorUserNamemandatory The name of the sensor as given by the system user. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.11.1.1.3 | ||||
emsSensorConfigSensorNormalStatemandatory Getting this variable will return the normal state of the sensor. Ifthe normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be ret… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.11.1.1.4 | ||||
emsSensorConfigSensorAlarmDelaymandatory The delay (in seconds) after a sensor detects an alarm condition before thecondition is reported. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.11.1.1.5 |
.1.3.6.1.4.1.318.1.1.10.3.13.1
·
1 row entry
·
18 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsProbeStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsProbeStatusTable'
Allows for access of individual probes. The number of entries is contained in the emsStatusProbeCount OID.
The probes to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsProbeStatusProbeIndexmandatory The index to the probe entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.1 | ||||||
emsProbeStatusProbeNamemandatory The name of the probe. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.2 | ||||||
emsProbeStatusProbeTemperaturemandatory Probe temperature reading.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.3 | ||||||
emsProbeStatusProbeHighTempThreshmandatory Probe high temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.4 | ||||||
emsProbeStatusProbeLowTempThreshmandatory Probe low temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.5 | ||||||
emsProbeStatusProbeHumiditymandatory Probe humidity reading.Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.6 | ||||||
| Probe high humidity threshold. Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.7 | ||||||
emsProbeStatusProbeLowHumidityThreshmandatory Probe low humidity threshold.Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.8 | ||||||
emsProbeStatusProbeSerialNumbermandatory A label indicating the type (Local[L] or Remote[R]) and Numberof the probe. For example, the first local probe would be L1 and the third remote probe would be R3. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.9 | ||||||
emsProbeStatusProbeCommStatusmandatory The state of communications to the probe.commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates communication is normal and active with this device. commsLo… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.13.1.1.10 | ||||||
emsProbeStatusProbeAlarmStatusmandatory The alarm status of the probe. This integer should be interpretedas a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the condition is… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.11 | ||||||
emsProbeStatusProbeMaxTempThreshmandatory Probe maximum temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.12 | ||||||
emsProbeStatusProbeMinTempThreshmandatory Probe minimum temperature threshold.Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.13 | ||||||
emsProbeStatusProbeMaxHumidityThreshmandatory Probe maximum humidity threshold.Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.14 | ||||||
emsProbeStatusProbeMinHumidityThreshmandatory Probe minimum humidity threshold.Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.15 | ||||||
emsProbeStatusProbeVoltagemandatory Probe voltage reading.Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.16 | ||||||
emsProbeStatusProbeMaxVoltThreshmandatory Probe maximum voltage threshold in Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.17 | ||||||
emsProbeStatusProbeMinVoltThreshmandatory Probe minimum voltage threshold in Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.13.1.1.18 |
.1.3.6.1.4.1.318.1.1.10.3.14.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsInputContactStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsInputContactStatusTable'
Allows for access of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID.
The input contacts to access.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The index to the input contact entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.14.1.1.1 | ||||
| The name of the input contact. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.14.1.1.2 | ||||
| Getting this variable will return the state of the input contact. If the input contact is closed, the contactClosedEMS (1) value will be returned. If the input contact state is open, the contactOpenEMS (2) value will be… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.14.1.1.3 | ||||
| Getting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is open, the normallyOpenEMS (2) value will b… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.14.1.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.15.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutputRelayStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutputRelayStatusTable'
Allows for access of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
The output relays to access.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsOutputRelayStatusOutputRelayIndexmandatory The index to the output relay entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.15.1.1.1 | ||||
emsOutputRelayStatusOutputRelayNamemandatory The name of the output relay. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.15.1.1.2 | ||||
emsOutputRelayStatusOutputRelayStatemandatory Getting this variable will return the state of the output relay. Ifthe output relay is closed, the relayClosedEMS (1) value will be returned. If the output relay is open, the relayOpenEMS (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.15.1.1.3 | ||||
| Getting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is open, the normallyOpenEMS (2) value will be… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.15.1.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.16.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsOutletStatusTable'
Allows for access of individual outlets. The number of entries is contained in the emsStatusOutletCount OID.
The outlets to access.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
emsOutletStatusOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.16.1.1.1 | ||||
emsOutletStatusOutletNamemandatory The name of the outlet. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.16.1.1.2 | ||||
emsOutletStatusOutletStatemandatory Getting this variable will return the state of the outlet. Ifthe outlet is on, the outletOnEMS (1) value will be returned. If the outlet is off, the outletOffEMS (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.16.1.1.3 | ||||
emsOutletStatusOutletNormalStatemandatory Getting this variable will return the normal state of the outlet. Ifthe normal state is on, the normallyOnEMS (1) value will be returned. If the normal state is off, the normallyOffEMS (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.16.1.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.17.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsAlarmDeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsAlarmDeviceStatusTable'
Allows for access of individual alarm devices. The number of entries is contained in the emsStatusAlarmDeviceCount OID.
The alarm devices to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsAlarmDeviceStatusDeviceIndexmandatory The index to the alarm device entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.17.1.1.1 | ||||||
emsAlarmDeviceStatusDeviceNamemandatory The name of the alarm device.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.17.1.1.2 | ||||||
emsAlarmDeviceStatusDeviceStatemandatory Getting this variable will return the device state. Ifthe device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the alarmDeviceOffEMS (2) value will be returned. If the device i… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.17.1.1.3 |
.1.3.6.1.4.1.318.1.1.10.3.18.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsSensorStatusTable'
Allows for access of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
The sensors to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.18.1.1.1 | ||||||
emsSensorStatusSensorSystemNamemandatory The system name of the sensor. This describes the hardware systemintent of this sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.18.1.1.2 | ||||||
emsSensorStatusSensorNamemandatory The name of the sensor as given by the system user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.18.1.1.3 | ||||||
emsSensorStatusSensorStatemandatory Getting this variable will return the sensor state. If the sensor is faulted,the sensorFaultedEMS (1) value will be returned. If the sensor is not faulted, the sensorOKEMS (2) value will be returned. If the sensor is n… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.18.1.1.4 | ||||||
emsSensorStatusSensorNormalStatemandatory Getting this variable will return the normal state of the sensor. Ifthe normal state is closed, the normallyClosedEMS (1) value will be returned. If the normal state is closed, the normallyOpenEMS (2) value will be ret… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.18.1.1.5 | ||||||
emsSensorStatusSensorAlarmDelaymandatory The delay (in seconds) after a sensor detects an alarm condition before thecondition is reported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.18.1.1.6 |
.1.3.6.1.4.1.318.1.1.10.3.19.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsSmokeSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsSmokeSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsSmokeSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.19.1.1.1 | ||||||
emsSmokeSensorConfigSensorNamemandatory The user defined name of the smoke sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.1.1.2 | ||||||
emsSmokeSensorConfigSensorLocationmandatory The user defined location of the smoke sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.1.1.3 | ||||||
emsSmokeSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.19.1.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.19.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsVibrationSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsVibrationSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsVibrationSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.19.2.1.1 | ||||||
emsVibrationSensorConfigSensorNamemandatory The user defined name of the vibration sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.2.1.2 | ||||||
| The user defined location of the vibration sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.2.1.3 | ||||||
| The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.19.2.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.19.3
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsFluidSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsFluidSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsFluidSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.19.3.1.1 | ||||||
emsFluidSensorConfigSensorNamemandatory The user defined name of the fluid sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.3.1.2 | ||||||
emsFluidSensorConfigSensorLocationmandatory The user defined location of the fluid sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.3.1.3 | ||||||
emsFluidSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.19.3.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.19.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsDoorSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsDoorSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsDoorSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.19.4.1.1 | ||||||
emsDoorSensorConfigSensorNamemandatory The user defined name of the door sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.4.1.2 | ||||||
emsDoorSensorConfigSensorLocationmandatory The user defined location of the door sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.4.1.3 | ||||||
emsDoorSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe door sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.19.4.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.19.5
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsLeakRopeConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsLeakRopeConfigTable'
Allows for the configuration of an individual leak rope.
The leak rope to configure.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
emsLeakRopeConfigIndexmandatory The index of the leak rope entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.19.5.1.1 | ||||||||||
emsLeakRopeConfigNamemandatory The user-defined name of the leak rope. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.5.1.2 | ||||||||||
emsLeakRopeConfigLocationmandatory The user-defined location of the leak rope. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.3.19.5.1.3 | ||||||||||
emsLeakRopeConfigSeveritymandatory The severity of the alarm that will be triggered when the leak rope is activated. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.19.5.1.4 |
.1.3.6.1.4.1.318.1.1.10.3.20.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsSmokeSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsSmokeSensorStatusTable'
Allows for the access of individual sensors.
The sensor to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsSmokeSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.20.2.1.1 | ||||||
emsSmokeSensorStatusSensorNamemandatory The user defined name of the smoke sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.2.1.2 | ||||||
emsSmokeSensorStatusSensorLocationmandatory The user defined location of the smoke sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.2.1.3 | ||||||
emsSmokeSensorStatusSensorStatemandatory The state of the smoke sensor.smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.2.1.4 | ||||||
emsSmokeSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.2.1.5 | ||||||
emsSmokeSensorCommStatusmandatory The communication status of the smoke sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.2.1.6 |
.1.3.6.1.4.1.318.1.1.10.3.20.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsVibrationSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsVibrationSensorStatusTable'
Allows for the access of individual sensors.
The sensor to access.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsVibrationSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.20.4.1.1 | ||||||
emsVibrationSensorStatusSensorNamemandatory The user defined name of the vibration sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.4.1.2 | ||||||
| The user defined location of the vibration sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.4.1.3 | ||||||
emsVibrationSensorStatusSensorStatemandatory The state of the vibration sensor.vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.4.1.4 | ||||||
| The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.4.1.5 | ||||||
emsVibrationSensorCommStatusmandatory The communication status of the vibration sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.4.1.6 |
.1.3.6.1.4.1.318.1.1.10.3.20.6
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsFluidSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsFluidSensorStatusTable'
Allows for the access of individual sensors.
The sensors to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsFluidSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.20.6.1.1 | ||||||
emsFluidSensorStatusSensorNamemandatory The user defined name of the fluid sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.6.1.2 | ||||||
emsFluidSensorStatusSensorLocationmandatory The user defined location of the fluid sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.6.1.3 | ||||||
emsFluidSensorStatusSensorStatemandatory The state of the fluid sensor.fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.6.1.4 | ||||||
emsFluidSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.6.1.5 | ||||||
emsFluidSensorCommStatusmandatory The communication status of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.6.1.6 |
.1.3.6.1.4.1.318.1.1.10.3.20.8
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsDoorSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsDoorSensorStatusTable'
Allows for the access of individual sensors.
The sensor to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
emsDoorSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.20.8.1.1 | ||||||
emsDoorSensorStatusSensorNamemandatory The user defined name of the door sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.8.1.2 | ||||||
emsDoorSensorStatusSensorLocationmandatory The user defined location of the door sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.8.1.3 | ||||||
emsDoorSensorStatusSensorStatemandatory The state of the door sensor.open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.8.1.4 | ||||||
emsDoorSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe door sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.8.1.5 | ||||||
emsDoorSensorCommStatusmandatory The communication status of the door sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.8.1.6 |
.1.3.6.1.4.1.318.1.1.10.3.20.10
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk emsLeakRopeStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsLeakRopeStatusTable'
Allows for the access of individual leak ropes.
The leak rope to access.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
emsLeakRopeStatusIndexmandatory The index of the leak rope entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.3.20.10.1.1 | ||||||||||
emsLeakRopeStatusNamemandatory The user defined name of the leak rope. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.10.1.2 | ||||||||||
emsLeakRopeStatusLocationmandatory The user defined location of the leak rope. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.3.20.10.1.3 | ||||||||||
emsLeakRopeStatusStatemandatory The state of the leak rope.The values can be noleak(1), leakdetected(2), or unknown(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.10.1.4 | ||||||||||
emsLeakRopeStatusSeveritymandatory The severity of the alarm that will be triggered when the leak rope is activated. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.10.1.5 | ||||||||||
emsLeakRopeCommStatusmandatory The communication status of the leak rope.The values can be connected(1), disconnected(2), or commsLost(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.3.20.10.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.1.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memModulesStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memModulesStatusTable'
Allows for getting status information from the modules attached to the system.
The unit to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
memModulesStatusModuleNumbermandatory The module number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.1 |
memModulesStatusModuleNamemandatory The module name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.2 |
memModulesStatusModuleLocationmandatory The location of the module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.3 |
memModulesStatusModelNumbermandatory The model number of the module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.4 |
memModulesStatusSerialNumbermandatory The serial number of the module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.5 |
memModulesStatusFirmwareRevmandatory The firmware revision of the module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.6 |
memModulesStatusHardwareRevmandatory The hardware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.1.2.1.7 |
.1.3.6.1.4.1.318.1.1.10.4.1.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memModulesConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memModulesConfigTable'
Allows for getting status information from the modules attached to the system.
The unit to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
memModulesConfigModuleNumbermandatory The module number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.1.4.1.1 |
memModulesConfigModuleNamemandatory The module name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.1.4.1.2 |
memModulesConfigModuleLocationmandatory The location of the module. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.1.4.1.3 |
.1.3.6.1.4.1.318.1.1.10.4.2.3
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memSensorsStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memSensorsStatusTable'
Allows for getting sensor status information.
The unit to get data from.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memSensorsStatusModuleNumbermandatory The number of the module that the sensor is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.1 | ||||||
memSensorsStatusSensorNumbermandatory The number of this sensor on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.2 | ||||||
memSensorsStatusSensorNamemandatory The sensor name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.3 | ||||||
memSensorsStatusSensorLocationmandatory The location of the sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.4 | ||||||
memSensorsTemperaturemandatory The sensor's current temperature reading.Units are displayed in the scale shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.5 | ||||||
memSensorsHumiditymandatory The current humidity reading from the sensor. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.6 | ||||||
memSensorsCommStatusmandatory The communications status of the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.2.3.1.7 | ||||||
memSensorsAlarmStatusmandatory The alarm status of the sensor.memWarning is not applicable to voltage sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.2.3.1.8 | ||||||
memSensorsTemperatureHighPrecmandatory The current temperature is displayed in tenths of degrees in the scaleshown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.9 | ||||||
memSensorsVoltagemandatory The sensor's current voltage reading.Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.3.1.10 |
.1.3.6.1.4.1.318.1.1.10.4.2.5
·
1 row entry
·
25 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memSensorsConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memSensorsConfigTable'
Allows for getting configuration information from sensors attached to the system.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memSensorsConfigModuleNumbermandatory The number of the module that the sensor is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.1 | ||||
memSensorsConfigSensorNumbermandatory The number of this sensor on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.2 | ||||
memSensorsNamemandatory A descriptive name for the sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.3 | ||||
memSensorsLocationmandatory The location of the sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.4 | ||||
memSensorsAlarmGenerationmandatory Enable or disable alarm generation on this sensor. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.2.5.1.5 | ||||
memSensorsTempMaxThreshmandatory The temperature at which the MEM will generate a maximumtemperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.6 | ||||
memSensorsTempHighThreshmandatory The temperature at which the MEM will generate a hightemperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.7 | ||||
memSensorsTempLowThreshmandatory The temperature at which the MEM will generate a lowtemperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.8 | ||||
memSensorsTempMinThreshmandatory The temperature at which the MEM will generate a minimumtemperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.9 | ||||
memSensorsTempThreshHysteresismandatory The change in temperature required to cause atemperature alarm to change from an active to an inactive state. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.10 | ||||
| The value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.11 | ||||
memSensorsTempShortDecRateThreshTimemandatory The time over which the temperature may not decreasebeyond the value specified by the temperature short-term decreasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.12 | ||||
| The value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.13 | ||||
memSensorsTempShortIncRateThreshTimemandatory The time over which the temperature may not increasebeyond the value specified by the temperature short-term increasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.14 | ||||
memSensorsTempLongDecRateThreshValuemandatory The value of the temperature long-term decreasing ratetime that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.15 | ||||
memSensorsTempLongDecRateThreshTimemandatory The time over which the temperature may not decreasebeyond the value specified by the temperature long-term decreasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.16 | ||||
memSensorsTempLongIncRateThreshValuemandatory The value of the temperature long-term increasing ratetime that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSysTempUnits OID. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.17 | ||||
memSensorsTempLongIncRateThreshTimemandatory The time over which the temperature may not increasebeyond the value specified by the temperature long-term increasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.18 | ||||
memSensorsHumidityMaxThreshmandatory The humidity at which the maximum humidity threshold alarmwill be generated. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.19 | ||||
memSensorsHumidityHighThreshmandatory The humidity at which the high humidity threshold alarmwill be generated. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.20 | ||||
memSensorsHumidityLowThreshmandatory The humidity at which the low humidity threshold alarmwill be generated. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.21 | ||||
memSensorsHumidityMinThreshmandatory The humidity at which the minimum humidity threshold alarmwill be generated. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.22 | ||||
memSensorsHumidityThreshHysteresismandatory The change in humidity required to cause an active humidityalarm to change to the inactive state. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.23 | ||||
memSensorsVoltMaxThreshmandatory The voltage in tenths of volts at which the MEM will generate a maximumvoltage threshold violation alarm on this sensor. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.24 | ||||
memSensorsVoltMinThreshmandatory The voltage in tenths of volts at which the MEM will generate a minimumvoltage threshold violation alarm on this sensor. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.2.5.1.25 |
.1.3.6.1.4.1.318.1.1.10.4.3.2
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memInputsStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memInputsStatusTable'
Allows for getting input status information.
The unit to get data from.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
memInputsStatusModuleNumbermandatory The number of the module that the input is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.3.2.1.1 | ||||||||
memInputsStatusInputNumbermandatory The number of this input on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.3.2.1.2 | ||||||||
memInputsStatusInputNamemandatory The input name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.3.2.1.3 | ||||||||
memInputsStatusInputLocationmandatory The location of the input. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.3.2.1.4 | ||||||||
memInputsStatusCurrentStatemandatory The current state of the input. This OID will returninputStateNotAplicable(4) for analog input types. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.2.1.5 | ||||||||
memInputsStatusCurrentAnalogValuemandatory The current analog value of the input in the units definedby the user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.3.2.1.6 | ||||||||
memInputsStatusAlarmStatusmandatory The alarm status of the input. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.2.1.7 | ||||||||
memInputsCommStatusmandatory The communications status of the input. This OID is only supported by NBRK0200. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.2.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.3.4
·
1 row entry
·
25 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memInputsConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memInputsConfigTable'
Allows for getting input configuration information.
The unit to get data from.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
memInputsConfigModuleNumbermandatory The number of the module that the input is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.1 | ||||||||||
memInputsConfigInputNumbermandatory The number of this input on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.2 | ||||||||||
memInputNamemandatory The name of the input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.3 | ||||||||||
memInputLocationmandatory The location of the input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.4 | ||||||||||
memInputTypemandatory The type of input this contact will take. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.4.1.5 | ||||||||||
memInputAlarmGenerationmandatory Enable or disable alarm generation on this input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.4.1.6 | ||||||||||
memInputNormalStatemandatory Defines the normal (no alarm) state of the input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.4.1.7 | ||||||||||
memInputAbnormalSeveritymandatory Defines the severity of the event that is associatedwith the abnormal state of the input. This OID will return inputSeverityNotApplicable(4) for analog input types. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.3.4.1.8 | ||||||||||
memInputNumberCalibrationPointsmandatory The number of calibration points that are required forthis input. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.9 | ||||||||||
memInputAnalogCalibrationPoint1mandatory The electrical value that the input sensor will measure at thefirst calibration point. This OID is relevant only for inputs configured as analog type (ma or V). | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.10 | ||||||||||
memInputAnalogCalibrationPoint2mandatory The electrical value that the input sensor will measure at thesecond calibration point. This OID is relevant only for inputs configured as analog type (ma or V). | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.11 | ||||||||||
memInputAnalogCalibrationPoint3mandatory The electrical value that the input sensor will measure at thethird calibration point. This OID is relevant only for inputs configured as analog type (ma or V). | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.12 | ||||||||||
memInputAnalogCalibrationPoint4mandatory The electrical value that the input sensor will measure at thefourth calibration point. This OID is relevant only for inputs configured as analog type (ma or V). | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.13 | ||||||||||
memInputAnalogCalibrationPoint5mandatory The electrical value that the input sensor will measure at thefifth calibration point. This OID is relevant only for inputs configured as analog type (ma or V). | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.14 | ||||||||||
memInputAnalogCalibrationPoint1Valuemandatory The value of the input, in units of measure defined bythe user, that corresponds to the current setting at the first calibration point. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.15 | ||||||||||
memInputAnalogCalibrationPoint2Valuemandatory The value of the input, in units of measure defined bythe user, that corresponds to the current setting at the second calibration point. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.16 | ||||||||||
memInputAnalogCalibrationPoint3Valuemandatory The value of the input, in units of measure defined bythe user, that corresponds to the current setting at the third calibration point. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.17 | ||||||||||
memInputAnalogCalibrationPoint4Valuemandatory The value of the input, in units of measure defined bythe user, that corresponds to the current setting at the fourth calibration point. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.18 | ||||||||||
memInputAnalogCalibrationPoint5Valuemandatory The value of the input, in units of measure defined bythe user, that corresponds to the current setting at the fifth calibration point. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.19 | ||||||||||
memInputAnalogMeasurementUnitsmandatory The units of measure to be used for this input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.20 | ||||||||||
memInputAnalogMaxThreshmandatory The input value at which a maximum threshold violationalarm will be generated on this input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.21 | ||||||||||
memInputAnalogHighThreshmandatory The input value at which a high threshold violationalarm will be generated on this input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.22 | ||||||||||
memInputAnalogLowThreshmandatory The input value at which a low threshold violationalarm will be generated on this input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.23 | ||||||||||
memInputAnalogMinThreshmandatory The input value at which a minimum threshold violationalarm will be generated on this input. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.24 | ||||||||||
memInputAnalogThreshHysteresismandatory The change in value required to cause an alarm on this inputto change from active to inactive. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.3.4.1.25 |
.1.3.6.1.4.1.318.1.1.10.4.4.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memOutputStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memOutputStatusTable'
Allows for getting output status information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memOutputStatusModuleNumbermandatory The number of the module that the output is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.4.2.1.1 | ||||
memOutputStatusOutputNumbermandatory The number of this output on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.4.2.1.2 | ||||
memOutputStatusOutputNamemandatory The output name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.4.2.1.3 | ||||
memOutputStatusOutputLocationmandatory The location of the output. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.4.2.1.4 | ||||
memOutputStatusCurrentStatemandatory The state of the output. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.4.2.1.5 | ||||
memOutputStatusAlarmStatemandatory The alarm state of the output. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.4.2.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.4.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memOutputConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memOutputConfigTable'
Allows for getting output configuration information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memOutputConfigModuleNumbermandatory The number of the module that the output is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.4.4.1.1 | ||||
memOutputConfigOutputNumbermandatory The number of this output on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.4.4.1.2 | ||||
memOutputNamemandatory The name of the output. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.4.4.1.3 | ||||
memOutputLocationmandatory The location of the output. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.4.4.1.4 | ||||
memOutputNormalStatemandatory The state of the output that will not generate an alarm. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.4.4.1.5 | ||||
memOutputActionmandatory Manual control actions for the output. SNMP get command will return the stateof the output, SNMP set of this OID controls the output. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.4.4.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.5.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memOutletStatusTable'
Allows for getting outlet status information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memOutletStatusModuleNumbermandatory The number of the module that the outlet is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.5.2.1.1 | ||||
memOutletStatusOutletNumbermandatory The number of this outlet on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.5.2.1.2 | ||||
memOutletStatusOutletNamemandatory The outlet name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.5.2.1.3 | ||||
memOutletStatusOutletLocationmandatory The location of the outlet. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.5.2.1.4 | ||||
memOutletStatusCurrentStatemandatory The state of the outlet. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.5.2.1.5 | ||||
memOutletStatusAlarmStatemandatory The alarm state of the outlet. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.5.2.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.5.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memOutletConfigTable'
Allows for getting outlet configuration information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memOutletConfigModuleNumbermandatory The number of the module that the Outlet is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.5.4.1.1 | ||||
memOutletConfigOutletNumbermandatory The number of this Outlet on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.5.4.1.2 | ||||
memOutletNamemandatory The name of the Outlet. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.5.4.1.3 | ||||
memOutletLocationmandatory The location of the Outlet. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.5.4.1.4 | ||||
memOutletNormalStatemandatory The state of the Outlet that will not generate an alarm. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.5.4.1.5 | ||||
memOutletActionmandatory Manual control actions for the Outlet. Get displays stateof outlet, set controls outlet. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.5.4.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.6.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memBeaconStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memBeaconStatusTable'
Allows for getting beacon status information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memBeaconStatusModuleNumbermandatory The number of the module that the beacon is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.6.2.1.1 | ||||
memBeaconStatusBeaconNumbermandatory The number of this beacon on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.6.2.1.2 | ||||
memBeaconStatusBeaconNamemandatory The beacon name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.6.2.1.3 | ||||
memBeaconStatusBeaconLocationmandatory The location of the beacon. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.6.2.1.4 | ||||
memBeaconStatusCurrentStatemandatory The state of the beacon. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.6.2.1.5 | ||||
memBeaconStatusAlarmStatemandatory The alarm state of the beacon. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.6.2.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.6.4
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memBeaconConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memBeaconConfigTable'
Allows for getting beacon configuration information.
The unit to get data from.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
memBeaconConfigModuleNumbermandatory The number of the module that the beacon is attached to. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.6.4.1.1 | ||||
memBeaconConfigBeaconNumbermandatory The number of this beacon on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.6.4.1.2 | ||||
memBeaconConfigNamemandatory The name of the beacon. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.6.4.1.3 | ||||
memBeaconConfigLocationmandatory The location of the beacon. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.6.4.1.4 | ||||
memBeaconActionmandatory Control action (on/off) for the beacon. Setting this OID will turn thebeacon on/off. Getting this OID will respond with the current state. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.6.4.1.5 |
.1.3.6.1.4.1.318.1.1.10.4.7.2
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memSmokeSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memSmokeSensorStatusTable'
Allows for the access of individual sensors.
The sensor to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memSmokeSensorStatusModuleIndexmandatory The index to the module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.2.1.1 | ||||||
memSmokeSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.2.1.2 | ||||||
memSmokeSensorStatusSensorNamemandatory The user defined name of the smoke sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.2.1.3 | ||||||
memSmokeSensorStatusSensorLocationmandatory The user defined location of the smoke sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.2.1.4 | ||||||
memSmokeSensorStatusSensorStatemandatory The state of the smoke sensor.smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.2.1.5 | ||||||
memSmokeSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.2.1.6 | ||||||
memSmokeStatusAlarmStatusmandatory The alarm status of the smoke sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.2.1.7 | ||||||
memSmokeSensorCommStatusmandatory The communication status of the smoke sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.2.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.7.4
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memVibrationSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memVibrationSensorStatusTable'
Allows for the access of individual sensors.
The sensors to access.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memVibrationSensorStatusModuleIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.4.1.1 | ||||||
memVibrationSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.4.1.2 | ||||||
memVibrationSensorStatusSensorNamemandatory The user defined name of the vibration sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.4.1.3 | ||||||
| The user defined location of the vibration sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.4.1.4 | ||||||
memVibrationSensorStatusSensorStatemandatory The state of the vibration sensor.vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.4.1.5 | ||||||
| The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.4.1.6 | ||||||
memVibrationStatusAlarmStatusmandatory The alarm status of the vibration sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.4.1.7 | ||||||
memVibrationSensorCommStatusmandatory The communication status of the vibration sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.4.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.7.6
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memFluidSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memFluidSensorStatusTable'
Allows for access of individual sensors.
The sensor to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memFluidSensorStatusModuleIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.6.1.1 | ||||||
memFluidSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.6.1.2 | ||||||
memFluidSensorStatusSensorNamemandatory The user defined name of the fluid sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.6.1.3 | ||||||
memFluidSensorStatusSensorLocationmandatory The user defined location of the fluid sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.6.1.4 | ||||||
memFluidSensorStatusSensorStatemandatory The state of the fluid sensor.fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.6.1.5 | ||||||
memFluidSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.6.1.6 | ||||||
memFluidStatusAlarmStatusmandatory The alarm status of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.6.1.7 | ||||||
memFluidSensorCommStatusmandatory The communication status of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.6.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.7.8
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memDoorSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memDoorSensorStatusTable'
Allows for the access of individual sensors.
The sensor to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memDoorSensorStatusModuleIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.8.1.1 | ||||||
memDoorSensorStatusSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.8.1.2 | ||||||
memDoorSensorStatusSensorNamemandatory The user defined name of the door sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.8.1.3 | ||||||
memDoorSensorStatusSensorLocationmandatory The user defined location of the door sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.8.1.4 | ||||||
memDoorSensorStatusSensorStatemandatory The state of the door sensor.open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.8.1.5 | ||||||
memDoorSensorStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe door sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.8.1.6 | ||||||
memDoorStatusAlarmStatusmandatory The alarm status of the door sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.8.1.7 | ||||||
memDoorSensorCommStatusmandatory The communication status of the door sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.8.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.7.9
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memSmokeSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memSmokeSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.9.1.1 | ||||||
memSmokeSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.9.1.2 | ||||||
memSmokeSensorConfigSensorNamemandatory The user defined name of the smoke sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.9.1.3 | ||||||
memSmokeSensorConfigSensorLocationmandatory The user defined location of the smoke sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.9.1.4 | ||||||
memSmokeSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.9.1.5 | ||||||
memSmokeSensorConfigAlarmGenerationmandatory Enable or disable alarm generation on this input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.9.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.7.10
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memVibrationSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memVibrationSensorConfigTable'
Allows for the configuration of individual sensors.
The sensor to configure.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memVibrationSensorModuleConfigIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.10.1.1 | ||||||
memVibrationSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.10.1.2 | ||||||
memVibrationSensorConfigSensorNamemandatory The user defined name of the vibration sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.10.1.3 | ||||||
| The user defined location of the vibration sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.10.1.4 | ||||||
| The severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.10.1.5 | ||||||
| Enable or disable alarm generation on this input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.10.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.7.11
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memFluidSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memFluidSensorConfigTable'
Allows for the configuration of individual sensors.
The sensor to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memFluidSensorModuleConfigIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.11.1.1 | ||||||
memFluidSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.11.1.2 | ||||||
memFluidSensorConfigSensorNamemandatory The user defined name of the fluid sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.11.1.3 | ||||||
memFluidSensorConfigSensorLocationmandatory The user defined location of the fluid sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.11.1.4 | ||||||
memFluidSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.11.1.5 | ||||||
memFluidSensorConfigAlarmGenerationmandatory Enable or disable alarm generation on this input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.11.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.7.12
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memDoorSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memDoorSensorConfigTable'
Allows for the configuration of individual sensors.
The sensors to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memDoorSensorModuleConfigIndexmandatory The index to the sensor module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.12.1.1 | ||||||
memDoorSensorConfigSensorIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.12.1.2 | ||||||
memDoorSensorConfigSensorNamemandatory The user defined name of the door sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.12.1.3 | ||||||
memDoorSensorConfigSensorLocationmandatory The user defined location of the door sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.12.1.4 | ||||||
memDoorSensorConfigSensorSeveritymandatory The severity of the alarm that will be triggered whenthe door sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.12.1.5 | ||||||
memDoorSensorConfigAlarmGenerationmandatory Enable or disable alarm generation on this input. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.12.1.6 |
.1.3.6.1.4.1.318.1.1.10.4.7.14
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memLeakRopeStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memLeakRopeStatusTable'
Allows for access of individual leak ropes.
The leak rope to access.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memLeakRopeStatusModuleIndexmandatory The index of the leak rope entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.14.1.1 | ||||||
memLeakRopeStatusSensorIndexmandatory The index of the leak rope sensor. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.14.1.2 | ||||||
memLeakRopeStatusSensorNamemandatory The user defined name of the leak rope sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.14.1.3 | ||||||
memLeakRopeStatusSensorLocationmandatory The user-defined location of the leak rope sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.4.7.14.1.4 | ||||||
memLeakRopeStatusSensorStatemandatory The state of the leak rope sensor.noleak (1) indicates there is no leak. leakdetected (2) indicates there is a detected leak. unknown (3) indicates the state is unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.14.1.5 | ||||||
memLeakRopeStatusSensorSeveritymandatory The severity of the alarm that will be triggered whenthe leak rope sensor is activated. The alarms can be critical(1), warning(2) or informational(3). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.14.1.6 | ||||||
memLeakRopeAlarmStatusmandatory The alarm status of the rope link sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.14.1.7 | ||||||
memLeakRopeCommStatusmandatory The communication status of the rope link sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.14.1.8 |
.1.3.6.1.4.1.318.1.1.10.4.7.15
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk memLeakRopeConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::memLeakRopeConfigTable'
Allows for the configuration of individual leak ropes.
The leak rope to configure.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
memLeakRopeConfigModuleIndexmandatory The index of the leak rope module entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.15.1.1 | ||||||
memLeakRopeConfigSensorIndexmandatory The index of the leak rope sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.4.7.15.1.2 | ||||||
memLeakRopeConfigSensorNamemandatory The user-defined name of the leak rope sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.15.1.3 | ||||||
memLeakRopeConfigSensorLocationmandatory The user-defined location of the leak rope sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.4.7.15.1.4 | ||||||
memLeakRopeConfigSensorSeveritymandatory The severity level of the leak rope sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.15.1.5 | ||||||
memLeakRopeConfigAlarmGenerationmandatory Enable or disable alarm generation on this input. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.4.7.15.1.6 |
.1.3.6.1.4.1.318.1.1.10.5.1.1
·
1 row entry
·
23 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk wirelessSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::wirelessSensorStatusTable'
Allows for the access of individual sensors.
A list of wireless sensor status table entries.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
wirelessSensorStatusIndexmandatory The index to the sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.1 | ||||
wirelessSensorStatusExtAddrmandatory The extended address is the combination of the unique 10 byteMAC address of the sensor concatenated with its short address. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.2 | ||||
wirelessSensorStatusNamemandatory The name of the wireless sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.3 | ||||
wirelessSensorStatusAlarmGenerationmandatory Indicates whether alarm generation is enabled or disabled for the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.1.1.1.4 | ||||
wirelessSensorStatusTemperaturemandatory The current temperature are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.5 | ||||
wirelessSensorStatusHighTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.6 | ||||
wirelessSensorStatusLowTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.7 | ||||
wirelessSensorStatusHumiditymandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.8 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.9 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.10 | ||||
wirelessSensorStatusCommStatusmandatory The communication status of the wireless sensor.inactive(0) indicates sensor is in the wireless network but not sending information. active(1) indicates wireless sensor is live and sending information. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.1.1.1.11 | ||||
wirelessSensorStatusMaxTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.12 | ||||
wirelessSensorStatusMinTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.13 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.14 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.15 | ||||
wirelessSensorStatusBatterymandatory Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.16 | ||||
wirelessSensorStatusLowBatteryThreshmandatory Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.17 | ||||
wirelessSensorStatusMinBatteryThreshmandatory Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.18 | ||||
wirelessSensorStatusRssimandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.19 | ||||
wirelessSensorStatusLowRssiThreshmandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.20 | ||||
wirelessSensorStatusMinRssiThreshmandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.21 | ||||
wirelessSensorStatusLocationmandatory A user-defined string identifying the locationof the wireless sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.22 | ||||
wirelessSensorStatusAlarmStatusmandatory The alarm status of the wireless sensor. This integer should be interpretedas a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the co… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.1.1.1.23 |
.1.3.6.1.4.1.318.1.1.10.5.2.1
·
1 row entry
·
26 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk wirelessSensorPodStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::wirelessSensorPodStatusTable'
Allows for the access of individual pod sensors.
The sensor pod to access.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
wirelessSensorPodStatusIndexmandatory The index to the pod sensor entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.1 | ||||
wirelessSensorPodPortIndexmandatory The pod sensor port index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.2 | ||||
wirelessSensorPodStatusExtAddrmandatory The extended address is the combination of the unique 10 byte MAC addressof the sensor concatenated with its short address. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.3 | ||||
wirelessSensorPodStatusNamemandatory The name of the sensor pod. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.4 | ||||
| Status of whether alarm generation is enabled or disabled. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.2.1.1.5 | ||||
wirelessSensorPodStatusTemperaturemandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.6 | ||||
| Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.7 | ||||
wirelessSensorPodStatusLowTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.8 | ||||
wirelessSensorPodStatusHumiditymandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.9 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.10 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.11 | ||||
wirelessSensorPodStatusCommStatusmandatory The communication status of the wireless sensor.inactive(0) indicates pod sensor is in the wireless network but not sending information. active(1) indicates wireless sensor is live and sending information. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.2.1.1.12 | ||||
wirelessSensorPodStatusMaxTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.13 | ||||
wirelessSensorPodStatusMinTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.14 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.15 | ||||
| Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.16 | ||||
| State of the dry contact. If the dry contact is closed, the drycontactClosed (1) value will be returned. If the dry contact state is open, the drycontactOpen (0) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.2.1.1.17 | ||||
| The normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpen (0) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.2.1.1.18 | ||||
wirelessSensorPodStatusBatterymandatory Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.19 | ||||
| Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.20 | ||||
| Values are displayed in tenths of Volts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.21 | ||||
wirelessSensorPodStatusRssimandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.22 | ||||
wirelessSensorPodStatusLowRssiThreshmandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.23 | ||||
wirelessSensorPodStatusMinRssiThreshmandatory Values are represented in whole number percentage. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.24 | ||||
wirelessSensorPodStatusLocationmandatory The location of the wireless sensor pod. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.25 | ||||
wirelessSensorPodStatusAlarmStatusmandatory The alarm status of the wireless pod sensor. This integer should be interpretedas a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if th… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.2.1.1.26 |
.1.3.6.1.4.1.318.1.1.10.5.3.1
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk wirelessSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::wirelessSensorConfigTable'
Allows for the configuration of individual sensors.
The sensor to configure.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
wirelessSensorConfigIndexmandatory The index to the entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.1 | ||||
wirelessSensorConfigNamemandatory The user-defined wireless sensor ID string. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.2 | ||||
wirelessSensorConfigAlarmGenerationmandatory Enable or disable alarm generation for this sensor. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.3.1.1.3 | ||||
wirelessSensorConfigHighTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.4 | ||||
wirelessSensorConfigLowTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.5 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.6 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.7 | ||||
wirelessSensorConfigMaxTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.8 | ||||
wirelessSensorConfigMinTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.9 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.10 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.11 | ||||
wirelessSensorConfigLowBatteryThreshmandatory Values are displayed in tenths of Volts DC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.12 | ||||
wirelessSensorConfigMinBatteryThreshmandatory Values are displayed in tenths of Volts DC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.13 | ||||
wirelessSensorConfigLowRssiThreshmandatory Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.14 | ||||
wirelessSensorConfigMinRssiThreshmandatory Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.15 | ||||
wirelessSensorConfigLocationmandatory A user-defined string identifying the location of thewireless sensor. Maximum text input is 20 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.5.3.1.1.16 |
.1.3.6.1.4.1.318.1.1.10.5.4.1
·
1 row entry
·
18 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk wirelessSensorPodConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::wirelessSensorPodConfigTable'
Allows for the configuration of individual sensors.
The sensor to configure.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
wirelessSensorPodConfigIndexmandatory The index to the entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.1 | ||||
wirelessSensorPodConfigPortIndexmandatory The sensor pod port index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.2 | ||||
wirelessSensorPodConfigNamemandatory The user defined name of the sensor pod. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.3 | ||||
| Enable or disable alarm generation for this sensor. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.4.1.1.4 | ||||
| The normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpen (0) value will be returned. Setting this variable will cha… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.10.5.4.1.1.5 | ||||
| Values are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.6 | ||||
wirelessSensorPodConfigLowTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.7 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.8 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.9 | ||||
wirelessSensorPodConfigMaxTempThreshmandatory Values are displayed in tenths of degrees in the scaleshown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.10 | ||||
wirelessSensorPodConfigMinTempThreshmandatory Values are represented in whole number degrees.Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.11 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.12 | ||||
| Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.13 | ||||
| Values are displayed in tenths of Volts DC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.14 | ||||
| Values are displayed in tenths of Volts DC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.15 | ||||
wirelessSensorPodConfigLowRssiThreshmandatory Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.16 | ||||
wirelessSensorPodConfigMinRssiThreshmandatory Values are represented in whole number percentage. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.17 | ||||
wirelessSensorPodConfigLocationmandatory A user-defined string identifying the location of thewireless pod sensor. Maximum text input is 20 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.10.5.4.1.1.18 |
.1.3.6.1.4.1.318.1.1.12.2.1.6
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDULoadDevBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadDevBankTable'
Allows for getting the Bank Max Load in the Rack PDU.
The Rack PDU Banks Access.
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDULoadDevBankIndexmandatory The index to the Rack PDU bank entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.6.1.1 |
rPDULoadDevBankNumbermandatory Getting this OID will return the bank number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.6.1.2 |
rPDULoadDevBankMaxLoadmandatory Getting this OID will return the maximum rated powerthat each bank of the Rack PDU can provide. It is represented in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.6.1.3 |
.1.3.6.1.4.1.318.1.1.12.2.1.8
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDULoadDevMaxOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadDevMaxOutletTable'
Allows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
This gives access to Max Outlet Load of an Outlet Monitored Rack PDU
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDULoadDevOutletIndexmandatory The index to the Outlet Monitored Rack PDU Max Outlet Load entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.8.1.1 |
rPDULoadDevOutletNumbermandatory Getting this OID will return the Outlet number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.8.1.2 |
rPDULoadDevMaxOutletLoadmandatory Getting this OID will return the maximum rated powerthat each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.1.8.1.3 |
.1.3.6.1.4.1.318.1.1.12.2.2.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDULoadPhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadPhaseConfigTable'
Allows for configuration of each Rack PDU phase. The number of entries is contained in the rPDULoadDevNumPhases OID.
The Rack PDU phase to configure.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDULoadPhaseConfigIndexmandatory The index to the Rack PDU phase entry. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.2.2.1.1.1 | ||||||||
rPDULoadPhaseConfigLowLoadThresholdmandatory A threshold that indicates the power consumption ofthe load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.2 | ||||||||
| A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.3 | ||||||||
rPDULoadPhaseConfigOverloadThresholdmandatory A threshold that indicates the power consumption ofthe load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.2.1.1.4 | ||||||||
rPDULoadPhaseConfigAlarmmandatory Getting this OID will return the current Phase Alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.2.2.1.1.5 |
.1.3.6.1.4.1.318.1.1.12.2.3.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDULoadStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadStatusTable'
Allows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (rPDULoadDevNumPhases OID) and the number of banks of outlets (rPDULoadDevNumBanks) Number of entries = #phases + #banks. NOTE: If a device has phase and bank information, all phase information shall precede the bank information. If a device has total information, it shall precede both the bank and the phase information.
The Rack PDU phase/bank to gather status from.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDULoadStatusIndexmandatory The index to the Rack PDU phase/bank entry. All phase information will precedeany bank information | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.3.1.1.1 | ||||||||
rPDULoadStatusLoadmandatory Getting this OID will return the phase/bank load measuredin tenths of Amps. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.12.2.3.1.1.2 | ||||||||
rPDULoadStatusLoadStatemandatory Getting this OID will return the phase/bank load state.phaseLoadNormal(1) indicates that the phase/bank is operating properly within the rPDULoadConfigLowLoadThreshold and rPDULoadConfigNearOverloadThres… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.2.3.1.1.3 | ||||||||
rPDULoadStatusPhaseNumbermandatory The phase number to which this record refers. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.3.1.1.4 | ||||||||
rPDULoadStatusBankNumbermandatory The bank number to which this record refers. A value of 0 will be returned ifany bank is not present or if it is phase related. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.3.1.1.5 |
.1.3.6.1.4.1.318.1.1.12.2.4.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDULoadBankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDULoadBankConfigTable'
Allows for configuration of each Rack PDU bank. The number of entries is contained in the rPDULoadDevNumBanks OID.
The Rack PDU bank to configure.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDULoadBankConfigIndexmandatory The index to the Rack PDU bank entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.4.1.1.1 | ||||||||
rPDULoadBankConfigLowLoadThresholdmandatory A threshold that indicates the power consumption ofthe load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.4.1.1.2 | ||||||||
| A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.4.1.1.3 | ||||||||
rPDULoadBankConfigOverloadThresholdmandatory A threshold that indicates the power consumption ofthe load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.2.4.1.1.4 | ||||||||
rPDULoadBankConfigAlarmmandatory Getting this OID will return the current Bank Alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.2.4.1.1.5 |
.1.3.6.1.4.1.318.1.1.12.3.2.1
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletPhaseTable'
Allows for management of outlets on a per phase basis.
The phase to manage.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDUOutletPhaseIndexmandatory The index to the Switched Rack PDU phase entry. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.2.1.1.1 | ||||||
rPDUOutletPhaseOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUphase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alwa… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.2.1.1.2 |
.1.3.6.1.4.1.318.1.1.12.3.3.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletControlTable'
Allows for control of the individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID.
The outlet to control.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDUOutletControlIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.3.1.1.1 | ||||||||||||||
rPDUOutletControlOutletNamemandatory The name of the outlet. The maximum string size is device dependent.An error will be returned if the set request exceeds the max size. This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.3.3.1.1.2 | ||||||||||||||
rPDUOutletControlOutletPhasemandatory The phase/s associated with this outlet.For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.3.1.1.3 | ||||||||||||||
rPDUOutletControlOutletCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setti… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.3.1.1.4 | ||||||||||||||
rPDUOutletControlOutletBankmandatory The bank associated with this outlet. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.3.1.1.5 |
.1.3.6.1.4.1.318.1.1.12.3.4.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletConfigTable'
Allows for configuration of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID.
The outlet to configure.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDUOutletConfigIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.1 | ||||||||||||
rPDUOutletConfigOutletNamemandatory The name of the outlet. The maximum string size is device dependent.An error will be returned if the set request exceeds the max size. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.2 | ||||||||||||
rPDUOutletConfigOutletPhasemandatory The phase/s associated with this outlet.For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.4.1.1.3 | ||||||||||||
rPDUOutletConfigPowerOnTimemandatory The amount of time (in seconds) the outlet will delaypowering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -1 - never power on. 0 … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.4 | ||||||||||||
rPDUOutletConfigPowerOffTimemandatory The amount of time (in seconds) the outlet will delaypowering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never power off. 0 - powe… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.5 | ||||||||||||
rPDUOutletConfigRebootDurationmandatory During a reboot sequence, power is turned off and thenback on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the start of the sequence, before turning power back on, at the en… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.6 | ||||||||||||
rPDUOutletConfigOutletBankmandatory The bank associated with this outlet. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.1.1.7 |
.1.3.6.1.4.1.318.1.1.12.3.4.3
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletConfigMonitoredTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletConfigMonitoredTable'
Allows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
This gives access to Monitored Outlet entries
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDUOutletConfigMonitoredIndexmandatory The index to the RACK PDU Phase entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.1 |
rPDUOutletConfigMonitoredNamemandatory The name of the Monitored Outlet. The maximum string size is device dependent.An error will be returned if the set request exceeds the max size. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.2 |
rPDUOutletConfigMonitoredNumbermandatory The outlet number of an Outlet Monitored RACK PDU. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.3 |
| A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.4 |
| A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.5 |
| A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.4.3.1.6 |
.1.3.6.1.4.1.318.1.1.12.3.5.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletStatusTable'
Allows for getting of status of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID or rPDUOutletDevMonitoredOutlets OID.
The outlet to gather status from.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDUOutletStatusIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.1 | ||||||||||||
rPDUOutletStatusOutletNamemandatory The name of the outlet. The maximum string size is device dependent.This OID is provided for informational purposes only. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.2 | ||||||||||||
rPDUOutletStatusOutletPhasemandatory The phase/s associated with this outlet.For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase1 (1), phase2 (2), or phase3 (… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.5.1.1.3 | ||||||||||||
rPDUOutletStatusOutletStatemandatory Getting this variable will return the outlet state. Ifthe outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusOff (2) value will be returned. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.5.1.1.4 | ||||||||||||
rPDUOutletStatusCommandPendingmandatory Getting this variable will return the command pendingstate of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will be returned. If there is not a command pending on the outle… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.5.1.1.5 | ||||||||||||
rPDUOutletStatusOutletBankmandatory The bank associated with this outlet. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.6 | ||||||||||||
rPDUOutletStatusLoadmandatory Getting this OID will return the measured Outlet load foran Outlet Monitored Rack PDU in tenths of Amps. For other models this OID is not supported. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.12.3.5.1.1.7 |
.1.3.6.1.4.1.318.1.1.12.3.6.1
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUOutletBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUOutletBankTable'
Allows for management of outlets on a per bank basis.
The bank to manage.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDUOutletBankIndexmandatory The index to the Switched Rack PDU bank entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.3.6.1.1.1 | ||||||
rPDUOutletBankOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUbank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alway… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.3.6.1.1.2 |
.1.3.6.1.4.1.318.1.1.12.5.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUStatusBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUStatusBankTable'
Allows for getting of status of each Rack PDU Bank
This gives access to Bank entries
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDUStatusBankIndexmandatory The index to the RACK PDU Bank entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.2.1.1 | ||||||||
rPDUStatusBankNumbermandatory Getting this OID will return the bank number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.2.1.2 | ||||||||
rPDUStatusBankStatemandatory Getting this OID will return the bank load state.bankLoadNormal(1) indicates that the bank is operating properly within the rPDULoadBankConfigLowLoadThreshold and rPDULoadBankConfigNearOverloadThreshold … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.5.2.1.3 |
.1.3.6.1.4.1.318.1.1.12.5.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUStatusPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUStatusPhaseTable'
Allows for getting of status of each Rack PDU Phase
This gives access to Phase entries
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDUStatusPhaseIndexmandatory The index to the RACK PDU Phase entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.4.1.1 | ||||||||
rPDUStatusPhaseNumbermandatory Getting this OID will return the phase number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.4.1.2 | ||||||||
rPDUStatusPhaseStatemandatory Getting this OID will return the Phase load state.phaseLoadNormal(1) indicates that the Phase is operating properly within the rPDULoadPhaseConfigLowLoadThreshold and rPDULoadPhaseConfigNearOverloadThres… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.5.4.1.3 |
.1.3.6.1.4.1.318.1.1.12.5.6
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDUStatusOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDUStatusOutletTable'
Allows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
This gives access to Outlet entries
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDUStatusOutletIndexmandatory The index to the RACK PDU Outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.6.1.1 | ||||||||
rPDUStatusOutletNumbermandatory Getting this OID will return the Outlet number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.12.5.6.1.2 | ||||||||
rPDUStatusOutletStatemandatory Getting this OID will return the Outlet load state.outletLoadNormal(1) indicates that the Outlet is operating properly within the rPDUOutletConfigMonitoredLowLoadThreshold and rPDUOutletConfigMonitoredNe… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.12.5.6.1.3 |
.1.3.6.1.4.1.318.1.1.13.1.1.3
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMIdentTable'
Allows for getting identification information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID |
|---|---|---|
airFMIdentModuleIndexmandatory The index of the module information. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.1 |
airFMIdentModuleModelNumbermandatory A character string identifying themodel number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.2 |
airFMIdentModuleDateOfMfgmandatory A character string identifying themanufacture date. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.3 |
airFMIdentModuleSerialNumbermandatory A character string identifying theunit serial number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.4 |
airFMIdentModuleFirmwareRevmandatory A character string identifying thefirmware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.5 |
airFMIdentModuleHardwareRevmandatory A character string identifying thehardware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.1.3.1.6 |
.1.3.6.1.4.1.318.1.1.13.1.2.20
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMStatusModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMStatusModuleTable'
Allows for getting information from each module in the system.
The module to get status from.
Indexes
| Column | Syntax | OID |
|---|---|---|
airFMStatusModuleIndexmandatory The index of the module information. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.1 |
airFMStatusModuleOutputCapacitymandatory The module output capacity in kilowatts.This OID has been deprecated in favor of airFMModOutputCapacity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.2 |
airFMStatusModuleSupplyTempCmandatory The module supply air temperature intenths of degrees Celsius. This OID has been deprecated in favor of airFMModSupplyTempC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.3 |
airFMStatusModuleSupplyTempFmandatory The module supply air temperature intenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModSupplyTempF. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.4 |
airFMStatusModuleSupplyHummandatory The module supply air humidity in tenths of percent RH.This OID has been deprecated in favor of airFMModSupplyHum. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.5 |
airFMStatusModuleReturnTempCmandatory The module return air temperature intenths of degrees Celsius. This OID has been deprecated in favor of airFMModReturnTempC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.6 |
airFMStatusModuleReturnTempFmandatory The module return air temperature intenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModReturnTempF. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.7 |
airFMStatusModuleReturnHummandatory The module return air humidity in tenths of percent RH.This OID has been deprecated in favor of airFMModReturnHum. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.2.20.1.8 |
.1.3.6.1.4.1.318.1.1.13.1.3.4.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMGroupSysRolesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMGroupSysRolesTable'
Allows for getting information from each system in the group.
The system to get status from.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
airFMGroupSysIndexmandatory The index of the system information. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.1 | ||||||||||||||
airFMGroupSysRoleStatusmandatory The present mode of the System. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.2 | ||||||||||||||
airFMGroupSysPresentRolemandatory The present role of the System in a Group. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.3 | ||||||||||||||
airFMGroupSysManualRoleSettingmandatory The manual role setting of the System in a Group.Only applies if Role Assignment Method is set to static (Manually Assigned Roles). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.4 | ||||||||||||||
airFMGroupSysRunHoursmandatory The total number of hours the System has beencontributing to environmental control. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.5 | ||||||||||||||
airFMGroupSysCommmandatory Indicates whether a system is communicating with theother Systems in the Group. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.6 | ||||||||||||||
airFMGroupSysIPAddressmandatory The IP Address of the System. | RFC1155-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.13.1.4.10.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysInputTable'
Allows for getting information from each input contact.
The input contact to obtain status from.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
airFMSysInputIndexmandatory The number designator of the Input Contact. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.1 | ||||||||||||
airFMSysInputNamemandatory The configurable name for the Input Contact. Maximumtext input is 13 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.2 | ||||||||||||
airFMSysInputStatusmandatory The state of this contact: Open or Closed. Aviolation will occur when this relay is not in its normal state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3 | ||||||||||||
airFMSysInputNormalStatemandatory Set the normal state of this contact (the state whenno alarm/event exists). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.4 | ||||||||||||
airFMSysInputDelaymandatory Set the delay between this contact exiting its normalstate and an alarm being triggered. Measured in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.5 | ||||||||||||
airFMSysInputAlarmActionmandatory Sets the behavior for this contact when it exits itsnormal state. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.6 |
.1.3.6.1.4.1.318.1.1.13.1.4.11.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysOutputTable'
Allows for getting information from each output relay.
The output relay to obtain status from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
airFMSysOutputIndexmandatory The number designator of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.1 | ||||
airFMSysOutputStatusmandatory The state of this relay: Open or Closed. A violationwill occur when this relay is not in its normal state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2 | ||||
airFMSysOutputNormalStatemandatory Set the normal state of this relay (the state when noalarm/event exists). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.1.2
·
1 row entry
·
17 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapSysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapSysTable'
Allows for getting alarm map information.
The system alarm map type to reference.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapSysOutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.1 | ||||||
airFMSysAlarmMapSysAnyAlarmmandatory System alarm map setting for Any Alarm.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.2 | ||||||
airFMSysAlarmMapSystemOnmandatory System alarm map setting for System On.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.3 | ||||||
airFMSysAlarmMapSystemOfflinemandatory System alarm map setting for System Offline.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.4 | ||||||
airFMSysAlarmMapSysHighEnvTempmandatory System alarm map setting for High EnvironmentalTemperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.5 | ||||||
airFMSysAlarmMapSysLowEnvTempmandatory System alarm map setting for Low EnvironmentalTemperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.6 | ||||||
airFMSysAlarmMapSysHighEnvHummandatory System alarm map setting for High EnvironmentalHumidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.7 | ||||||
airFMSysAlarmMapSysLowEnvHummandatory System alarm map setting for Low EnvironmentalHumidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.8 | ||||||
airFMSysAlarmMapSysFireDetmandatory System alarm map setting for Fire Detected.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.9 | ||||||
airFMSysAlarmMapSysSmokeDetmandatory System alarm map setting for Smoke Detected.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.10 | ||||||
airFMSysAlarmMapSysEconIsolmandatory System alarm map setting for Econ Isolator.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.11 | ||||||
airFMSysAlarmMapSysSupplySensFailmandatory System alarm map setting for Supply Sensor Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.12 | ||||||
airFMSysAlarmMapSysReturnSensFailmandatory System alarm map setting for Return Sensor Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.13 | ||||||
airFMSysAlarmMapSysRemSensRemovedmandatory System alarm map setting for Remote Sensor Removed.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.14 | ||||||
airFMSysAlarmMapSysPrimSensFailmandatory System alarm map setting for Primary Sensor Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.15 | ||||||
airFMSysAlarmMapSysSecSensFailmandatory System alarm map setting for Secondary Sensor Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.16 | ||||||
airFMSysAlarmMapSysSecSensActivemandatory System alarm map setting for Secondary Sensor Active.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.17 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.2.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapMainModTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapMainModTable'
Allows for getting alarm map information.
The main module alarm map type to reference.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapMainModOutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.1 | ||||||
airFMSysAlarmMapMainModAnyAlarmmandatory Main Module alarm map setting for Any Alarm.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.2 | ||||||
airFMSysAlarmMapMainModMaintReqmandatory Main Module alarm map setting for Module MaintenanceRequired. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.3 | ||||||
airFMSysAlarmMapMainModCoolFailmandatory Main Module alarm map setting for Module CoolingFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.4 | ||||||
| Main Module alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.5 | ||||||
airFMSysAlarmMapMainModLowSupplyTempmandatory Main Module alarm map setting for Low SupplyTemperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.6 | ||||||
airFMSysAlarmMapMainModHumFailmandatory Main Module alarm map setting for Humidifier Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.7 | ||||||
airFMSysAlarmMapMainModHumReplCylmandatory Main Module alarm map setting for Humidifier ReplaceCylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.8 | ||||||
airFMSysAlarmMapMainModCondPumpFailmandatory Main Module alarm map setting for Condensate PumpFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.9 | ||||||
airFMSysAlarmMapMainModBlwrCntl1Failmandatory Main Module alarm map setting for Blower Controller 1Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.10 | ||||||
airFMSysAlarmMapMainModBlwrCntl2Failmandatory Main Module alarm map setting for Blower Controller 2Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.11 | ||||||
airFMSysAlarmMapMainModHighFltrDPmandatory Main Module alarm map setting for High FilterDifferential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.12 | ||||||
airFMSysAlarmMapMainModLowAirFlowmandatory Main Module alarm map setting for Low Air Flow.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.13 | ||||||
| Main Module alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.14 | ||||||
airFMSysAlarmMapMainModWaterDetectedmandatory Main Module alarm map setting for Water Detected.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.15 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.3.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapExpMod1Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapExpMod1Table'
Allows for getting alarm map information.
The expansion module 1 alarm map type to reference.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapExpMod1OutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.1 | ||||||
airFMSysAlarmMapExpMod1AnyAlarmmandatory Exp Module 1 alarm map setting for Any Alarm.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.2 | ||||||
airFMSysAlarmMapExpMod1MaintReqmandatory Exp Module 1 alarm map setting for Module MaintenanceRequired. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.3 | ||||||
airFMSysAlarmMapExpMod1CoolFailmandatory Exp Module 1 alarm map setting for Module CoolingFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.4 | ||||||
| Exp Module 1 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.5 | ||||||
airFMSysAlarmMapExpMod1LowSupplyTempmandatory Exp Module 1 alarm map setting for Low SupplyTemperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.6 | ||||||
airFMSysAlarmMapExpMod1HumFailmandatory Exp Module 1 alarm map setting for Humidifier Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.7 | ||||||
airFMSysAlarmMapExpMod1HumReplCylmandatory Exp Module 1 alarm map setting for Humidifier ReplaceCylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.8 | ||||||
airFMSysAlarmMapExpMod1CondPumpFailmandatory Exp Module 1 alarm map setting for Condensate PumpFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.9 | ||||||
airFMSysAlarmMapExpMod1BlwrCntl1Failmandatory Exp Module 1 alarm map setting for Blower Controller 1Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.10 | ||||||
airFMSysAlarmMapExpMod1BlwrCntl2Failmandatory Exp Module 1 alarm map setting for Blower Controller 2Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.11 | ||||||
airFMSysAlarmMapExpMod1HighFltrDPmandatory Exp Module 1 alarm map setting for High FilterDifferential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.12 | ||||||
airFMSysAlarmMapExpMod1LowAirFlowmandatory Exp Module 1 alarm map setting for Low Air Flow.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.13 | ||||||
| Exp Module 1 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.14 | ||||||
airFMSysAlarmMapExpMod1WaterDetectedmandatory Exp Module 1 alarm map setting for Water Detected.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.15 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.4.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapExpMod2Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapExpMod2Table'
Allows for getting alarm map information.
The expansion module 2 alarm map type to reference.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapExpMod2OutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.1 | ||||||
airFMSysAlarmMapExpMod2AnyAlarmmandatory Exp Module 2 alarm map setting for Any Alarm.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.2 | ||||||
airFMSysAlarmMapExpMod2MaintReqmandatory Exp Module 2 alarm map setting for Module MaintenanceRequired. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.3 | ||||||
airFMSysAlarmMapExpMod2CoolFailmandatory Exp Module 2 alarm map setting for Module CoolingFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.4 | ||||||
| Exp Module 2 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.5 | ||||||
airFMSysAlarmMapExpMod2LowSupplyTempmandatory Exp Module 2 alarm map setting for Low SupplyTemperature. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.6 | ||||||
airFMSysAlarmMapExpMod2HumFailmandatory Exp Module 2 alarm map setting for Humidifier Failure.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.7 | ||||||
airFMSysAlarmMapExpMod2HumReplCylmandatory Exp Module 2 alarm map setting for Humidifier ReplaceCylinder. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.8 | ||||||
airFMSysAlarmMapExpMod2CondPumpFailmandatory Exp Module 2 alarm map setting for Condensate PumpFailure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.9 | ||||||
airFMSysAlarmMapExpMod2BlwrCntl1Failmandatory Exp Module 2 alarm map setting for Blower Controller 1Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.10 | ||||||
airFMSysAlarmMapExpMod2BlwrCntl2Failmandatory Exp Module 2 alarm map setting for Blower Controller 2Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.11 | ||||||
airFMSysAlarmMapExpMod2HighFltrDPmandatory Exp Module 2 alarm map setting for High FilterDifferential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.12 | ||||||
airFMSysAlarmMapExpMod2LowAirFlowmandatory Exp Module 2 alarm map setting for Low Air Flow.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.13 | ||||||
| Exp Module 2 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.14 | ||||||
airFMSysAlarmMapExpMod2WaterDetectedmandatory Exp Module 2 alarm map setting for Water Detected.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.15 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.5.2
·
1 row entry
·
17 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapInputTable'
Allows for getting alarm map information.
The input contact alarm map type to reference.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapInputOutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.1 | ||||||
airFMSysAlarmMapInput1mandatory Input contact 1 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.2 | ||||||
airFMSysAlarmMapInput2mandatory Input contact 2 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.3 | ||||||
airFMSysAlarmMapInput3mandatory Input contact 3 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.4 | ||||||
airFMSysAlarmMapInput4mandatory Input contact 4 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.5 | ||||||
airFMSysAlarmMapInput5mandatory Input contact 5 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.6 | ||||||
airFMSysAlarmMapInput6mandatory Input contact 6 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.7 | ||||||
airFMSysAlarmMapInput7mandatory Input contact 7 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.8 | ||||||
airFMSysAlarmMapInput8mandatory Input contact 8 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.9 | ||||||
airFMSysAlarmMapInput9mandatory Input contact 9 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.10 | ||||||
airFMSysAlarmMapInput10mandatory Input contact 10 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.11 | ||||||
airFMSysAlarmMapInput11mandatory Input contact 11 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.12 | ||||||
airFMSysAlarmMapInput12mandatory Input contact 12 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.13 | ||||||
airFMSysAlarmMapInput13mandatory Input contact 13 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.14 | ||||||
airFMSysAlarmMapInput14mandatory Input contact 14 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.15 | ||||||
airFMSysAlarmMapInput15mandatory Input contact 15 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.16 | ||||||
airFMSysAlarmMapInput16mandatory Input contact 16 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.17 |
.1.3.6.1.4.1.318.1.1.13.1.4.12.6.2
·
1 row entry
·
17 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMSysAlarmMapOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMSysAlarmMapOutputTable'
Allows for getting alarm map information.
The input contact alarm map type to reference.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMSysAlarmMapOutputIndexmandatory The index of the output relay. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.1 | ||||||
airFMSysAlarmMapOutput1mandatory Output relay 1 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.2 | ||||||
airFMSysAlarmMapOutput2mandatory Output relay 2 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.3 | ||||||
airFMSysAlarmMapOutput3mandatory Output relay 3 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.4 | ||||||
airFMSysAlarmMapOutput4mandatory Output relay 4 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.5 | ||||||
airFMSysAlarmMapOutput5mandatory Output relay 5 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.6 | ||||||
airFMSysAlarmMapOutput6mandatory Output relay 6 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.7 | ||||||
airFMSysAlarmMapOutput7mandatory Output relay 7 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.8 | ||||||
airFMSysAlarmMapOutput8mandatory Output relay 8 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.9 | ||||||
airFMSysAlarmMapOutput9mandatory Output relay 9 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.10 | ||||||
airFMSysAlarmMapOutput10mandatory Output relay 10 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.11 | ||||||
airFMSysAlarmMapOutput11mandatory Output relay 11 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.12 | ||||||
airFMSysAlarmMapOutput12mandatory Output relay 12 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.13 | ||||||
airFMSysAlarmMapOutput13mandatory Output relay 13 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.14 | ||||||
airFMSysAlarmMapOutput14mandatory Output relay 14 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.15 | ||||||
airFMSysAlarmMapOutput15mandatory Output relay 15 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.16 | ||||||
airFMSysAlarmMapOutput16mandatory Output relay 16 alarm map setting.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.17 |
.1.3.6.1.4.1.318.1.1.13.1.5.1.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModIdentTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID |
|---|---|---|
airFMModIdentModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.1 |
airFMModModelNumbermandatory Model number of the Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.2 |
airFMModSerialNumbermandatory Unique identification number for this Module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.3 |
airFMModManufactureDatemandatory Date the Module was manufactured. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.4 |
airFMModFirmwareRevmandatory Revision number of the firmware installed on thisModule. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.5 |
airFMModHardwareRevmandatory Revision number of the hardware installed on thisModule. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.6 |
.1.3.6.1.4.1.318.1.1.13.1.5.2.2
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModStatusTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID |
|---|---|---|
airFMModStatusModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.1 |
airFMModSupplyTempCmandatory The temperature measured at the supply sensor.Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.2 |
airFMModSupplyTempFmandatory The temperature measured at the supply sensor.Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.3 |
airFMModSupplyHummandatory The humidity measured at the supply sensor.Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.4 |
airFMModReturnTempCmandatory The temperature measured at the return sensor.Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.5 |
airFMModReturnTempFmandatory The temperature measured at the return sensor.Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.6 |
airFMModReturnHummandatory The humidity measured at the return sensor.Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.7 |
airFMModFilterDiffPresPamandatory The difference in pressure on either side of the airfilters. A high differential pressure indicates a clogged filter. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device d… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.8 |
airFMModFilterDiffPresInWCmandatory The difference in pressure on either side of the airfilters. A high differential pressure indicates a clogged filter. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.9 |
airFMModCoilDiffPresPamandatory The difference in pressure on either side of thecooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.10 |
airFMModCoilDiffPresInWCmandatory The difference in pressure on either side of thecooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does not apply to this device due to its co… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.11 |
.1.3.6.1.4.1.318.1.1.13.1.5.3.2
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModPropTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModPropTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
airFMModPropModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.1 | ||||||||||||||||
airFMModOutputCapacitymandatory The cooling capacity (in Kilowatts) of the displayedModule. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.2 | ||||||||||||||||
airFMModCapacityCtrlmandatory The method used to load and unload the compressors.Tandem compressor Modules use two stages (one compressor each). Single compressor Modules use hot gas bypass. A value of notApplicable indicates that this OID does not… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.3 | ||||||||||||||||
airFMModHeaterTypemandatory The type of reheating device installed in this Module.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.4 | ||||||||||||||||
airFMModElectricHeaterTypemandatory The type/capacity of the electric heater, if installed.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.5 | ||||||||||||||||
airFMModHumidifierTypemandatory The type of equipment installed in the Module to runthe humidification mode. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.6 | ||||||||||||||||
airFMModBlwrFreqSettingmandatory Frequency of the blower in tenths of hertz.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.7 | ||||||||||||||||
airFMModNomCoilDiffPresPamandatory The difference in pressure on either side of thecooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.8 | ||||||||||||||||
airFMModNomCoilDiffPresInWCmandatory The difference in pressure on either side of thecooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicates that this OID does not apply to this device due to its co… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.9 | ||||||||||||||||
airFMModCondPumpmandatory Indicates the presence of a condensate pump in theModules of this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.10 | ||||||||||||||||
airFMModFireDetectormandatory Indicates the presence of a fire detector for eachof the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.11 | ||||||||||||||||
airFMModSmokeDetectormandatory Indicates the presence of a smoke detector for eachof the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.12 | ||||||||||||||||
airFMModWaterDetectormandatory Indicates the presence of a water leak detector foreach of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.13 |
.1.3.6.1.4.1.318.1.1.13.1.5.4.2
·
1 row entry
·
9 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModCoolTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModCoolTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMModCoolModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.1 | ||||||
airFMModComp1mandatory The status of compressor 1 of the tandem compressorunit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.2 | ||||||
airFMModComp2mandatory The status of compressor 2 of the tandem compressorunit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.3 | ||||||
airFMModSuctPresKPamandatory The refrigerant pressure measured at the suctioninlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.4 | ||||||
airFMModSuctPresPSImandatory The refrigerant pressure measured at the suctioninlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.5 | ||||||
airFMModDischPresKPamandatory The refrigerant pressure measured at the dischargeoutlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.6 | ||||||
airFMModDischPresPSImandatory The refrigerant pressure measured at the dischargeoutlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.7 | ||||||
airFMModCondFluidVlvPosmandatory The position of the condenser fluid valve. The valveregulates the flow of liquid coolant into the heat exchanger (condenser). 100% indicates the valve is completely open, and 0% indicates that the valve is closed. Mea… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.8 | ||||||
airFMModCoilFluidVlvPosmandatory The position of the coil fluid valve. The valveregulates the flow of liquid coolant in the fluid cooling coil (MultiCool, Economizer, or Chilled Water). 100% indicates the valve is completely open, and 0% indicates tha… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.9 |
.1.3.6.1.4.1.318.1.1.13.1.5.5.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModHumTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModHumTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
airFMModHumModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.1 | ||||||||
airFMModHumidifiermandatory The type of equipment installed in the Module to runthe humidification mode. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.2 | ||||||||
airFMModElectrodeCurrentmandatory The current drawn by the electrodes of the steamcylinder humidifier. Measured in tenths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.3 | ||||||||
airFMModHumActualOutputmandatory The humidification output of an individual Module.Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.4 | ||||||||
airFMModWaterConductivitymandatory The conductivity of the water in the humidifiercylinder. Measured in microSiemens per centimeter. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.5 | ||||||||
airFMModHotWaterVlvPosmandatory The position of the hot water valve. 100% indicatesthe valve is completely open, and 0% indicates that the valve is closed. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this de… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.6 | ||||||||
airFMModStmElectHumModemandatory Set the humidifier function mode.Off: Remove power from electrodes. Auto: Humidifier controlled by Module controller. Drain: Remove power from electrodes and drain the cylinder. A value of notApplicable … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7 |
.1.3.6.1.4.1.318.1.1.13.1.5.6.2
·
1 row entry
·
25 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModBlwr1Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModBlwr1Table'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
airFMModBlwr1ModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.1 | ||||||||
airFMModBlwr1CtrlTypemandatory The type of blower controller.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.2 | ||||||||
airFMModBlwr1CmdFreqmandatory The requested operating frequency for the blower.Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.3 | ||||||||
airFMModBlwr1ActFreqmandatory The frequency at which the blower controller isoperating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.4 | ||||||||
airFMModBlwr1Polesmandatory The number of poles of the blower motor that theblower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.5 | ||||||||
airFMModBlwr1RatedHorsePowermandatory The power rating of the blower motor. Measured inhundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.6 | ||||||||
airFMModBlwr1RatedCurrentmandatory The current rating of the blower motor. Measured inhundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.7 | ||||||||
airFMModBlwr1ActTorqmandatory The actual torque of the blower motor. Measured inhundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.8 | ||||||||
airFMModBlwr1Currentmandatory The percent of rated current drawn by the blowermotor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.9 | ||||||||
airFMModBlwr1Vltmandatory The voltage supplied to the blower motor. Measuredin tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.10 | ||||||||
airFMModBlwr1DCLinkVltmandatory The voltage of the blower controller's DC bus.Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.11 | ||||||||
airFMModBlwr1AccTimemandatory The time to accelerate the blower to the specifiedfrequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.12 | ||||||||
airFMModBlwr1DecTimemandatory The time to decelerate the blower frequency to zero.Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.13 | ||||||||
airFMModBlwr1CapLifemandatory The remaining life of the main circuit capacitor.Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.14 | ||||||||
airFMModBlwr1CtrlCoolFanLifemandatory The total operation time of the blower controllercooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.15 | ||||||||
airFMModBlwr1ElOvModemandatory Enables or disables the electronic overload relay.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.16 | ||||||||
airFMModBlwr1ElOvSettingmandatory The electronic overload relay is activated when thecurrent exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.17 | ||||||||
airFMModBlwr1ElOvTimeConstmandatory The delay between the current exceeding the overloadthreshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -2147483648 indicates that this OID does not apply to this d… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18 | ||||||||
airFMModBlwr1FanPowermandatory The actual power of the blower motor. Measured intenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.19 | ||||||||
airFMModBlwr1HeatsinkTempCmandatory The temperature of the heatsink on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.20 | ||||||||
airFMModBlwr1HeatsinkTempFmandatory The temperature of the heatsink on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.21 | ||||||||
airFMModBlwr1ChokeTempCmandatory The temperature of the choke on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.22 | ||||||||
airFMModBlwr1ChokeTempFmandatory The temperature of the choke on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.23 | ||||||||
airFMModBlwr1InverterTempCmandatory The temperature of the inverter on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.24 | ||||||||
airFMModBlwr1InverterTempFmandatory The temperature of the inverter on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.25 |
.1.3.6.1.4.1.318.1.1.13.1.5.7.2
·
1 row entry
·
25 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModBlwr2Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModBlwr2Table'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
airFMModBlwr2ModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.1 | ||||||||
airFMModBlwr2CtrlTypemandatory The type of blower controller.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.2 | ||||||||
airFMModBlwr2CmdFreqmandatory The requested operating frequency for the blower.Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.3 | ||||||||
airFMModBlwr2ActFreqmandatory The frequency at which the blower controller isoperating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.4 | ||||||||
airFMModBlwr2Polesmandatory The number of poles of the blower motor that theblower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.5 | ||||||||
airFMModBlwr2RatedHorsePowermandatory The power rating of the blower motor. Measured inhundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.6 | ||||||||
airFMModBlwr2RatedCurrentmandatory The current rating of the blower motor. Measured inhundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.7 | ||||||||
airFMModBlwr2ActTorqmandatory The actual torque of the blower motor. Measured inhundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.8 | ||||||||
airFMModBlwr2Currentmandatory The percent of rated current drawn by the blowermotor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.9 | ||||||||
airFMModBlwr2Vltmandatory The voltage supplied to the blower motor. Measuredin tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.10 | ||||||||
airFMModBlwr2DCLinkVltmandatory The voltage of the blower controller's DC bus.Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.11 | ||||||||
airFMModBlwr2AccTimemandatory The time to accelerate the blower to the specifiedfrequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.12 | ||||||||
airFMModBlwr2DecTimemandatory The time to decelerate the blower frequency to zero.Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.13 | ||||||||
airFMModBlwr2CapLifemandatory The remaining life of the main circuit capacitor.Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.14 | ||||||||
airFMModBlwr2CtrlCoolFanLifemandatory The total operation time of the blower controllercooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.15 | ||||||||
airFMModBlwr2ElOvModemandatory Enables or disables the electronic overload relay.A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.16 | ||||||||
airFMModBlwr2ElOvSettingmandatory The electronic overload relay is activated when thecurrent exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.17 | ||||||||
airFMModBlwr2ElOvTimeConstmandatory The delay between the current exceeding the overloadthreshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -2147483648 indicates that this OID does not apply to this d… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.18 | ||||||||
airFMModBlwr2FanPowermandatory The actual power of the blower motor. Measured intenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.19 | ||||||||
airFMModBlwr2HeatsinkTempCmandatory The temperature of the heatsink on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.20 | ||||||||
airFMModBlwr2HeatsinkTempFmandatory The temperature of the heatsink on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.21 | ||||||||
airFMModBlwr2ChokeTempCmandatory The temperature of the choke on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.22 | ||||||||
airFMModBlwr2ChokeTempFmandatory The temperature of the choke on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.23 | ||||||||
airFMModBlwr2InverterTempCmandatory The temperature of the inverter on the blowercontroller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.24 | ||||||||
airFMModBlwr2InverterTempFmandatory The temperature of the inverter on the blowercontroller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.25 |
.1.3.6.1.4.1.318.1.1.13.1.5.8.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModRHTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModRHTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMModRHModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.1 | ||||||
airFMModRHComp1mandatory Compressor 1 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.2 | ||||||
airFMModRHComp2mandatory Compressor 2 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.3 | ||||||
airFMModRHHeatermandatory Heater run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.4 | ||||||
airFMModRHHummandatory Humidifier run hoursA value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.5 | ||||||
airFMModRHBlwr1mandatory Blower 1 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.6 | ||||||
airFMModRHBlwr2mandatory Blower 2 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.7 | ||||||
airFMModRHBlwrCtrl1mandatory Blower Controller 1 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.8 | ||||||
airFMModRHBlwrCtrl2mandatory Blower Controller 2 run hours.A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.9 | ||||||
airFMModRHComp1Resetmandatory Reset the compressor 1 run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.10 | ||||||
airFMModRHComp2Resetmandatory Reset the compressor 2 run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.11 | ||||||
airFMModRHHeaterResetmandatory Reset the heater run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.12 | ||||||
airFMModRHHumResetmandatory Reset the humidifier run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.13 | ||||||
airFMModRHBlwr1Resetmandatory Reset the blower 1 run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.14 | ||||||
airFMModRHBlwr2Resetmandatory Reset the blower 2 run hours.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.15 |
.1.3.6.1.4.1.318.1.1.13.1.5.10.2
·
1 row entry
·
9 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMModServIntResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMModServIntResetTable'
Allows for getting information from each module in the system.
The module to get information from.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airFMModServIntResetModuleIndexmandatory The index of the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.1 | ||||||
airFMModServIntComp1Resetmandatory Reset the compressor 1 service interval maintenancealarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its con… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.2 | ||||||
airFMModServIntComp2Resetmandatory Reset the compressor 2 service interval maintenancealarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its con… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.3 | ||||||
airFMModServIntHeaterResetmandatory Reset the heater service interval maintenance alarm.Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configura… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.4 | ||||||
airFMModServIntHumResetmandatory Reset the humidifier service interval maintenancealarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its confi… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.5 | ||||||
airFMModServIntBlwr1Resetmandatory Reset the blower 1 service interval maintenancealarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configu… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.6 | ||||||
airFMModServIntBlwr2Resetmandatory Reset the blower 2 service interval maintenancealarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to its configu… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.7 | ||||||
airFMModServIntBlwrCtrl1Resetmandatory Reset the blower controller 1 service intervalmaintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.8 | ||||||
airFMModServIntBlwrCtrl2Resetmandatory Reset the blower controller 2 service intervalmaintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply to this device due to … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.9 |
.1.3.6.1.4.1.318.1.1.13.1.6.4
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airFMAlarmConditionsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airFMAlarmConditionsTable'
Table of active alarm conditions for the device.
Alarm condition specification
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
airFMAlarmConditionsIndexmandatory Alarm condition index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.6.4.1.1 | ||||||||||
airFMAlarmSeveritymandatory Severity of the alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.6.4.1.2 | ||||||||||
airFMAlarmTypemandatory Type of alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.1.6.4.1.3 | ||||||||||
airFMEventCodemandatory APC event code for the alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.1.6.4.1.4 | ||||||||||
airFMAlarmDatemandatory Date the alarm was recorded. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.6.4.1.5 | ||||||||||
airFMAlarmTimemandatory Time the alarm was recorded. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.1.6.4.1.6 | ||||||||||
airFMAlarmDescriptionmandatory Description of the alarm. | OctetString Constraints: range: 0-64 | .1.3.6.1.4.1.318.1.1.13.1.6.4.1.7 |
.1.3.6.1.4.1.318.1.1.13.3.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRAlarmConditionsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRAlarmConditionsTable'
Table of active alarm conditions for the device.
Alarm condition specification
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRAlarmConditionsIndexmandatory Alarm condition index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.3.1.2.1.1 |
airIREventCodemandatory Code for the alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.3.1.2.1.2 |
airIRAlarmDescriptionmandatory Description of the alarm. | OctetString Constraints: range: 0-64 | .1.3.6.1.4.1.318.1.1.13.3.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.13.4.3.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG2AlarmsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG2AlarmsTable'
Table of active alarms for the device.
Alarms specification
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG2AlarmsIndexmandatory Alarm index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.3.2.1.1 |
airIRG2AlarmsEventCodemandatory Code for the alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.3.2.1.2 |
airIRG2AlarmsDescriptionmandatory Description of the alarm. | OctetString Constraints: range: 0-64 | .1.3.6.1.4.1.318.1.1.13.4.3.2.1.3 |
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.5
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG2RDT2RunHoursFanPSTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG2RDT2RunHoursFanPSTable'
Allows for getting run hour information from each power supply.
The run hours fan power supply table entry.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
airIRG2RDT2RunHoursFanPSIndexmandatory Index of run hours fan power supply table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.1 | ||||||||
airIRG2RDT2RunHoursFanPSHoursmandatory Fan power supply run time in hours. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.2 | ||||||||
airIRG2RDT2RunHoursFanPSPositionmandatory Position of fan power supply within the unit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.3 |
.1.3.6.1.4.1.318.1.1.13.4.5.2.2.7
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG2RDT2RunHoursEvapFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG2RDT2RunHoursEvapFanTable'
Allows for getting information from each evaporator fan run hour in the system.
Allows for getting information from each evaporator fan run
hour in the system.
hour in the system.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG2RDT2RunHoursEvapFanIndexmandatory Index of run hours evaporator fan table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.1 |
airIRG2RDT2RunHoursEvapFanHoursmandatory Evaporator fan run time in hours. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.2 |
.1.3.6.1.4.1.318.1.1.13.5.2.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRmAlarmsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRmAlarmsTable'
Table of active alarms for the device.
Alarms specification
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRmAlarmsIndexmandatory Alarm index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.5.2.2.1.1 |
airIRmAlarmsEventCodemandatory Code for the alarm. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.5.2.2.1.2 |
airIRmAlarmsDescriptionmandatory Description of the alarm. | OctetString Constraints: range: 0-64 | .1.3.6.1.4.1.318.1.1.13.5.2.2.1.3 |
.1.3.6.1.4.1.318.1.1.13.6.1.2
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3IdentTable'
Allows to get ident information of current RDU and its assigned CM's.
The ident table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3IdentIndexmandatory Index of ident table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.1 |
airIRG3IdentNamemandatory A character string identifying the unit name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.2 |
airIRG3IdentLocationmandatory A character string identifying the unit location. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.3 |
airIRG3IdentModelNumbermandatory A character string identifying the unit model number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.4 |
airIRG3IdentSerialNumbermandatory A character string identifying the unit serial number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.5 |
airIRG3IdentFirmwareRevisionmandatory A character string identifying the unit firmware version. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.6 |
airIRG3IdentHardwareRevisionmandatory A character string identifying the unit controller hardware revision. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.7 |
airIRG3IdentManufactureDatemandatory A character string identifying the unit manufacture date. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.8 |
airIRG3IdentRDUSysOIDmandatory This OID contains an OID path to the RDU data. | ObjectIdentifier | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.9 |
airIRG3IdentCMSysOIDmandatory This OID contains an OID path to the cooling module data. | ObjectIdentifier | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.10 |
airIRG3IdentGroupSysOIDmandatory This OID contains an OID path to the group data. | ObjectIdentifier | .1.3.6.1.4.1.318.1.1.13.6.1.2.1.11 |
.1.3.6.1.4.1.318.1.1.13.6.2.2
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3GroupStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3GroupStatusTable'
Allows to get group status information.
The group staus table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3GroupStatusIndexmandatory Index of group status table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.1 |
airIRG3GroupStatusCoolOutputmandatory The group cooling output in tenths of kilowatts (kW).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.2 |
airIRG3GroupStatusCoolDemandmandatory The group cooling demand in tenths of kilowatts (kW).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.3 |
airIRG3GroupStatusAirFlowUSmandatory The group air flow in cubic feet per minute (CFM).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.4 |
airIRG3GroupStatusAirFlowMetricmandatory The group air flow in liters per second (L/s).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.5 |
airIRG3GroupStatusMaxRackInletTempUSmandatory The group maximum rack inlet temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.6 |
| The group maximum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.7 |
airIRG3GroupStatusMinRackInletTempUSmandatory The group minimum rack inlet temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.8 |
| The group minimum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.9 |
airIRG3GroupStatusMaxReturnAirTempUSmandatory The group maximum return air temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.10 |
| The group maximum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.11 |
airIRG3GroupStatusMinReturnAirTempUSmandatory The group minimum return air temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.12 |
| The group minimum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.13 |
airIRG3GroupStatusAvgSupplyTempUSmandatory The group average supply air temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.14 |
| The group average supply air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.15 |
airIRG3GroupStatusAvgReturnTempUSmandatory The group average return air temperature in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.16 |
| The group average return air temperature in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.17 |
airIRG3GroupStatusAvgFanSpeedmandatory The group average fan speed in revolutions per minute (RPM).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.18 |
airIRG3GroupStatusAvgAirFlowUSmandatory The group average air flow in cubic feet per minute (CFM).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.19 |
airIRG3GroupStatusAvgAirFlowMetricmandatory The group average air flow in liters per second (L/s).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.20 |
airIRG3GroupStatusTotalAirFlowUSmandatory The group total air flow in cubic feet per minute (CFM).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.21 |
airIRG3GroupStatusTotalAirFlowMetricmandatory The group total air flow in liters per second (L/s).Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.2.1.22 |
.1.3.6.1.4.1.318.1.1.13.6.2.3
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3GroupSetpointsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3GroupSetpointsTable'
Allows to access the group setpoints.
The group setpoints table entry.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
airIRG3GroupSetpointsIndexmandatory Index of group setpoints table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.1 | ||||||||||
airIRG3GroupSetpointsCoolSetpointUSmandatory Group cooling setpoint in tenths ofdegrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.2 | ||||||||||
| Group cooling setpoint in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.3 | ||||||||||
airIRG3GroupSetpointsCoolDeadbandUSmandatory Group cooling deadband in tenths ofdegrees Fahrenheit. Returns (-1) if not supported. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.4 | ||||||||||
| Group cooling deadband in tenths of degrees Celsius. Returns (-1) if not supported. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.5 | ||||||||||
| The group preferred fan speed setting. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.3.1.6 | ||||||||||
| Group supply air setpoint in tenths of degrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.7 | ||||||||||
| Group supply air setpoint in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.8 | ||||||||||
airIRG3GroupSetpointsAirFlowControlmandatory The group air flow control. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.3.1.9 | ||||||||||
airIRG3GroupSetpointsLightingOnTimemandatory The group lighting on time in minutes. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.3.1.10 |
.1.3.6.1.4.1.318.1.1.13.6.2.4
·
1 row entry
·
12 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3GroupConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3GroupConfigTable'
Allows to access group configuration table.
The group config table entry.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
airIRG3GroupConfigIndexmandatory Index of group config table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.1 | ||||||||
| The number of cooling units. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.2 | ||||||||
airIRG3GroupConfigConfigurationTypemandatory The group configuration type.The spot configuration type is not supported. Returns (-1) if not supported. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.3 | ||||||||
| The group capacity control. Returns (-1) if not supported. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.4 | ||||||||
airIRG3GroupConfigFanSpeedControlmandatory The group fan speed control. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.5 | ||||||||
airIRG3GroupConfigCoolGainPmandatory The gain component of the PID in hundredths. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.6 | ||||||||
airIRG3GroupConfigCoolResetRateImandatory The integral component of the PID in hundredths. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.7 | ||||||||
airIRG3GroupConfigCoolDerivativeDmandatory The derivative component of the PID in hundredths. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.8 | ||||||||
airIRG3GroupConfigCoolPIDResetmandatory Will reset the PID coefficients back to the factory defaults.Readback is not supported, returns -1. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.9 | ||||||||
| The number of backup units. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.2.4.1.10 | ||||||||
| Enable or disable runtime balancing feature. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.11 | ||||||||
airIRG3GroupConfigLoadAssistEnablemandatory Enable or disable load assist feature. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.2.4.1.12 |
.1.3.6.1.4.1.318.1.1.13.6.3.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3AlarmsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3AlarmsTable'
Table of active alarms for the device.
Alarms specification
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3AlarmsIndexmandatory Alarm index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.3.2.1.1 |
airIRG3AlarmsEventCodemandatory Event Code for the alarm. Returns (-1) if not supported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.3.2.1.2 |
airIRG3AlarmsDescriptionmandatory Description of the alarm. Returns (-1) if not supported. | OctetString Constraints: range: 0-64 | .1.3.6.1.4.1.318.1.1.13.6.3.2.1.3 |
.1.3.6.1.4.1.318.1.1.13.6.4.2
·
1 row entry
·
43 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDUStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDUStatusTable'
Allows to access RDU status table.
The RDU status table entry.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
airIRG3RDUStatusDeviceIndexmandatory Index of RDU status table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.1 | ||||||||||
airIRG3RDUIDmandatory The current RDU ID (1 to F).Configured RDU only shall display ID, else return -1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.2 | ||||||||||
airIRG3RDUStatusOnReadyStandbymandatory The RDU current status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.3 | ||||||||||
airIRG3RDUStatusOperatingModemandatory The RDU actual operating mode. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.4 | ||||||||||
airIRG3RDUStatusLeadPumpmandatory The RDU lead pump. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.5 | ||||||||||
airIRG3RDUStatusStartupDelaymandatory The RDU start up delay in seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.6 | ||||||||||
| The RDU pump change over interval in days. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.7 | ||||||||||
airIRG3RDUStatusStopOnLeakDetectmandatory The RDU status of stop on leak detect. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.8 | ||||||||||
airIRG3RDUStatusPowerSourcemandatory The RDU power source status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.9 | ||||||||||
airIRG3RDUStatusTotalRDUOutputPowermandatory The RDU output power in tenths of kilowatts (kW). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.10 | ||||||||||
airIRG3RDUStatusInletWaterTempUSmandatory The RDU inlet water temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.11 | ||||||||||
airIRG3RDUStatusInletWaterTempMetricmandatory The RDU inlet water temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.12 | ||||||||||
airIRG3RDUStatusOutletWaterTempUSmandatory The RDU outlet water temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.13 | ||||||||||
| The RDU outlet water temperature in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.14 | ||||||||||
| The RDU condenser saturation temperature in tenths of degrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.15 | ||||||||||
| The RDU condenser saturation temperature in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.16 | ||||||||||
airIRG3RDUStatusDewPointTempUSmandatory The RDU dew point temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.17 | ||||||||||
airIRG3RDUStatusDewPointTempMetricmandatory The RDU dew point temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.18 | ||||||||||
airIRG3RDUStatusPumpOutletTempUSmandatory The RDU pump outlet temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.19 | ||||||||||
airIRG3RDUStatusPumpOutletTempMetricmandatory The RDU pump outlet temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.20 | ||||||||||
| The RDU sub cooler outlet temperature in tenths of degrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.21 | ||||||||||
| The RDU sub cooler outlet temperature in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.22 | ||||||||||
| The RDU condenser outlet temperature in tenths of degrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.23 | ||||||||||
| The RDU condenser outlet temperature in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.24 | ||||||||||
airIRG3RDUStatusCondenserInletTempUSmandatory The RDU condenser inlet temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.25 | ||||||||||
| The RDU condenser inlet temperature in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.26 | ||||||||||
| The RDU condenser outlet pressure in pounds per square inch (PSI). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.27 | ||||||||||
| The RDU condenser outlet pressure in kiloPascals (KPa). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.28 | ||||||||||
airIRG3RDUStatusPump1HeadPressureUSmandatory The RDU Pump 1 head pressure in pounds per square inch (PSI). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.29 | ||||||||||
| The RDU Pump 1 head pressure in kiloPascals (KPa). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.30 | ||||||||||
airIRG3RDUStatusPump2HeadPressureUSmandatory The RDU Pump 2 head pressure in pounds per square inch (PSI). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.31 | ||||||||||
| The RDU Pump 2 head pressure in kiloPascals (KPa). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.32 | ||||||||||
airIRG3RDUStatusPump1Speedmandatory The RDU Pump 1 speed in revolutions per minute (RPM). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.33 | ||||||||||
airIRG3RDUStatusPump2Speedmandatory The RDU Pump 2 speed in revolutions per minute (RPM). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.34 | ||||||||||
airIRG3RDUStatusCWValvePositionmandatory The RDU CW Valve position in % open | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.35 | ||||||||||
airIRG3RDUStatusReceiverLiquidLevelmandatory The RDU receiver liquid level in % Full | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.36 | ||||||||||
| The RDU DC Power Supply 1 Current in Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.37 | ||||||||||
| The RDU DC Power Supply 2 Current in Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.38 | ||||||||||
| The RDU Total DC Power Supply Current in Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.39 | ||||||||||
airIRG3RDUStatusInputStatemandatory The RDU Input state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.40 | ||||||||||
airIRG3RDUStatusOutputStatemandatory The RDU Output state | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.41 | ||||||||||
airIRG3RDUStatusByPassValvePositionmandatory The RDU By Pass Valve position in % open | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.2.1.42 | ||||||||||
| The RDU refrigerant leak detector status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.2.1.43 |
.1.3.6.1.4.1.318.1.1.13.6.4.3
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDURunHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDURunHoursTable'
Allows to access RDU run hours table.
The RDU run hours table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3RDURunHoursDeviceIndexmandatory Index of RDU run hours table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.1 |
airIRG3RDURunHoursRDUIDmandatory The current RDU ID (1 to F).Configured RDU only shall display ID, else return -1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.2 |
airIRG3RDURunHoursPump1mandatory The RDU run hours of Pump 1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.3 |
airIRG3RDURunHoursPump2mandatory The RDU run hours of Pump 2. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.4 |
airIRG3RDURunHoursPowerSupply1mandatory The RDU run hours of power supply 1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.5 |
airIRG3RDURunHoursPowerSupply2mandatory The RDU run hours of power supply 2. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.3.1.6 |
.1.3.6.1.4.1.318.1.1.13.6.4.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDUServiceIntervalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDUServiceIntervalsTable'
Allows to access RDU service intervals table.
The service interval table entry.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| Index of service interval table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.4.1.1 | ||||
airIRG3RDUServiceIntervalsRDUIDmandatory The current RDU ID (1 to F).Configured RDU only shall display ID, else return -1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.4.4.1.2 | ||||
| The RDU service interval for air filter in hours. Returns -1 if not supported. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.4.1.3 | ||||
| The RDU service interval air filter alarm status. Returns -1 if not supported. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.4.1.4 |
.1.3.6.1.4.1.318.1.1.13.6.4.5
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDUThresholdsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDUThresholdsTable'
Allows to access RDU thresholds table.
The RDU thresholds table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3RDUThresholdsDeviceIndexmandatory Index of RDU thresholds table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.5.1.1 |
airIRG3RDUThresholdsRDUIDmandatory The current RDU ID (1 to F).Configured RDU only shall display ID, else return -1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.4.5.1.2 |
| The RDU threshold for entering fluid temperature in tenths of degrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.5.1.3 |
| The RDU threshold for entering fluid temperature in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.5.1.4 |
.1.3.6.1.4.1.318.1.1.13.6.4.6
·
1 row entry
·
1 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDUSetpointsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDUSetpointsTable'
Allows to access RDU set points table.
The RDU set points table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3RDUSetpointsDeviceIndexmandatory Index of RDU set points table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.6.1.1 |
.1.3.6.1.4.1.318.1.1.13.6.4.7
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3RDUConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3RDUConfigTable'
Allows to access RDU configuration table.
The RDU configuration table entry.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airIRG3RDUConfigDeviceIndexmandatory Index of RDU configuration table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.7.1.1 | ||||||
airIRG3RDUConfigRDUIDmandatory The current RDU ID (1 to F).Configured RDU only shall display ID, else return -1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.4.7.1.2 | ||||||
airIRG3RDUConfigStopOnLeakDetectmandatory The RDU stop on leak detect set. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.3 | ||||||
airIRG3RDUConfigStartupDelaymandatory The RDU start up delay in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.7.1.4 | ||||||
| The RDU pump change over interval in days. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.4.7.1.5 | ||||||
airIRG3RDUConfigPowerSourcemandatory The RDU power source. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.6 | ||||||
airIRG3RDUConfigOutputSourcemandatory The RDU output source. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.7 | ||||||
airIRG3RDUConfigInputNormalStatemandatory The RDU Input Normal State. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.8 | ||||||
airIRG3RDUConfigOutputNormalStatemandatory The RDU Output Normal State. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.9 | ||||||
airIRG3RDUConfigByPassValveEnabledmandatory The RDU By Pass Valve Enabled State. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.10 | ||||||
| The RDU Refrigerant Leak Detector Enabled State. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.11 | ||||||
| This parameter allows to calibrate the RDU Refrigerant Leak Detector and is write only. The read returns -1. Only 'yes' is supported. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.12 | ||||||
airIRG3RDUConfigOnReadyStandbymandatory This parameter allows to configure RDU on/standby parameter.Ready is currently not supported. If unsupported returns -1. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.4.7.1.13 |
.1.3.6.1.4.1.318.1.1.13.6.5.2
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMStatusTable'
Allows to access CM status table.
The CM status table entry.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
airIRG3CMStatusDeviceIndexmandatory Index of CM status table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.1 | ||||||
airIRG3CMStatusCMIDmandatory The CM ID (RDU Number - Group Number - CM Unit Number). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.2 | ||||||
airIRG3CMStatusOperatingModemandatory The current operating mode of the CM. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.2.1.3 | ||||||
airIRG3CMStatusUnitTypemandatory The current CM unit type. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.2.1.4 | ||||||
airIRG3CMStatusRackInletTempUSmandatory The CM rack inlet temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.5 | ||||||
airIRG3CMStatusRackInletTempMetricmandatory The CM rack inlet temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.6 | ||||||
airIRG3CMStatusReturnAirTempUSmandatory The CM return air temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.7 | ||||||
airIRG3CMStatusReturnAirTempMetricmandatory The CM return air temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.8 | ||||||
airIRG3CMStatusLiquidTempUSmandatory The CM liquid temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.9 | ||||||
airIRG3CMStatusLiquidTempMetricmandatory The CM liquid temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.10 | ||||||
airIRG3CMStatusVaporTempUSmandatory The CM vapor temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.11 | ||||||
airIRG3CMStatusVaporTempMetricmandatory The CM vapor temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.12 | ||||||
airIRG3CMStatusEvaporatorTempUSmandatory The CM saturation temperature in tenths ofdegrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.13 | ||||||
airIRG3CMStatusEvaporatorTempMetricmandatory The CM saturation temperature in tenths ofdegrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.14 | ||||||
airIRG3CMStatusLiquidInletPressureUSmandatory The CM Liquid Inlet pressure in pounds per square inch (PSI). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.15 | ||||||
| The CM Liquid Inlet pressure in kiloPascals (kPa). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.16 | ||||||
airIRG3CMStatusVaporOutletPressureUSmandatory The CM Vapor Outlet pressure in pounds per square inch (PSI). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.17 | ||||||
| The CM Vapor Outlet pressure in kiloPascals (kPa). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.18 | ||||||
| The CM expansion valve position in % open | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.19 | ||||||
airIRG3CMStatusEPRValvePositionmandatory The CM Evaporator Pressure Regulator Valve Positionin tenths of percent open | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.20 | ||||||
| The status of the on/off control on the CM local display. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.2.1.21 | ||||||
airIRG3CMStatusAverageFanSpeedmandatory The CM Average Fan Speed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.2.1.22 |
.1.3.6.1.4.1.318.1.1.13.6.5.3
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMRunHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMRunHoursTable'
Allows to access CM run hours table.
The CM run hours table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3CMRunHoursDeviceIndexmandatory Index of CM run hours table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.1 |
airIRG3CMRunHoursCMIDmandatory The CM ID (RDU Number - Group Number - CM Unit Number). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.2 |
airIRG3CMRunHoursFan1mandatory The CM run hours for Fan1.Returns (-1) if not appilcable. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.3 |
airIRG3CMRunHoursFan2mandatory The CM run hours for Fan2.Returns (-1) if not appilcable. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.4 |
airIRG3CMRunHoursFan3mandatory The CM run hours for Fan3.Returns (-1) if not appilcable. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.5 |
airIRG3CMRunHoursFan4mandatory The CM run hours for Fan4.Returns (-1) if not appilcable. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.6 |
airIRG3CMRunHoursFan5mandatory The CM run hours for Fan5.Returns (-1) if not appilcable. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.7 |
airIRG3CMRunHoursAirFiltermandatory The CM run hours for air filter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.3.1.8 |
.1.3.6.1.4.1.318.1.1.13.6.5.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMServiceIntervalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMServiceIntervalsTable'
Allows to access CM service intervals table.
The CM service interval table entry.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
airIRG3CMServiceIntervalsDeviceIndexmandatory Index of CM service intervals table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.4.1.1 | ||||
airIRG3CMServiceIntervalsCMIDmandatory The CM ID (RDU Number - Group Number - CM Unit Number). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.5.4.1.2 | ||||
| The CM service interval for air filter in weeks. Supported only for RA. Returns -1 if not supported. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.4.1.3 | ||||
| The CM service interval air filter alarm status. Supported only for RA. Returns -1 if not supported. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.4.1.4 |
.1.3.6.1.4.1.318.1.1.13.6.5.5
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMThresholdsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMThresholdsTable'
Allows to access CM thresholds table.
The CM thresholds table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3CMThresholdsDeviceIndexmandatory Index for CM thresholds table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.1 |
airIRG3CMThresholdsCMIDmandatory The CM ID (RDU Number - Group Number - CM Unit Number). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.2 |
| The CM high threshold for rack inlet temperature in tenths of degrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.3 |
| The CM high threshold for rack inlet temperature in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.4 |
| The CM high threshold for supply air temperature in tenths of degrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.5 |
| The CM high threshold for supply air temperature in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.6 |
| The CM high threshold for return air temperature in tenths of degrees Fahrenheit. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.7 |
| The CM high threshold for return air temperature in tenths of degrees Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.5.1.8 |
.1.3.6.1.4.1.318.1.1.13.6.5.6
·
1 row entry
·
1 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMSetpointsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMSetpointsTable'
Allows to access CM set points table.
The CM set points table entry.
Indexes
| Column | Syntax | OID |
|---|---|---|
airIRG3CMSetpointsDeviceIndexmandatory Index of CM set points table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.6.1.1 |
.1.3.6.1.4.1.318.1.1.13.6.5.7
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk airIRG3CMConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::airIRG3CMConfigTable'
Allows to access CM configuration table.
The CM configuration table entry.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
airIRG3CMConfigDeviceIndexmandatory Index of CM configuration table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.7.1.1 | ||||
airIRG3CMConfigCMIDmandatory The CM ID (RDU Number - Group Number - CM Unit Number). | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.13.6.5.7.1.2 | ||||
airIRG3CMConfigStopOnCoolFailmandatory Enable/Disable Stop On cool fail. When enabled, stops the unitif it detects that it is blowing warm air into the cold aisle. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.7.1.3 | ||||
airIRG3CMConfigStartupDelaymandatory The CM start up delay in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.13.6.5.7.1.4 | ||||
airIRG3CMConfigRemoteOnStandbymandatory The CM configuration for operating mode. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.7.1.5 | ||||
airIRG3CMConfigPowerSourcemandatory The CM power source. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.13.6.5.7.1.6 |
.1.3.6.1.4.1.318.1.1.14.1.1
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUIdentTable'
Allows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID.
The device to query.
Indexes
| Column | Syntax | OID |
|---|---|---|
rARUIdentAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.1.1.1.1 |
rARUIdentNamemandatory A character string identifying the device. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.14.1.1.1.2 |
.1.3.6.1.4.1.318.1.1.14.2.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUConfigTable'
Allows for configuration of the individual ARU devices accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
The ARUs to configure.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rARUConfigAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.2.1.1.1 | ||||||||||||||||||||||||||||||||||||
rARUConfigAruNamemandatory The name of the ARU. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.14.2.1.1.2 | ||||||||||||||||||||||||||||||||||||
rARUConfigAruRemoteSetpointmandatory This OID defines the desired base airflow of the ARU, and sets thespeed of the ARU fans when the temperature override is inactive. Values specified in cfm (cubic feet per minute) can be converted to metr… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.2.1.1.3 | ||||||||||||||||||||||||||||||||||||
rARUConfigAruTempOvrdEnableDisablemandatory This OID is used to enable/disable the remote temperature override setting of the ARU.If this OID is set to 1, the remote setting for temperature override is disabled. If this OID is set to 2, the remote… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.2.1.1.4 | ||||||||||||||||||||||||||||||||||||
rARUConfigAruTempOvrdSetpointmandatory This OID is the Temperature Override setpoint of the ARU.NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees using the units specified… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.2.1.1.5 | ||||||||||||||||||||||||||||||||||||
rARUConfigAruMasterControlmandatory This is the master on/off control for the ARU. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.2.1.1.6 |
.1.3.6.1.4.1.318.1.1.14.3.3
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUStatusTable'
Allows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
The ARUs to access.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rARUStatusAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.1 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruNamemandatory The name of the ARU. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.14.3.3.1.2 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruRemoteSetpointmandatory This OID defines the desired base airflow of the ARU, or thespeed of the ARU fans when the temperature override is inactive. See also the rARUConfigAruRemoteSetpoint OID. NOTE: -1 will be … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.3 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruManualSetpointmandatory Manual operating setpoint of the ARU, which is set on thepanel of the ARU. If the ARU doesn't have a manual , the OID will always return a value of aruRem (10). NOTE: -1 will be returned if the ARU is no… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.4 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTemp1mandatory ARU temperature probe #1 reading.The summary exhaust temperature on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number d… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.5 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTemp2mandatory ARU temperature probe #2 reading.The exhaust temperature in the upper plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in wh… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.6 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTemp3mandatory ARU temperature probe #3 reading.The exhaust temperature in the lower plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in wh… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.7 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTempOvrdEnableDisablemandatory This OID indicates whether the ARU remote temperature override is enabled or disabled.If this OID is a 1, the remote setting for temperature override is disabled. If this OID is a 2, the remote setting for temperature … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.8 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTempOvrdSetpointmandatory ARU remote temperature override setpoint setting.NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Units are displayed in the scale… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.9 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruAlarmStatemandatory An ASCII string containing the 8 flags representingthe current alarm state of the ARU. If the state of the ARU is unknown, this variable is set to 'UNKNOWN'. The flags are numbered 1 to 8, read from left… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.14.3.3.1.10 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruCommStatusmandatory The state of communications to the device.commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates communication is normal and active with this device. commsL… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.11 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTempOvrdStatusmandatory Specifies whether the ARU is increasing airflow becauseexhaust air temperature has exceeded the setting specified in the rARUConfigAruTempOvrdSetpoint OID. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.12 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruMasterControlmandatory This is the master on/off control for the ARU. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.3.3.1.13 | ||||||||||||||||||||||||||||||||||||
rARUStatusAruTotalAirflowmandatory The total airflow provided by the aru. Specified in cfm (cubic feet per minute).Can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per hour). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.3.3.1.14 |
.1.3.6.1.4.1.318.1.1.14.4.1
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUFanStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUFanStatusTable'
Allows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID.
The device to query.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rARUFanStatusAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.1 | ||||||||||||||
rARUFanStatusNominalFanSpeedmandatory The nominal rotational speed (RPM) of the fans when they areoperating at the 100% level. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.2 | ||||||||||||||
rARUFanStatusSelectedFanLevelmandatory The currently selected ARU speed level,specified in percent of full capacity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.3 | ||||||||||||||
rARUFanStatusReplacementThresholdmandatory Threshold above which a run hour alarm will exist, indicatingthat it might be time to proactively replace a fan. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.4.1.1.4 | ||||||||||||||
rARUFanStatusFanIndexmandatory The index to an individual fan table entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.5 | ||||||||||||||
rARUFanStatusFanOperatingStatusmandatory The current operating state of the fan. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.4.1.1.6 | ||||||||||||||
rARUFanStatusFanRpmSpeedmandatory The current rotational speed of the fan,specified in rotations per minute (RPM). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.7 | ||||||||||||||
rARUFanStatusFanFlowRatemandatory The flow rate provided by the fan, based on its measured rotational speed.Specified in cfm (cubic feet per minute). Can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^3/hr (cubic meters per h… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.8 | ||||||||||||||
rARUFanStatusFanInServiceDatemandatory The installation/replacement date of the fan. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.14.4.1.1.9 | ||||||||||||||
rARUFanStatusFanRunhourCountermandatory The total time for which the fan has been running.Specified in 10ths of hours. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.4.1.1.10 | ||||||||||||||
rARUFanStatusFanRunhourResetmandatory Writing yes to this This OID will reset a fan's total run hour counter,which is shown in the rARUFanStatusFanRunhourCounter OID. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.4.1.1.11 |
.1.3.6.1.4.1.318.1.1.14.5.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUPowerStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUPowerStatusTable'
Allows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
The device to query.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
rARUPowerStatusAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.5.1.1.1 | ||||
rARUPowerStatusPrimaryAcPresentmandatory Indicates whether or not line voltage is present on AC input 1. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.5.1.1.2 | ||||
rARUPowerStatusAuxiliaryAcPresentmandatory Indicates whether or not line voltage is present on AC input 2. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.5.1.1.3 | ||||
rARUPowerStatusRedundantAcConfigmandatory Indicates whether or not a dual cord is in use.When this setting is set to dualCord (2), aruRedundantPowerLostAlarm traps will be generated when either primary or auxiliary input voltage is not present. When this setti… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.14.5.1.1.4 |
.1.3.6.1.4.1.318.1.1.14.6.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUSensorsStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUSensorsStatusTable'
Allows for getting environmental sensor status information.
The unit to get data from.
| Column | Syntax | OID |
|---|---|---|
rARUSensorsStatusAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.2.1.1 |
rARUSensorsStatusSensorNumbermandatory The number of the sensor on the device. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.2.1.2 |
rARUSensorsTemperaturemandatory The sensor's current temperature reading. The temperature scaleis based on the system preferences configuration. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.2.1.3 |
.1.3.6.1.4.1.318.1.1.14.6.4
·
1 row entry
·
17 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rARUSensorsConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rARUSensorsConfigTable'
Allows for getting configuration information from environmental sensors attached to the device.
The unit to get data from.
| Column | Syntax | OID |
|---|---|---|
rARUSensorsConfigAruIndexmandatory The index to the ARU entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.1 |
rARUSensorsConfigSensorNumbermandatory The number of the sensor on the device. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.2 |
rARUSensorsNamemandatory A descriptive name for the sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.14.6.4.1.3 |
rARUSensorsLocationmandatory The location of the sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.14.6.4.1.4 |
rARUSensorsTempMaxThreshmandatory The temperature at which a maximum temperature thresholdviolation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.5 |
rARUSensorsTempHighThreshmandatory The temperature at which a high temperature thresholdviolation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.6 |
rARUSensorsTempLowThreshmandatory The temperature at which a low temperature thresholdviolation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.7 |
rARUSensorsTempMinThreshmandatory The temperature at which a min temperature thresholdviolation alarm will be generated for this sensor. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.8 |
rARUSensorsTempThreshHysteresismandatory The change in temperature required to cause atemperature alarm to change from an active to an inactive state. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.9 |
| The value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.10 |
| The time over which the temperature may not decrease beyond the value specified by the temperature short-term decreasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.11 |
| The value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.12 |
| The time over which the temperature may not increase beyond the value specified by the temperature short-term increasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.13 |
| The value of the temperature long-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.14 |
rARUSensorsTempLongDecRateThreshTimemandatory The time over which the temperature may not decreasebeyond the value specified by the temperature long-term decreasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.15 |
| The value of the temperature long-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences configuration. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.16 |
rARUSensorsTempLongIncRateThreshTimemandatory The time over which the temperature may not increasebeyond the value specified by the temperature long-term increasing rate threshold value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.14.6.4.1.17 |
.1.3.6.1.4.1.318.1.1.15.3.1.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUMainInputVoltagePhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUMainInputVoltagePhaseTable'
A list of input voltage table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUMainInputVoltageTableSize OID.
An entry containing information applicable to a
particular main input voltage phase.
particular main input voltage phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUMainInputVoltagePhaseIndexmandatory Description of each input phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.3.1.4.1.1 | ||||||
xPDUMainInputVoltageLtoLmandatory Line-to-line PDU input voltage when an isolation transformer is present,or -1 if no transformer present in this PDU. Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.1.4.1.2 | ||||||
xPDUMainInputVoltageLtoNmandatory Line-to-neutral PDU input voltage when an isolation transformer is not present,or -1 if a transformer is present in this PDU. Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.1.4.1.3 |
.1.3.6.1.4.1.318.1.1.15.3.2.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUBypassInputVoltagePhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUBypassInputVoltagePhaseTable'
A list of output table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUBypassInputVoltagePhaseTableSize OID.
An entry containing information applicable to a
particular bypass input voltage phase.
particular bypass input voltage phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUBypassInputVoltagePhaseIndexmandatory Index of each bypass input phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.3.2.4.1.1 | ||||||
xPDUBypassInputVoltageLtoLmandatory Line-to-line bypass input voltage, or -1 if no bypassfeed is present in this PDU. Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.2.4.1.2 | ||||||
xPDUBypassInputVoltageLtoNmandatory Line-to-neutral bypass input voltage, or -1 if no bypassfeed is present in this PDU. Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.2.4.1.3 |
.1.3.6.1.4.1.318.1.1.15.3.3.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUUPSInputVoltagePhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUUPSInputVoltagePhaseTable'
A list of UPS input table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUUPSInputVoltagePhaseTableSize OID.
An entry containing information applicable to a
particular UPS input voltage phase.
particular UPS input voltage phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUUPSInputVoltagePhaseIndexmandatory Description of each UPS input phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.3.3.2.1.1 | ||||||
xPDUUPSInputVoltageLtoNPresentmandatory Indicates whether or not voltage is present at the UPS feed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.3.3.2.1.2 |
.1.3.6.1.4.1.318.1.1.15.3.4.14
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUSystemOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUSystemOutputPhaseTable'
A list of system output table entries. The number of entries is contained in the xPDUSystemOutputTableSize OID.
An entry containing information applicable to a
particular system output phase.
particular system output phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUSystemOutputPhaseIndexmandatory Description of each output phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.3.4.14.1.1 | ||||||
xPDUSystemOutputVoltageLtoLmandatory Line-to-line system output voltage available at the circuit panel.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.2 | ||||||
xPDUSystemOutputVoltageLtoNmandatory Line-to-neutral system output voltage available at the circuit panel.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.3 | ||||||
xPDUSystemOutputPhaseCurrentmandatory System load current per phase. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.4 | ||||||
xPDUSystemOutputPowermandatory System output power per phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.5 | ||||||
xPDUSystemOutputApparentPowermandatory System output power per phase. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.6 | ||||||
xPDUSystemOutputPowerFactormandatory Indicates the Power Factor of the system output per phase.A value of 100 representing a unity Power Factor (1.00). Measured in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.3.4.14.1.7 |
.1.3.6.1.4.1.318.1.1.15.4.1.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUSystemBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUSystemBreakerTable'
A list of system breaker entries. The number of entries is contained in the xPDUSystemBreakerTableSize OID.
An entry containing information applicable to a
particular system breaker.
particular system breaker.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUSystemBreakerTableIndexmandatory Index of system breaker entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.4.1.2.1.1 | ||||||
xPDUSystemBreakerDescriptionmandatory A brief description of the system breakers. | OctetString Constraints: range: 0-79 | .1.3.6.1.4.1.318.1.1.15.4.1.2.1.2 | ||||||
xPDUSystemBreakerPositionmandatory Indicates whether this breaker is open(1) or closed(2). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.4.1.2.1.3 |
.1.3.6.1.4.1.318.1.1.15.4.2.3
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUBranchBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUBranchBreakerTable'
A list of branch breaker table entries. The number of entries is given by the value of xPDUBranchBreakerTableSize The number of entries is contained in the xPDUBranchBreakerTableSize OID.
An entry containing information applicable to a
particular branch breaker (panel position).
particular branch breaker (panel position).
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
xPDUBranchBreakerTableIndexmandatory Index of branch breaker entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.1 | ||||
xPDUBranchBreakerRatingmandatory Indicates current rating of this breaker.0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker current rating in Amps. A value above 60 Amp will signify a … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.2 | ||||
xPDUBranchBreakerRDPFeedmandatory Indicates that a breaker position is feeding a remotedistribution panel. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.4.2.3.1.3 | ||||
xPDUBranchBreakerTieIndicatormandatory Indicates whether or not the breaker in this positionis logically associated with the breaker immediately below it. This setting is used grouping the breakers feeding a multi-pole branch circuit. Note: When setting an … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.4.2.3.1.4 | ||||
xPDUBranchBreakerCurrentmandatory Indicates the branch current in tenths of Amps or -1 when not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.5 | ||||
| Threshold above which a branch circuit high current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch c… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.6 | ||||
| Threshold below which a branch circuit low current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branch ci… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.7 | ||||
xPDUBranchBreakerMaxCurrentThresholdmandatory Threshold above which a branch circuit maximum currentcondition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branc… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.8 | ||||
xPDUBranchBreakerMinCurrentThresholdmandatory Threshold below which a branch circuit minimum currentcondition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates that the threshold is disabled. Note: When setting branc… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.9 | ||||
xPDUBranchBreakerNamemandatory The description of the purpose/use of the breaker. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.10 | ||||
xPDUBranchBreakerLocationmandatory The description of the location of the breaker. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.15.4.2.3.1.11 |
.1.3.6.1.4.1.318.1.1.15.5.3
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUInputContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUInputContactTable'
A list of contacts supported by the PDU. The number of entries is contained in the xPDUInputContactTableSize OID.
A contact entry containing information for a given contact.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUInputContactNumbermandatory An index identifying the contact on the PDU. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.5.3.1.1 | ||||||
xPDUInputContactNamemandatory The description of the purpose/use of the contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.15.5.3.1.2 | ||||||
xPDUInputContactNormalStatemandatory The normal operating position of the contact. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.5.3.1.3 | ||||||
xPDUInputContactCurrentStatemandatory This value indicates the current state of the contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.5.3.1.4 |
.1.3.6.1.4.1.318.1.1.15.6.3
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xPDUOutputRelayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUOutputRelayTable'
A list of output relays supported by the PDU. The number of entries is contained in the xPDUOutputRelayTableSize OID.
A output relay entry containing information for a given contact.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xPDUOutputRelayNumbermandatory An index identifying the output relay on the PDU. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.15.6.3.1.1 | ||||||
xPDUOutputRelayNamemandatory The description of the purpose/use of the output relay. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.15.6.3.1.2 | ||||||
xPDUOutputRelayNormalStatemandatory The normal operating position of the output relay. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.6.3.1.3 | ||||||
xPDUOutputRelayCurrentStatemandatory This value indicates the current state of the output relay. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.15.6.3.1.4 |
.1.3.6.1.4.1.318.1.1.16.3.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManUnitCalibTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManUnitCalibTable'
Allows for getting calibration information from each unit in the system.
The unit to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
battManUnitCalibIndexmandatory Index of unit calibration entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.3.2.1.1 |
battManUnitSerialNumbermandatory The serial number of the unit. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.16.3.2.1.2 |
battManBatteryVoltageZeroCalibmandatory The unit battery voltage zero calibration in millivolts. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.3.2.1.3 |
battManBatteryVoltageSpanCalibmandatory The unit battery voltage span calibration in hundredths of percent. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.3.2.1.4 |
.1.3.6.1.4.1.318.1.1.16.4.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManStringCalibTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManStringCalibTable'
Allows for getting calibration information from each string in the system.
The string to get data from.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
battManStringCalibIndexmandatory Index of string calibration entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.4.2.1.1 | ||||||||||
battManDCCurrentZeroCalibmandatory The string DC current zero calibration in tenths of amps. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.4.2.1.2 | ||||||||||
battManACCurrentZeroCalibmandatory The string AC current zero calibration in tenths of amps. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.4.2.1.3 | ||||||||||
battManProbeRangemandatory The string probe range in amps. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.4.2.1.4 |
.1.3.6.1.4.1.318.1.1.16.5.2
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1BatteryCalibTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1BatteryCalibTable'
Allows for getting calibration information from each battery in String 1.
The string to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
battManString1BatteryCalibIndexmandatory Index of battery calibration entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.5.2.1.1 |
| The battery inter-tier ohmic value in ohms. This corresponds to the ohmic value for the positive terminal of the battery. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.5.2.1.2 |
.1.3.6.1.4.1.318.1.1.16.5.4
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2BatteryCalibTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2BatteryCalibTable'
Allows for getting calibration information from each battery in String 2.
The string to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
battManString2BatteryCalibIndexmandatory Index of battery calibration entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.5.4.1.1 |
| The battery inter-tier ohmic value in ohms. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.5.4.1.2 |
.1.3.6.1.4.1.318.1.1.16.9.2
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManStringTable'
Allows for getting information from each string in the system.
The string to get data from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
battManStringIndexmandatory Index of string entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.1 | ||||
battManStringCurrentmandatory The string current in tenths of amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.2 | ||||
battManStringRippleCurrentmandatory The string ripple current in tenths of amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.3 | ||||
battManStringChargerHighVoltageAlarmmandatory When set to alarm(2), indicates that the string charger has a high voltage alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.9.2.1.4 | ||||
battManStringChargerLowVoltageAlarmmandatory When set to alarm(2), indicates that the string charger has a low voltage alarm. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.9.2.1.5 | ||||
| When set to alarm(2), indicates that the string charger probe is disconnected. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.9.2.1.6 | ||||
battManStringOnBatterymandatory When set to alarm(2), indicates that the string is in the on-battery state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.9.2.1.7 | ||||
battManStringHighRippleCurrentmandatory When set to alarm(2), indicates that the string has a high ripple current. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.9.2.1.8 | ||||
battManStringVoltagemandatory The sum of the voltages for all of the batteries on astring in millivolts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.9 | ||||
battManStringDischargeLess5Secondsmandatory The number of recorded discharges lasting less than5 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.10 | ||||
battManStringDischarge5to10Secondsmandatory The number of recorded discharges lasting between 5and 10 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.11 | ||||
battManStringDischarge10to60Secondsmandatory The number of recorded discharges lasting between 10and 60 seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.12 | ||||
battManStringDischargeMore60Secondsmandatory The number of recorded discharges lasting more than60 seconds (1 minute). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.9.2.1.13 |
.1.3.6.1.4.1.318.1.1.16.10.2
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1BatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1BatteryTable'
Allows for getting information from each string in the system.
The string to get data from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
battManString1BatteryIndexmandatory Index of string entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.2.1.1 | ||||
battManString1BatteryVoltagemandatory The battery voltage in millivolts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.2.1.2 | ||||
battManString1BatteryLowestVoltagemandatory The lowest battery discharge voltage during the last power event in millivolts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.2.1.3 | ||||
battManString1BatteryCellShortedmandatory When set to alarm(2), indicates that a battery cell is shorted. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.4 | ||||
| When set to alarm(2), indicates that a fuse or connection is open. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.5 | ||||
battManString1BatteryLowCapacitymandatory When set to alarm(2), indicates a battery has low capacity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.6 | ||||
battManString1BatteryHighOhmicValuemandatory When set to alarm(2), indicates a battery has a high ohmic value. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.7 | ||||
battManString1BatteryThermalRunawaymandatory When set to alarm(2), indicates a battery has a thermal runaway condition. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.8 | ||||
battManString1BatteryDryoutmandatory When set to alarm(2), indicates a battery has a dryout condition. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.9 | ||||
| When set to alarm(2), indicates a battery has violated the user level high voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.10 | ||||
| When set to alarm(2), indicates a battery has violated the user level low voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.11 | ||||
| When set to alarm(2), indicates a battery has violated the chemistry level high voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.12 | ||||
| When set to alarm(2), indicates a battery has violated the chemistry level low voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.13 | ||||
battManString1BatteryOpenCellmandatory When set to alarm(2), indicates the battery has an opencell or an inter-connection is abnormal. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.2.1.14 |
.1.3.6.1.4.1.318.1.1.16.10.4
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2BatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2BatteryTable'
Allows for getting information from each string in the system.
The string to get data from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
battManString2BatteryIndexmandatory Index of string entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.4.1.1 | ||||
battManString2BatteryVoltagemandatory The battery voltage in millivolts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.4.1.2 | ||||
battManString2BatteryLowestVoltagemandatory The lowest battery discharge voltage during the last power event in millivolts DC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.10.4.1.3 | ||||
battManString2BatteryCellShortedmandatory When set to alarm(2), indicates that a battery cell is shorted. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.4 | ||||
| When set to alarm(2), indicates that a fuse or connection is open. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.5 | ||||
battManString2BatteryLowCapacitymandatory When set to alarm(2), indicates a battery has low capacity. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.6 | ||||
battManString2BatteryHighOhmicValuemandatory When set to alarm(2), indicates a battery has a high ohmic value. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.7 | ||||
battManString2BatteryThermalRunawaymandatory When set to alarm(2), indicates a battery has a thermal runaway condition. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.8 | ||||
battManString2BatteryDryoutmandatory When set to alarm(2), indicates a battery has a dryout condition. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.9 | ||||
| When set to alarm(2), indicates a battery has violated the user level high voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.10 | ||||
| When set to alarm(2), indicates a battery has violated the user level low voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.11 | ||||
| When set to alarm(2), indicates a battery has violated the chemistry level high voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.12 | ||||
| When set to alarm(2), indicates a battery has violated the chemistry level low voltage limit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.13 | ||||
battManString2BatteryOpenCellmandatory When set to alarm(2), indicates the battery has an opencell or an inter-connection is abnormal. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.10.4.1.14 |
.1.3.6.1.4.1.318.1.1.16.11.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManInputContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManInputContactTable'
Allows for getting information from each contact in the system.
The contact to get data from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
battManInputContactIndexmandatory Index of contact entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.11.2.1.1 | ||||
battManInputContactNamemandatory The name of the input contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.16.11.2.1.2 | ||||
battManInputContactAlarmStatemandatory When set to alarm(2), indicates that the alarm condition is active for this contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.11.2.1.3 | ||||
battManInputContactStatemandatory When set to open(1), the input contact is in the open state.When set to closed(2), the input contact is in the closed state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.11.2.1.4 | ||||
battManInputContactNormalStatemandatory When set to open(1), the input contact is normally open.When set to closed(2), the input contact is normally closed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.11.2.1.5 | ||||
battManInputContactAlarmDelaymandatory The input contact alarm delay time in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.11.2.1.6 |
.1.3.6.1.4.1.318.1.1.16.13.3
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1OhmicValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1OhmicValueTable'
Allows for getting ohmic value information from each battery in String 1.
The string to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
battManString1OhmicValueIndexmandatory The battery number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.3.1.1 |
battManString1OhmicValueDatamandatory The battery inter-tier ohmic value in tenths of milli-Ohms.Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.3.1.2 |
.1.3.6.1.4.1.318.1.1.16.13.5
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1ResponseTestChangeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1ResponseTestChangeTable'
Allows for getting response test change information from each battery in String 1.
The string to get data from.
| Column | Syntax | OID |
|---|---|---|
| Index of the entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.5.1.1 |
battManString1ResponseTestChangeDatamandatory The battery response test change in percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.5.1.2 |
.1.3.6.1.4.1.318.1.1.16.13.8
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2OhmicValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2OhmicValueTable'
Allows for getting ohmic value information from each battery in String 2.
The string to get data from.
Indexes
| Column | Syntax | OID |
|---|---|---|
battManString2OhmicValueIndexmandatory Index of battery calibration entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.8.1.1 |
battManString2OhmicValueDatamandatory The battery inter-tier ohmic value in ohms.Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.8.1.2 |
.1.3.6.1.4.1.318.1.1.16.13.10
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2ResponseTestChangeTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2ResponseTestChangeTable'
Allows for getting response test change information from each battery in String 2.
The string to get data from.
| Column | Syntax | OID |
|---|---|---|
| Index of the entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.10.1.1 |
battManString2ResponseTestChangeDatamandatory The battery response test change in percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.13.10.1.2 |
.1.3.6.1.4.1.318.1.1.16.13.12
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1ResponseTestCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1ResponseTestCurrentTable'
Allows for getting response test current information from each battery in String 1.
The string to get data from.
.1.3.6.1.4.1.318.1.1.16.13.14
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2ResponseTestCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2ResponseTestCurrentTable'
Allows for getting response test current information from each battery in String 2.
The string to get data from.
.1.3.6.1.4.1.318.1.1.16.13.16
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString1ResponseTestCurrentBenchmarkTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString1ResponseTestCurrentBenchmarkTable'
Allows for getting response test current benchmark information from each battery in String 1.
The string to get data from.
.1.3.6.1.4.1.318.1.1.16.13.18
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManString2ResponseTestCurrentBenchmarkTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManString2ResponseTestCurrentBenchmarkTable'
Allows for getting response test current benchmark information from each battery in String 2.
The string to get data from.
.1.3.6.1.4.1.318.1.1.16.14.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk battManUnitStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::battManUnitStatusTable'
Allows for getting status information from each unit in the system.
The unit to get data from.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
battManUnitStatusIndexmandatory Index of unit status entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.14.2.1.1 | ||||
battManUnitStatusSerialNumbermandatory The battery manager unit serial number character string.This value is set at the factory. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.16.14.2.1.2 | ||||
battManUnitHardwareRevmandatory The battery manager unit hardware revision.This value is set at the factory. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.14.2.1.3 | ||||
battManUnitFirmwareRevmandatory The battery manager unit firmware revision.This value is set at the factory and can change with firmware update. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.16.14.2.1.4 | ||||
battManUnitCommLossmandatory When set to alarm(2), indicates the system has lostcommunication with the unit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.14.2.1.5 | ||||
battManUnitRelayStuckmandatory When set to alarm(2), indicates the unit monitor relayis stuck. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.16.14.2.1.6 |
.1.3.6.1.4.1.318.1.1.17.3.3.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSwitchTimersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchTimersTable'
A list of timers supported by ATS. The number of entries is contained in the xATSSwitchTimersTableSize OID.
An entry containing information about an individual ATS timer.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
xATSSwitchTimersIndexmandatory Index of timer entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.3.2.1.1 | ||||
xATSSwitchTimersNamemandatory Name of the individual timer.Refer to ATS operation manual,or on-line help, for detailed descriptions of ATS timers. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.17.3.3.2.1.2 | ||||
xATSSwitchTimersAbortmandatory This aborts the individual timer. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.3.3.2.1.3 | ||||
xATSSwitchTimersStatusmandatory The status of the individual timer. Designates whether this timerentry is currently running or inactive. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.3.3.2.1.4 | ||||
xATSSwitchTimersRemainingTimemandatory The time remaining for this timer entry.Specified in seconds. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.3.2.1.5 | ||||
xATSSwitchTimersDelaySettingmandatory The delay settings associated with this timer entry.When this timer entry is active, the timer value must exceed this setting before the ATS behavior associated with this timer is executed. Refer to ATS operation manua… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.3.2.1.6 |
.1.3.6.1.4.1.318.1.1.17.3.4.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSwitchBlockMapTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchBlockMapTable'
A list of blocking maps supported by the ATS. The number of entries is contained in the xATSSwitchBlockMapTableSize OID.
An entry containing information about a specific ATS blocking map.
Indexes
| Column | Syntax | OID |
|---|---|---|
xATSSwitchBlockMapIndexmandatory Index of blocking map entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.4.2.1.1 |
xATSSwitchBlockMapNamemandatory A string describing the ATS action to be blocked. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.17.3.4.2.1.2 |
xATSSwitchBlockMapStatusmandatory Represents the status of this blocking map entry, in bit-mapped format.A non-zero value indicates that this entry's ATS action is currently being blocked. The bit(s) set indicate which input(s) are causing the blocking… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.4.2.1.3 |
xATSSwitchBlockMapSettingmandatory This setting designates the inputs that block the ATS actionThe mapping is specified as a bit-field, where each bit set indicates the input that blocks the ATS action associated with the entry. bit 0 - C… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.4.2.1.4 |
.1.3.6.1.4.1.318.1.1.17.3.5.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSwitchStatisticsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchStatisticsTable'
A list of statistics supported by ATS. The number of entries is contained in the xATSSwitchStatisticsTableSize OID.
An entry containing information about an individual ATS statistic.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
xATSSwitchStatisticsIndexmandatory Index of ATS statistics entries in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.3.5.2.1.1 | ||||
xATSSwitchStatisticsNamemandatory This is the name of the ATS statistic associated with this entry. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.17.3.5.2.1.2 | ||||
xATSSwitchStatisticsValuemandatory This is the value of the ATS statistic associated with this entry. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.17.3.5.2.1.3 | ||||
xATSSwitchStatisticsResetmandatory This will reset the individual ATS statistic associated with this entry. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.3.5.2.1.4 |
.1.3.6.1.4.1.318.1.1.17.4.1.7
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSource1PhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSource1PhaseTable'
A list of voltage table entries for source 1. The number of entries are the phase entries. The number of entries is contained in the xATSSource1TableSize OID.
An entry containing information applicable to a
particular input voltage phase at the source 1 input of the ATS.
particular input voltage phase at the source 1 input of the ATS.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xATSSource1Indexmandatory Description of each phase utilized at source 1. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.4.1.7.1.1 | ||||||
xATSSource1VoltageLtoLmandatory Source 1 line-to-line input voltage.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.1.7.1.2 | ||||||
xATSSource1VoltageLtoNmandatory Source 1 line-to-neutral input voltage.Measured in tenths of Volts. -1 for a 3-wire service type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.1.7.1.3 |
.1.3.6.1.4.1.318.1.1.17.4.2.7
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSource2PhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSource2PhaseTable'
A list of voltage table entries for the source 2. The number of entries are the phase entries. The number of entries is contained in the xATSSource2TableSize OID.
An entry containing information applicable to a
particular input voltage phase at the source 2 input of the ATS.
particular input voltage phase at the source 2 input of the ATS.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xATSSource2Indexmandatory Description of each phase utilized at the source 2. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.4.2.7.1.1 | ||||||
xATSSource2VoltageLtoLmandatory Source 2 line-to-line input voltage.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.2.7.1.2 | ||||||
xATSSource2VoltageLtoNmandatory Source 2 line-to-neutral input voltage.Measured in tenths of Volts. -1 for a 3-wire service type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.2.7.1.3 |
.1.3.6.1.4.1.318.1.1.17.4.3.12
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSSystemOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSystemOutputPhaseTable'
A list of system output table entries. The number of entries is contained in the xATSSystemOutputTableSize OID.
An entry containing information applicable to a
particular system output phase.
particular system output phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xATSSystemOutputPhaseIndexmandatory Description of each system output phase utilized in this device. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.4.3.12.1.1 | ||||||
xATSSystemOutputVoltageLtoLmandatory Line-to-line system output voltage available at the circuit panel.Measured in tenths of Volts. -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.2 | ||||||
xATSSystemOutputVoltageLtoNmandatory Line-to-neutral system output voltage available at the circuit panel.Measured in tenths of Volts. -1 for a 3-wire service type or if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.3 | ||||||
xATSSystemOutputPhaseCurrentmandatory System load current per phase. Measured in Amps.-1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.4 | ||||||
xATSSystemOutputPowermandatory System output power per phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.5 | ||||||
xATSSystemOutputApparentPowermandatory system output power per phase. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.6 | ||||||
xATSSystemOutputPowerFactormandatory indicates the power factor of the system output per phase.A value of 100 representing a unity power factor (1.00). Measured in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.4.3.12.1.7 |
.1.3.6.1.4.1.318.1.1.17.6.3
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSInputContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSInputContactTable'
A list of contacts supported by the ATS. The number of entries is contained in the xATSInputContactTableSize OID.
A contact entry containing information for a given contact.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
xATSInputContactNumbermandatory An index identifying the contact on the ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.6.3.1.1 | ||||
xATSInputContactNamemandatory The description of the purpose/use of the contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.17.6.3.1.2 | ||||
xATSInputContactNormalStatemandatory The normal operating position of the contact. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.6.3.1.3 | ||||
xATSInputContactCurrentStatemandatory This value indicates the current state of the contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.6.3.1.4 |
.1.3.6.1.4.1.318.1.1.17.7.3
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSOutputRelayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSOutputRelayTable'
A list of output relays supported by the ATS. The number of entries is contained in the xATSOutputRelayTableSize OID.
A output relay entry containing information for a given contact.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
xATSOutputRelayNumbermandatory An index identifying the output relay on the ATS. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.17.7.3.1.1 | ||||
xATSOutputRelayNamemandatory The description of the purpose/use of the output relay. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.17.7.3.1.2 | ||||
xATSOutputRelayNormalStatemandatory The normal operating position of the output relay. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.7.3.1.3 | ||||
xATSOutputRelayCurrentStatemandatory This value indicates the current state of the output relay. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.17.7.3.1.4 |
.1.3.6.1.4.1.318.1.1.18.1.4.6
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk xATSGeneratorOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSGeneratorOutputPhaseTable'
A list of generator output table entries. The number of entries is contained in the xATSGeneratorOutputTableSize OID.
An entry containing information applicable to a
particular generator output phase.
particular generator output phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
xATSGeneratorOutputPhaseIndexmandatory Description of each generator output phase utilized in this device. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.18.1.4.6.1.1 | ||||||
xATSGeneratorOutputVoltageLtoLmandatory Line-to-line generator output voltage.Measured in Volts, or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.2 | ||||||
xATSGeneratorOutputVoltageLtoNmandatory Line-to-neutral generator output voltage.Measured in volts, or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.3 | ||||||
xATSGeneratorOutputPhaseCurrentmandatory Generator load current per phase.Measured in Amps, or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.4 | ||||||
xATSGeneratorOutputPowermandatory Generator output power per phase.Measured in tenths of kW, or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.5 | ||||||
xATSGeneratorOutputApparentPowermandatory Generator output power per phase.Measured in tenths of kVA, or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.6 | ||||||
xATSGeneratorOutputPowerFactormandatory Indicates the load power factor of the generator output per phase.A value of 100 representing a unity power factor (1.00), or -1 if not available. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.18.1.4.6.1.7 |
.1.3.6.1.4.1.318.1.1.19.1.1.4.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsCardIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsCardIdentTable'
A table of PCMCIA card identifications.
Identification information for a PCMCIA card.
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsCardIdentIndexmandatory Number to identify the socket Card. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.1 |
cpsCardIdentProdmandatory Product identification string. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.2 |
cpsCardIdentManmandatory Manufacturer ID code. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.3 |
cpsCardIdentFuncmandatory Function ID code. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.4 |
cpsCardIdentPCImandatory PCI ID | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.5 |
.1.3.6.1.4.1.318.1.1.19.1.1.4.3
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsCardConfTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsCardConfTable'
A table of socket configuration information.
Configuration information for a socket.
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsCardConfIndexmandatory Number to identify the socket PCMCIA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.1 |
cpsCardConfPowermandatory Power Settings. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.2 |
cpsCardConfTypemandatory Interface Type. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.3 |
cpsCardConfIntermandatory Interrupt number. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.4 |
cpsCardConfFuncmandatory Function. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.5 |
cpsCardConfCardvmandatory Card values. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.6 |
cpsCardConfPort1mandatory I/O Port 1. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.7 |
cpsCardConfPort2mandatory I/O Port 2. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.8 |
.1.3.6.1.4.1.318.1.1.19.1.1.4.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsCardStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsCardStatusTable'
A table of current socket status information.
Current status information for a socket.
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsCardStatusIndexmandatory Number to identify the socket PCMCIA. | Integer32 Constraints: range: 0-2 | .1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.1 |
cpsCardStatusCardmandatory Current Card State. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.2 |
cpsCardStatusFuncmandatory Current Function. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.3 |
.1.3.6.1.4.1.318.1.1.19.1.2.6.1.11
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsSerialGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsSerialGroupTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsSerialGroupIndexmandatory Number to identify the group. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.1 |
cpsSerialGroupNamemandatory The group name. | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.2 |
cpsSerialGroupUsersmandatory The user's names. | OctetStringr/w Constraints: range: 0-80 | .1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.3 |
.1.3.6.1.4.1.318.1.1.19.1.2.6.2.1
·
1 row entry
·
58 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsSerialPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsSerialPortTable'
This is the specific configuration per serial port.
One particular serial port configuration.
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsSerialPortNumbermandatory Number to identify the serial port. Value 0 is ALL. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.1 |
cpsSerialPortTtymandatory The device name for the serial port. | OctetStringr/w Constraints: range: 0-25 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.2 |
cpsSerialPortNamemandatory Alias name given to the server connected to the serial port. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.3 |
cpsSerialPortSpeedmandatory The speed of the serial port.Supported values are: 50, 75, 110, 134, 150, 200, 300, 600, 1200, 1800, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200, 230400, and 460800 | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.4 |
cpsSerialPortDataSizemandatory The data size for the serial port. | Integer32r/w Constraints: range: 4-8 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.5 |
cpsSerialPortStopBitsmandatory The number of stop bits for the serial port. | Integer32r/w Constraints: range: 0-2 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.6 |
cpsSerialPortParitymandatory The parity for the serial port. | OctetStringr/w Constraints: range: 0-5 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.7 |
cpsSerialPortFlowCtrlmandatory The flow control for the serial port. | OctetStringr/w Constraints: range: 0-5 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.8 |
cpsSerialPortDTRdelaymandatory This specifies how long (in milliseconds) a DTR signalwill be turned off before it is turned on again. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.9 |
cpsSerialPortDCDCtrlmandatory DCD signal controls the connection request.0 will indicate nocontrol, 1 will indicate control. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.10 |
cpsSerialPortLogUtmpmandatory Update the login records in /var/run/utmp file.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.11 |
cpsSerialPortLogWtmpmandatory Update the login records in /var/run/wtmp file.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.12 |
cpsSerialPortLogformmandatory This is the format to write the login record. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.13 |
cpsSerialPortAuthtypemandatory Authentication type. | OctetStringr/w Constraints: range: 0-25 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.14 |
cpsSerialPortAuthSrv1mandatory IP address of the primary authentication server. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.15 |
cpsSerialPortAccSrv1mandatory IP address of the primary accounting server. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.16 |
cpsSerialPortAuthTmomandatory This is the timeout (in seconds) for the authenticationquery to be answered. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.17 |
cpsSerialPortAuthRetrmandatory This defines the number of times each server is triedbefore another is contacted. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.18 |
cpsSerialPortAuthSrv2mandatory IP address of the secondary authentication server. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.19 |
cpsSerialPortAccSrv2mandatory IP address of the secondary accounting server. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.20 |
cpsSerialPortAuthSecretmandatory This is the shared secret with authentication servers. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.21 |
cpsSerialPortAuthRadPmandatory Radius state.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.22 |
cpsSerialPortAuthAccmandatory Access restriction. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.23 |
cpsSerialPortProtocolmandatory Defines the serial port's protocol. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.24 |
cpsSerialPortRemoteIPmandatory This is the default IP address of the serial port. | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.25 |
cpsSerialPortSocketPortmandatory This defines an alternative labeling system for the serial port. | OctetStringr/w Constraints: range: 0-10 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.26 |
cpsSerialPortRemHostmandatory The IP address of the host to which the serial port will connect. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.27 |
cpsSerialPortBannermandatory This defines the banner. | OctetStringr/w Constraints: range: 0-250 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.28 |
cpsSerialPortPromptmandatory This defines the login prompt to the serial port. | OctetStringr/w Constraints: range: 0-250 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.29 |
cpsSerialPortTermTypemandatory This defines the terminal type. | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.30 |
cpsSerialPortAutomUsrmandatory This defines the automatic user. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.31 |
cpsSerialPortNetMaskmandatory The network mask used in dial in connection. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.32 |
cpsSerialPortPppMtumandatory The PPP MTU - dial in connection. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.33 |
cpsSerialPortPppMrumandatory The PPP MRU - dial in connection. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.34 |
cpsSerialPortPppOptionsmandatory The PPP options when the PPP session is autodetected. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.35 |
cpsSerialPortPppFoptionmandatory The PPP forced options when the user has already been authenticated. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.36 |
cpsSerialPortModemChatmandatory The initchat send to modem connected. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.37 |
cpsSerialPortSttyCmdmandatory The tty settings after socket connection is established. | OctetStringr/w Constraints: range: 0-180 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.38 |
cpsSerialPortSockTxmandatory Defines the delay (in milliseconds) before transmission tothe Ethernet of data received through a serial port. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.39 |
cpsSerialPortSockPollmandatory Keep-alive timer (milliseconds) for the TCP connection. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.40 |
cpsSerialPortSockIdlemandatory The idle timeout in seconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.41 |
cpsSerialPortDBsizemandatory Maximum size of the data buffering file. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.42 |
cpsSerialPortDBtimemandatory Timestamp in data buffering.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.43 |
cpsSerialPortDBmodemandatory Data buffering mode : circ or line. | OctetStringr/w Constraints: range: 0-5 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.44 |
cpsSerialPortDBsyslogmandatory Size of the data buffer sent to syslog. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.45 |
cpsSerialPortDBmenumandatory Menu type for data buffering.0 will indicate display Menu, 1 will indicate inactive, 2 will indicate DB, 3 will indicate Parc. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.46 |
cpsSerialPortDBalarmmandatory Alarm generation status.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.47 |
cpsSerialPortSSHbreakmandatory Break sequence - ssh session. | OctetStringr/w Constraints: range: 0-16 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.48 |
cpsSerialPortSniffSessmandatory Sniff session type. | OctetStringr/w Constraints: range: 0-5 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.49 |
cpsSerialPortSniffAdmmandatory List of admin users allowed to sniff session. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.50 |
cpsSerialPortSniffEscmandatory Escape sequence used in sniff session. | OctetStringr/w Constraints: range: 0-6 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.51 |
cpsSerialPortSniffMsessmandatory | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.52 |
cpsSerialPortTelnetModemandatory Mode negotiated by client telnet with the server.0 will indicate text, 1 will indicate binary. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.53 |
cpsSerialPortSysBufSessmandatory Syslog Buffering at all times.0 will indicate yes, 1 will indicate no. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.54 |
cpsSerialPortLFSuppressmandatory LF suppression in socket_server session.0 will indicate inactive, 1 will indicate active. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.55 |
cpsSerialPortAutoInputmandatory Input string used for auto answer. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.56 |
cpsSerialPortAutoOutputmandatory Output string used for auto answer. | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.57 |
cpsSerialPortBreakIntervalmandatory The break interval in milliseconds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.58 |
.1.3.6.1.4.1.318.1.1.19.1.3.1
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk cpsInfoSerialPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::cpsInfoSerialPortTable'
This is the information of the specific serial port.
One particular serial port.
Indexes
| Column | Syntax | OID |
|---|---|---|
cpsInfoSerialPortNumbermandatory Number to identify the serial port. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.1 |
cpsInfoSerialPortTtymandatory The device name for the serial port. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.2 |
cpsInfoSerialPortNamemandatory Alias name given to the server connected to the serial port. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.3 |
cpsInfoSerialPortSpeedmandatory The speed for serial port. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.4 |
cpsInfoSerialPortTxBytesmandatory The number of transmitted bytes by the serial port. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.5 |
cpsInfoSerialPortRXBytesmandatory The number of received bytes by the serial port. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.6 |
cpsInfoSerialPortErrFramemandatory The number of frame errors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.7 |
cpsInfoSerialPortErrParitymandatory The number of parity errors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.8 |
cpsInfoSerialPortErrBreaksmandatory The number of breaks errors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.9 |
cpsInfoSerialPortErrOverrunmandatory The number of overrun errors. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.10 |
cpsInfoSerialPortSigDTRmandatory The state of the DTR signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.11 |
cpsInfoSerialPortSigCDmandatory The state of the DCD signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.12 |
cpsInfoSerialPortSigDSRmandatory The state of the DSR signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.13 |
cpsInfoSerialPortSigRTSmandatory The state of the RTS signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.14 |
cpsInfoSerialPortSigCTSmandatory The state of the CTS signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.15 |
cpsInfoSerialPortSigRImandatory The state of the RI signal.0 will indicate down, 1 will indicate up. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.19.1.3.1.1.16 |
.1.3.6.1.4.1.318.1.1.22.1.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistInfoTable'
Allows for getting information about the modular distribution metering equipment.
An entry containing information about an individual metering segment.
Indexes
| Column | Syntax | OID |
|---|---|---|
isxModularDistInfoSegmentIndexmandatory The index of the metering segment. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.1.2.1.1 |
isxModularDistInfoMeterModelNumbermandatory The model number of the metering board for this segment. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.1.2.1.2 |
isxModularDistInfoMeterSerialNumbermandatory The serial number of the metering board for this segment. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.1.2.1.3 |
| The date of manufacture for the metering board for this segment, in the format mm/dd/yyyy. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.1.2.1.4 |
isxModularDistInfoMeterFirmwareRevmandatory The firmware revision number of the metering board for this segment. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.1.2.1.5 |
isxModularDistInfoMeterHardwareRevmandatory The hardware revision number of the metering board for this segment. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.1.2.1.6 |
.1.3.6.1.4.1.318.1.1.22.2.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistModuleInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistModuleInfoTable'
Allows for getting basic information about the distribution modules installed in the system.
An entry containing information about a specific distribution module.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
isxModularDistModuleInfoModIndexmandatory The number of the distribution module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.2.1.1 | ||||||||||
isxModularDistModuleInfoAlarmStatusmandatory The status of this module. This reflects the indicator lamp(s) on the front of the module.A value of notPresent indicates that the module is not installed. A value of unknown indicates that there is no communication wi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.2.1.2 | ||||||||||
isxModularDistModuleInfoModelNumbermandatory The model number of the distribution module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.2.2.1.3 | ||||||||||
isxModularDistModuleInfoSerialNumbermandatory The serial number of the distribution module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.2.2.1.4 | ||||||||||
| The date that the distribution module was manufactured. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.2.2.1.5 | ||||||||||
isxModularDistModuleInfoNumCablesmandatory The number of cables provided by this distribution module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.22.2.4
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistModuleBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistModuleBreakerTable'
Allows for getting operational information about the distribution modules.
An entry containing information about a specific distribution modules and circuit breakers.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistModuleBreakerModIndexmandatory The distribution module number. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.1 | ||||||
| The index to an individual breaker in the distribution module. The index also corresponds to the system phase to which the breaker is attached. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.4.1.2 | ||||||
| This is a bit map representing the active alarms for this breaker: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceeded (wa… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.3 | ||||||
isxModularDistModuleBreakerRatingmandatory The current rating of the breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.4 | ||||||
| Numeric value used to indicate that a breaker is a part of a multi-pole breaker. Breakers within a distribution module, with equivalent physical group numbers, may have their handles physically tied together. A value of… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.5 | ||||||
isxModularDistModuleBreakerCableNummandatory Numeric value used to indicate the distribution cable to whichthis breaker is connected. These distribution cables are described in the table isxModularDistModuleOutputTable, and indexed by the OID isxModularDistModule… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.6 | ||||||
isxModularDistModuleBreakerPositionmandatory The physical status of this breaker pole, either closed or open (including tripped). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.4.1.7 | ||||||
| Enable or disable breaker position alarms for this circuit breaker. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.4.1.8 | ||||||
isxModularDistModuleBreakerCurrentmandatory The current flowing though this breaker. Measured in tenths of amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.9 | ||||||
isxModularDistModuleBreakerPercentmandatory The loading on this breaker as a percentage of the breaker's current rating.Expressed in tenths of percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.10 | ||||||
isxModularDistModuleBreakerPowermandatory The power being supplied through this breaker. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.4.1.11 |
.1.3.6.1.4.1.318.1.1.22.2.6
·
1 row entry
·
23 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistModuleOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistModuleOutputTable'
Allows for getting and setting information related to the load equipment being fed by the distribution modules in the ISX Modular Distribution System.
An entry containing information about a specific distribution module
and its output distribution cables.
and its output distribution cables.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
isxModularDistModuleOutputModIndexmandatory The number of the distribution module supplying power to the load equipment. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.1 | ||||||||||
isxModularDistModuleOutputNumCablesmandatory The number of distribution cables provided by this module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.2 | ||||||||||
isxModularDistModuleOutputCordIndexmandatory The index of an individual distribution cable supplied by this module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.3 | ||||||||||
isxModularDistModuleOutputNamemandatory A string describing the load equipment being supplied by this distribution cable. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.22.2.6.1.4 | ||||||||||
isxModularDistModuleOutputLocationmandatory A string describing the location of equipment being supplied by distribution cable. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.22.2.6.1.5 | ||||||||||
isxModularDistModuleOutputStatusmandatory This reflects the worse case severity for alarms associated with this distribution cable.A value of notPresent indicates that the cable does not exist for this module. A value of unknown indicates that the there is no … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.6 | ||||||||||
| Enable or disable all alarm generation related to this distribution cable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.7 | ||||||||||
isxModularDistModuleOutputBreakerMapmandatory This is a bit map representing the breaker poles within themodule that are associated with this distribution cable. The following 3 bits are used to indicate the indices of the breakers feeding the cable: … | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.8 | ||||||||||
| When the current drops below this value a critical alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.9 | ||||||||||
| When the current drops below this value a warning alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.10 | ||||||||||
| When the current exceeds this value a warning alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.11 | ||||||||||
| When the current exceeds this value a critical alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.12 | ||||||||||
| Enable or disable minimum current alarm generation for this distribution cable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.13 | ||||||||||
| Enable or disable low current alarm generation for this distribution cable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.14 | ||||||||||
| Enable or disable high current alarm generation for this distribution cable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.15 | ||||||||||
| Enable or disable maximum current alarm generation for this distribution cable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.16 | ||||||||||
| The length of this distribution cable. Specified in tenths of meters. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.17 | ||||||||||
| A string describing the connector on the end of this distribution cable. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.2.6.1.18 | ||||||||||
| This is a bit map representing the voltages that are available at the connector. 6 bits are used to indicate the following: b0 - L1 b1 - L2 b2 - L3 b3 - L1-2 b4 - L2-3 b5 - L3-1 | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.19 | ||||||||||
isxModularDistModuleOutputTotalPowermandatory The total power being consumed by the load equipment supplied by this distribution cable.Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.20 | ||||||||||
isxModularDistModuleOutputKwhUsagemandatory The total energy consumed by the load equipment fed by this distribution cable.This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate OID, and may be cleared using the isxModularDistMo… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.2.6.1.21 | ||||||||||
isxModularDistModuleOutputKwhResetmandatory Writing yes to this OID will reset the total kWh usage shownin the isxModularDistModuleOutputKwhUsage OID. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.2.6.1.22 | ||||||||||
| The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.2.6.1.23 |
.1.3.6.1.4.1.318.1.1.22.3.2
·
1 row entry
·
20 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistSubFeedInfoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSubFeedInfoTable'
Allows for getting information about distribution subfeed breakers.
An entry containing information about a specific distribution subfeed.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistSubFeedInfoSubIndexmandatory The index of an individual subfeed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.1 | ||||||
isxModularDistSubFeedInfoNamemandatory A string describing the load equipment being supplied by this subfeed. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.22.3.2.1.2 | ||||||
isxModularDistSubFeedInfoLocationmandatory A string describing the location of the equipment being supplied by this subfeed. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.22.3.2.1.3 | ||||||
| The current rating of this subfeed breaker. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.4 | ||||||
| The operational status of this breaker, either closed or open (including tripped). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.5 | ||||||
isxModularDistSubFeedInfoAlarmStatusmandatory The worst case alarm status for this subfeed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.6 | ||||||
| Enable or disable all alarm generation related to this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.7 | ||||||
| When the current drops below this value a critical alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.8 | ||||||
| When the current drops below this value a warning alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.9 | ||||||
| When the current exceeds this value a warning alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.10 | ||||||
| When the current exceeds this value a critical alarm will exist. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.11 | ||||||
| Enable or disable minimum current alarm generation for this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.12 | ||||||
| Enable or disable low current alarm generation for this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.13 | ||||||
| Enable or disable high current alarm generation for this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.14 | ||||||
| Enable or disable maximum current alarm generation for this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.15 | ||||||
| Enable or disable breaker position alarms for this subfeed. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.16 | ||||||
isxModularDistSubFeedInfoTotalPowermandatory The total power being supplied by this subfeed. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.17 | ||||||
isxModularDistSubFeedInfoKwhUsagemandatory The total energy consumed by the load equipment fed by this subfeed.This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate OID, and may be cleared using the isxModularDistSubFeedInfoKwh… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.2.1.18 | ||||||
isxModularDistSubFeedInfoKwhResetmandatory Writing yes to this OID will reset the total kWh usage shownin the isxModularDistSubFeedInfoKwhUsage OID. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.2.1.19 | ||||||
| The date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.22.3.2.1.20 |
.1.3.6.1.4.1.318.1.1.22.3.4
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistSubFeedLoadingTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSubFeedLoadingTable'
Allows for getting subfeed phase loading information.
An entry containing data for an individual subfeed.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistSubFeedLoadingSubIndexmandatory The index of an individual subfeed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.4.1.1 | ||||||
| Description of each input phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.3.4.1.2 | ||||||
| This is a bit map representing the active alarms for this subfeed: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceeded (wa… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.4.1.3 | ||||||
isxModularDistSubFeedLoadingCurrentmandatory The current flowing though this subfeed phase. Measured in tenths of amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.4.1.4 | ||||||
isxModularDistSubFeedLoadingPercentmandatory The loading on this subfeed phase as a percentage of the subfeed's current rating.Expressed in tenths of percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.4.1.5 | ||||||
isxModularDistSubFeedLoadingPowermandatory The power being supplied by this subfeed phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.3.4.1.6 |
.1.3.6.1.4.1.318.1.1.22.4.1.15
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistSysVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysVoltageTable'
Allows for getting the system output voltage information.
An entry containing data for an individual system output phase.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistSysVoltagePhaseIndexmandatory Description of each phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.4.1.15.1.1 | ||||||
isxModularDistSysVoltageAlarmStatusmandatory This is a bit map representing the active alarms for this output phase:b0 - Minimum voltage threshold exceeded (critical) b1 - Low voltage threshold exceeded (warning) b2 - High voltage threshold exceede… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.1.15.1.2 | ||||||
isxModularDistSysVoltageLtoNmandatory Line-to-neutral system output voltage available at the distribution panel.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.1.15.1.3 | ||||||
isxModularDistSysVoltageLtoLmandatory Line-to-line system output voltage available at the distribution panel.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.1.15.1.4 |
.1.3.6.1.4.1.318.1.1.22.4.2.11
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistSysCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysCurrentTable'
Allows for getting the total system phase current information.
An entry containing data for an individual system output phase.
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistSysCurrentPhaseIndexmandatory Description of each phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.4.2.11.1.1 | ||||||
isxModularDistSysCurrentAlarmStatusmandatory This is a bit map representing the active alarms for this output phase:b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warning) b2 - High current threshold exceede… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.2.11.1.2 | ||||||
isxModularDistSysCurrentAmpsmandatory The current flowing though this system output phase. Measured in tenths of amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.2.11.1.3 | ||||||
isxModularDistSysCurrentPercentmandatory The loading on this system output phase as a percentage of the panel current rating.Expressed in tenths of percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.2.11.1.4 |
.1.3.6.1.4.1.318.1.1.22.4.3.5
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk isxModularDistSysPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistSysPowerTable'
Allows for getting the total system phase power loading information.
An entry containing data for an individual system output phase.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
isxModularDistSysPowerPhaseIndexmandatory Description of each phase entry in the table. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.22.4.3.5.1.1 | ||||||
isxModularDistSysPowerKwmandatory The power being supplied by this system output phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.3.5.1.2 | ||||||
isxModularDistSysPowerKwhPhaseUsagemandatory The energy consumed by the load equipment on this system output phase.This is the total since the date specified in the isxModularDistSysPowerKwhResetDate OID, and may be cleared using the isxModularDistSysPowerKwhRese… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.22.4.3.5.1.3 |
.1.3.6.1.4.1.318.1.1.25.1.2
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioSensorStatusTable'
Allows for getting sensor status information.
The unit from which to get data.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
uioSensorStatusPortIDmandatory The ID of the port to which the sensor is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.1 | ||||||||
uioSensorStatusSensorIDmandatory The ID of the sensor. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.2 | ||||||||
uioSensorStatusSensorNamemandatory The sensor name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.1.2.1.3 | ||||||||
uioSensorStatusSensorLocationmandatory The location of the sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.1.2.1.4 | ||||||||
uioSensorStatusTemperatureDegFmandatory The sensor's current temperature reading in degrees Fahrenheit.-1 indicates an invalid reading due to lost communications. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.5 | ||||||||
uioSensorStatusTemperatureDegCmandatory The sensor's current temperature reading in degrees Celsius.-1 indicates an invalid reading due to lost communications. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.6 | ||||||||
uioSensorStatusHumiditymandatory The sensor's current humidity reading in percent relativehumidity. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.7 | ||||||||
uioSensorStatusViolationStatusmandatory The violation status of the sensor. This integer should be interpretedas a bit map, with each bit representing the presence or absence of the specific alarm conditions listed below. The bit will be '1' if the conditi… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.2.1.8 | ||||||||
uioSensorStatusAlarmStatusmandatory The alarm status of the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.2.1.9 | ||||||||
uioSensorStatusCommStatusmandatory The communications status of the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.2.1.10 |
.1.3.6.1.4.1.318.1.1.25.1.4
·
1 row entry
·
22 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioSensorConfigTable'
Allows for configuring the sensor.
The sensor from which to get configuration.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
uioSensorConfigPortIDmandatory The ID of the port to which the sensor is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.1 | ||||
uioSensorConfigSensorIDmandatory The ID of the sensor. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.2 | ||||
uioSensorConfigSensorNamemandatory The sensor name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.1.4.1.3 | ||||
uioSensorConfigSensorLocationmandatory The location of the sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.1.4.1.4 | ||||
| The minimum (critical) temperature alarm threshold for the probe in degrees C. Must be lower than the low threshold to ensure proper sensor alarm behavior. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.5 | ||||
| The low (warning) temperature alarm threshold for the probe in degrees C. Must be higher than the minimum threshold and lower than the high threshold to ensure proper sensor alarm behavior. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.6 | ||||
| The high (warning) temperature alarm threshold for the probe in degrees C. Must be lower than the maximum threshold and higher than the low threshold to ensure proper sensor alarm behavior. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.7 | ||||
| The maximum (critical) temperature alarm threshold for the probe in degrees C. Must be higher than the high threshold to ensure proper sensor alarm behavior. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.8 | ||||
uioSensorConfigTemperatureHysteresismandatory The number of degrees C beyond the temperature thresholds atwhich an active temperature alarm will be cleared. This value applies to all temperature thresholds. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.9 | ||||
uioSensorConfigMinTemperatureEnablemandatory The minimum temperature alarm enable/disable for the sensor.1 - disabled 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.10 | ||||
uioSensorConfigLowTemperatureEnablemandatory The low temperature alarm enable/disable for the sensor.1 - disabled 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.11 | ||||
uioSensorConfigHighTemperatureEnablemandatory The high temperature alarm enable/disable for the sensor.1 - disabled 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.12 | ||||
uioSensorConfigMaxTemperatureEnablemandatory The maximum temperature alarm enable/disable for the sensor.1 - disabled 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.13 | ||||
uioSensorConfigMinHumidityThresholdmandatory The minimum (critical) humidity alarm threshold for theprobe in percent relative humidity. Must be lower than the low threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.14 | ||||
uioSensorConfigLowHumidityThresholdmandatory The low (warning) humidity alarm threshold for the probe inpercent relative humidity. Must be higher than the minimum threshold and lower than the high threshold to ensure proper sensor alarm behavior. -1 if the sensor… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.15 | ||||
uioSensorConfigHighHumidityThresholdmandatory The high (warning) humidity alarm threshold for the probe inpercent relative humidity. Must be lower than the maximum threshold and higher than the low threshold to ensure proper sensor alarm behavior. -1 if the sensor… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.16 | ||||
uioSensorConfigMaxHumidityThresholdmandatory The maximum (critical) humidity alarm threshold for theprobe in percent relative humidity. Must be higher than the high threshold to ensure proper sensor alarm behavior. -1 if the sensor doesn't read humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.17 | ||||
uioSensorConfigHumidityHysteresismandatory The number of percent relative humidity beyond the humiditythresholds at which an active humidity alarm will be cleared. This value applies to all humidity thresholds. -1 if the sensor doesn't read humidity. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.1.4.1.18 | ||||
uioSensorConfigMinHumidityEnablemandatory The minimum humidity alarm enable/disable for the sensor.1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.19 | ||||
uioSensorConfigLowHumidityEnablemandatory The low humidity alarm enable/disable for the sensor.1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.20 | ||||
uioSensorConfigHighHumidityEnablemandatory The high humidity alarm enable/disable for the sensor.1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.21 | ||||
uioSensorConfigMaxHumidityEnablemandatory The maximum humidity alarm enable/disable for the sensor.1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.1.4.1.22 |
.1.3.6.1.4.1.318.1.1.25.2.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioInputContactStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioInputContactStatusTable'
Allows for getting input contact status information.
The input contact from which to get data.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
uioInputContactStatusPortIDmandatory The ID of the port to which the input contact is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.2.2.1.1 | ||||||||
uioInputContactStatusContactIDmandatory The ID of the input contact on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.2.2.1.2 | ||||||||
uioInputContactStatusContactNamemandatory The input contact name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.2.2.1.3 | ||||||||
uioInputContactStatusContactLocationmandatory The location of the input contact. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.2.2.1.4 | ||||||||
uioInputContactStatusCurrentStatemandatory The current state of the input contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.2.1.5 | ||||||||
uioInputContactStatusAlarmStatusmandatory The alarm status of the input contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.2.1.6 | ||||||||
uioInputContactStatusCommStatusmandatory The communications status of the input contact. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.2.1.7 |
.1.3.6.1.4.1.318.1.1.25.2.4
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioInputContactConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioInputContactConfigTable'
Allows for configuring the input contacts.
The input contact from which to get configuration.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
uioInputContactConfigPortIDmandatory The ID of the port to which the input contact is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.2.4.1.1 | ||||
uioInputContactConfigContactIDmandatory The ID of the input contact on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.2.4.1.2 | ||||
uioInputContactConfigContactNamemandatory The input contact name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.2.4.1.3 | ||||
uioInputContactConfigContactLocationmandatory The location of the input contact. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.2.4.1.4 | ||||
uioInputContactConfigEnablemandatory Enable or disable this input contact.1 - disabled 2 - enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.4.1.5 | ||||
uioInputContactConfigNormalStatemandatory The normal (non-alarm) state of the input contact.1 - normally open 2 - normally closed | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.4.1.6 | ||||
uioInputContactConfigSeveritymandatory The severity of the alarm that this input contact willgenerate in the abnormal state. 1 - critical severity 2 - warning severity | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.2.4.1.7 |
.1.3.6.1.4.1.318.1.1.25.3.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioOutputRelayStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioOutputRelayStatusTable'
Allows for getting output relay status information.
The unit from which to get data.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
uioOutputRelayStatusPortIDmandatory The ID of the port to which the output relay is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.3.2.1.1 | ||||||||
uioOutputRelayStatusRelayIDmandatory The ID of the output relay on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.3.2.1.2 | ||||||||
uioOutputRelayStatusRelayNamemandatory The output relay name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.3.2.1.3 | ||||||||
uioOutputRelayStatusRelayLocationmandatory The location of the output relay. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.3.2.1.4 | ||||||||
uioOutputRelayStatusCurrentStatemandatory The current state of the output relay. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.3.2.1.5 | ||||||||
uioOutputRelayStatusAlarmStatusmandatory The alarm status of the output relay. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.3.2.1.6 | ||||||||
uioOutputRelayStatusCommStatusmandatory The communications status of the output relay. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.3.2.1.7 |
.1.3.6.1.4.1.318.1.1.25.3.4
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioOutputRelayConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioOutputRelayConfigTable'
Allows for configuring the output relay.
The unit from which to get configuration.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
uioOutputRelayConfigPortIDmandatory The ID of the port to which the output relay is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.3.4.1.1 | ||||
uioOutputRelayConfigRelayIDmandatory The ID of the output relay on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.3.4.1.2 | ||||
uioOutputRelayConfigRelayNamemandatory The output relay name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.3.4.1.3 | ||||
uioOutputRelayConfigRelayLocationmandatory The location of the output relay. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.3.4.1.4 | ||||
uioOutputRelayConfigNormalStatemandatory The normal state of the output relay.1 - normally open 2 - normally closed | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.3.4.1.5 | ||||
uioOutputRelayConfigControlStatemandatory Close or open the output relay for testing purposes. Alwaysreturns 1 when read. 1 - close output relay 2 - open output relay | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.3.4.1.6 | ||||
uioOutputRelayConfigDelaymandatory The time a selected alarm condition must exist before theoutput relay is activated. Valid values are whole seconds from 0 to 65535. | RFC1155-SMITimeTicksr/w Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.25.3.4.1.7 | ||||
uioOutputRelayConfigHoldmandatory The minimum time the output relay remains activated after thealarm occurs. Valid values are whole seconds from 0 to 65535. | RFC1155-SMITimeTicksr/w Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.25.3.4.1.8 |
.1.3.6.1.4.1.318.1.1.25.4.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioSpotFluidSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioSpotFluidSensorStatusTable'
Allows for getting fluid sensor status information.
The unit from which to get data.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
uioSpotFluidSensorStatusPortIDmandatory The ID of the port to which the fluid sensor is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.4.2.1.1 | ||||||||
uioSpotFluidSensorStatusSensorIDmandatory The ID of the fluid sensor on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.4.2.1.2 | ||||||||
uioSpotFluidSensorStatusSensorNamemandatory The fluid sensor name. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.4.2.1.3 | ||||||||
| The location of the fluid sensor. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.25.4.2.1.4 | ||||||||
uioSpotFluidSensorStatusCurrentStatemandatory The current state of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.4.2.1.5 | ||||||||
uioSpotFluidSensorStatusAlarmStatusmandatory The alarm status of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.4.2.1.6 | ||||||||
uioSpotFluidSensorStatusCommStatusmandatory The communications status of the fluid sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.25.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.25.4.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk uioSpotFluidSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::uioSpotFluidSensorConfigTable'
Allows for configuring the fluid sensor.
The unit from which to get configuration.
| Column | Syntax | OID |
|---|---|---|
uioSpotFluidSensorConfigPortIDmandatory The ID of the port to which the fluid sensor is attached. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.4.4.1.1 |
uioSpotFluidSensorConfigSensorIDmandatory The ID of the fluid sensor on the module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.25.4.4.1.2 |
uioSpotFluidSensorConfigSensorNamemandatory The fluid sensor name. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.4.4.1.3 |
| The location of the fluid sensor. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.25.4.4.1.4 |
.1.3.6.1.4.1.318.1.1.26.2
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2IdentTable'
A table of Rack PDU identification data
Identification data from Rack PDU being queried
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2IdentIndexmandatory The index to the Rack PDU identification tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.2.1.1 |
rPDU2IdentModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.2.1.2 |
rPDU2IdentNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.3 |
rPDU2IdentLocationmandatory A user-defined string identifying the locationof the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.4 |
rPDU2IdentHardwareRevmandatory The Rack PDU hardware version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.5 |
rPDU2IdentFirmwareRevmandatory The Rack PDU firmware version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.6 |
rPDU2IdentDateOfManufacturemandatory The date the Rack PDU was manufacturedin mm/dd/yyyy format | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.7 |
rPDU2IdentModelNumbermandatory The Rack PDU model number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.8 |
rPDU2IdentSerialNumbermandatory The Rack PDU serial number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.9 |
rPDU2IdentContactmandatory A user-defined string identifying theperson to contact regarding the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.10 |
rPDU2IdentBootMonitorRevmandatory The Rack PDU Boot Monitor version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.11 |
rPDU2IdentLongDescriptionmandatory The Rack PDU Long Description name | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.12 |
rPDU2IdentNMCSerialNumbermandatory The Rack PDU Network Management Card (NMC) serial number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.13 |
rPDU2IndentAppBuildDatemandatory The Rack PDU Application build date | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.14 |
rPDU2IndentAOSBuildDatemandatory The Rack PDU AOS build date | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.15 |
rPDU2IndentBootMonBuildDatemandatory The Rack PDU Boot Monitor build date | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.16 |
.1.3.6.1.4.1.318.1.1.26.4.1
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2DeviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2DeviceConfigTable'
A table of Rack PDU configuration data
Configuration data from Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2DeviceConfigIndexmandatory The index to the Rack PDU table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.1 | ||||||
rPDU2DeviceConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.2 | ||||||
rPDU2DeviceConfigNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.3 | ||||||
rPDU2DeviceConfigLocationmandatory A user-defined string identifying the locationof the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.4 | ||||||
rPDU2DeviceConfigDisplayOrientationmandatory Indicates the intended physical orientationof the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.5 | ||||||
rPDU2DeviceConfigColdstartDelaymandatory The amount of delay, measured in seconds, betweenwhen power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.6 | ||||||
| User-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.7 | ||||||
| User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.8 | ||||||
| User-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.9 | ||||||
| Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value. Models that do … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.10 | ||||||
rPDU2DeviceConfigDeviceEnergyResetmandatory Setting this OID to reset (2) will cause the device energy meter valueto be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.11 | ||||||
rPDU2DeviceConfigOutletsEnergyResetmandatory Setting this OID to reset (2) will cause the all outlet energy meter valuesto be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not sup… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.12 | ||||||
| Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not suppor… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.13 | ||||||
rPDU2DeviceConfigContactmandatory A user-defined string identifying theperson to contact regarding the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.14 |
.1.3.6.1.4.1.318.1.1.26.4.2
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2DevicePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2DevicePropertiesTable'
A table of Rack PDU properties
Properties of the Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DevicePropertiesIndexmandatory The index to the Rack PDU properties table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.1 | ||||||||||||||||||||
rPDU2DevicePropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.2 | ||||||||||||||||||||
rPDU2DevicePropertiesNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.2.1.3 | ||||||||||||||||||||
rPDU2DevicePropertiesNumOutletsmandatory The number of outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.4 | ||||||||||||||||||||
| The number of switched outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.5 | ||||||||||||||||||||
| The number of metered outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.6 | ||||||||||||||||||||
rPDU2DevicePropertiesNumPhasesmandatory The number of phases present in the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.7 | ||||||||||||||||||||
rPDU2DevicePropertiesNumMeteredBanksmandatory The number of metered banks present in the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.8 | ||||||||||||||||||||
| The maximum current rating, measured in Amps, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.9 | ||||||||||||||||||||
rPDU2DevicePropertiesOrientationmandatory Rack PDU orientation | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.2.1.10 | ||||||||||||||||||||
rPDU2DevicePropertiesOutletLayoutmandatory Getting this OID will return outlet layout for the device.seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for single phase SKUs, all outlets 1-N … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.2.1.11 | ||||||||||||||||||||
| The maximum current rating, measured in Amps, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.12 | ||||||||||||||||||||
| The maximum power rating, measured in tenths of kilowatts, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.13 |
.1.3.6.1.4.1.318.1.1.26.4.3
·
1 row entry
·
18 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2DeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2DeviceStatusTable'
A table of Rack PDU status information
Status information from the Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DeviceStatusIndexmandatory The index to the Rack PDU status table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.1 | ||||||||||
rPDU2DeviceStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.2 | ||||||||||
rPDU2DeviceStatusNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.3 | ||||||||||
rPDU2DeviceStatusLoadStatemandatory Indicates the present load status of the Rack PDU.Models that do not support this feature will respond to this OID with a value of notsupported (5). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.4 | ||||||||||
rPDU2DeviceStatusPowermandatory The power consumption of the Rack PDU load in hundredths of kilowatts.Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.5 | ||||||||||
rPDU2DeviceStatusPeakPowermandatory The peak power consumption of the Rack PDU load in hundredths of kilowatts.Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.6 | ||||||||||
rPDU2DeviceStatusPeakPowerTimestampmandatory Indicates the date and time that peak power consumption occurred.Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.7 | ||||||||||
rPDU2DeviceStatusPeakPowerStartTimemandatory Indicates the date and time of the last device peak power reset.Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.8 | ||||||||||
rPDU2DeviceStatusEnergymandatory A user resettable energy meter measuring Rack PDU loadenergy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.9 | ||||||||||
rPDU2DeviceStatusEnergyStartTimemandatory Indicates the date and time of the last device energymeter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.10 | ||||||||||
rPDU2DeviceStatusCommandPendingmandatory Indicates whether or not the deviceis processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cyc… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.11 | ||||||||||
rPDU2DeviceStatusPowerSupplyAlarmmandatory Indicates a power supply alarm is active when valueequals alarm (2) | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.12 | ||||||||||
rPDU2DeviceStatusPowerSupply1Statusmandatory Indicates whether or not an alarm is active in PowerSupply 1 | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.13 | ||||||||||
rPDU2DeviceStatusPowerSupply2Statusmandatory Indicates whether or not an alarm is active in PowerSupply 2 | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.14 | ||||||||||
| Indicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.15 | ||||||||||
rPDU2DeviceStatusApparentPowermandatory The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.16 | ||||||||||
rPDU2DeviceStatusPowerFactormandatory The power factor of the Rack PDU load in hundredths. Models that do not support this featurewill respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.17 | ||||||||||
rPDU2DeviceStatusNPSTypemandatory The device NPS status:notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group. Only one Rack PDU in an NPS group is allowed to be the ho… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.18 |
.1.3.6.1.4.1.318.1.1.26.4.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2DeviceControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2DeviceControlTable'
A table of Rack PDU control data
Control data from Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DeviceControlIndexmandatory The index to the Rack PDU control table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.4.1.1 | ||||||||||||||||
rPDU2DeviceControlModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.4.1.2 | ||||||||||||||||
rPDU2DeviceControlNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.4.1.3 | ||||||||||||||||
rPDU2DeviceControlCommandmandatory Setting this OID to immediateAllOn (1) will turn all outletson immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.4.1.4 |
.1.3.6.1.4.1.318.1.1.26.6.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2PhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2PhaseConfigTable'
A table of Rack PDU phase configuration data
Configuration data from currently queried Rack
PDU phase
PDU phase
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2PhaseConfigIndexmandatory The index to the Rack PDU phase configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.1 | ||||||||
rPDU2PhaseConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.2 | ||||||||
rPDU2PhaseConfigNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.3 | ||||||||
rPDU2PhaseConfigOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUphase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alwa… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.1.1.4 | ||||||||
| User-defined low load phase current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.5 | ||||||||
| User-defined near phase overload warning threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.6 | ||||||||
| User-defined phase overload current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.7 | ||||||||
| Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.6.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2PhasePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2PhasePropertiesTable'
A table of Rack PDU phase properties
Properties of the currently queried Rack
PDU phase
PDU phase
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2PhasePropertiesIndexmandatory The index to the Rack PDU phase propertiestable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.1 |
rPDU2PhasePropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.2 |
rPDU2PhasePropertiesNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.3 |
.1.3.6.1.4.1.318.1.1.26.6.3
·
1 row entry
·
12 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2PhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2PhaseStatusTable'
A table of Rack PDU phase status data
Status data from currently queried Rack PDU
phase
phase
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2PhaseStatusIndexmandatory The index to the Rack PDU phase status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.1 | ||||||||
rPDU2PhaseStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.2 | ||||||||
rPDU2PhaseStatusNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.3 | ||||||||
rPDU2PhaseStatusLoadStatemandatory Indicates the present load status of the Rack PDUphase being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.3.1.4 | ||||||||
rPDU2PhaseStatusCurrentmandatory Indicates the current draw, in tenths of Amps, of the loadon the Rack PDU phase being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.5 | ||||||||
rPDU2PhaseStatusVoltagemandatory Indicates the Voltage, in Volts, of the RackPDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.6 | ||||||||
rPDU2PhaseStatusPowermandatory Indicates the load power, in hundredths of kilowatts (kW),consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.7 | ||||||||
rPDU2PhaseStatusApparentPowermandatory Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.8 | ||||||||
rPDU2PhaseStatusPowerFactormandatory Indicates the load power factor, in hundredths,of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.9 | ||||||||
rPDU2PhaseStatusPeakCurrentmandatory The peak current of the Rack PDU phase load in tenths of Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.10 | ||||||||
rPDU2PhaseStatusPeakCurrentTimestampmandatory Indicates the date and time that the peak current occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.6.3.1.11 | ||||||||
rPDU2PhaseStatusPeakCurrentStartTimemandatory Indicates the date and time of the last phase peak current reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.6.3.1.12 |
.1.3.6.1.4.1.318.1.1.26.8.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2BankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2BankConfigTable'
A table of Rack PDU bank configuration data
Configuration data from currently queried
Rack PDU bank
Rack PDU bank
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankConfigIndexmandatory The index to the Rack PDU bank configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.1 | ||||||||
rPDU2BankConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.2 | ||||||||
rPDU2BankConfigNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.3 | ||||||||
rPDU2BankConfigOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUbank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alway… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.1.1.4 | ||||||||
| User-defined low load bank current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.5 | ||||||||
| User-defined near bank overload current warning threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.6 | ||||||||
| User-defined bank overload current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.7 | ||||||||
rPDU2BankConfigBankPeakCurrentResetmandatory Setting this OID to reset (2) will cause the existing peak current valueto be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.8.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2BankPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2BankPropertiesTable'
A table of Rack PDU bank properties
Properties of the currently queried
Rack PDU bank
Rack PDU bank
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankPropertiesIndexmandatory The index to the Rack PDU bank propertiestable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.1 | ||||||||||||
rPDU2BankPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.2 | ||||||||||||
rPDU2BankPropertiesNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.3 | ||||||||||||
rPDU2BankPropertiesPhaseLayoutmandatory This OID describes the outlet phase connections onthe referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to Neutral. seqPhase2ToNeutral(2)… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.8.2.1.4 | ||||||||||||
rPDU2BankPropertiesBreakerRatingmandatory If bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.5 |
.1.3.6.1.4.1.318.1.1.26.8.3
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2BankStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2BankStatusTable'
A table of Rack PDU bank status data
Status data from currently queried Rack PDU
bank
bank
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankStatusIndexmandatory The index to the Rack PDU bank statustable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.1 | ||||||||
rPDU2BankStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.2 | ||||||||
rPDU2BankStatusNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.3 | ||||||||
rPDU2BankStatusLoadStatemandatory Indicates the present load status of the Rack PDUbank being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.3.1.4 | ||||||||
rPDU2BankStatusCurrentmandatory Indicates the current draw, in tenths of Amps, of the loadon the Rack PDU bank being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.5 | ||||||||
rPDU2BankStatusPeakCurrentmandatory The peak current of the Rack PDU bank load in tenths of Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.6 | ||||||||
rPDU2BankStatusPeakCurrentTimestampmandatory Indicates the date and time the bank peak current occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.8.3.1.7 | ||||||||
rPDU2BankStatusPeakCurrentStartTimemandatory Indicates the date and time of the last bank peak current reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.8.3.1.8 |
.1.3.6.1.4.1.318.1.1.26.9.2.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletSwitchedConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletSwitchedConfigTable'
A table of Rack PDU switched outlet configuration data
Configuration data from currently queried
Rack PDU switched outlet
Rack PDU switched outlet
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2OutletSwitchedConfigIndexmandatory The index to the Rack PDU switched outletconfiguration table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 |
rPDU2OutletSwitchedConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 |
rPDU2OutletSwitchedConfigNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 |
rPDU2OutletSwitchedConfigNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 |
rPDU2OutletSwitchedConfigPowerOnTimemandatory The amount of delay, in seconds, between whenpower is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 = Never power on, 0 = immediate power on, and 1-7200 = secon… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 |
| The amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds to delay. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 |
| After turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 |
| User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications… | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.9.2.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletSwitchedPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletSwitchedPropertiesTable'
A table of Rack PDU switched outlet properties
Properties of the currently queried Rack PDU
switched outlet
switched outlet
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedPropertiesIndexmandatory The index to the Rack PDU switched outletproperties table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 | ||||||||||||
rPDU2OutletSwitchedPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 | ||||||||||||
rPDU2OutletSwitchedPropertiesNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 | ||||||||||||
rPDU2OutletSwitchedPropertiesNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 | ||||||||||||
| This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicat… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 | ||||||||||||
rPDU2OutletSwitchedPropertiesBankmandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.26.9.2.3
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletSwitchedStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletSwitchedStatusTable'
A table of Rack PDU switched outlet status information
Status information for currently queried
Rack PDU switched outlet
Rack PDU switched outlet
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedStatusIndexmandatory The index to the Rack PDU switched outletstatus information table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 | ||||||
rPDU2OutletSwitchedStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 | ||||||
rPDU2OutletSwitchedStatusNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 | ||||||
rPDU2OutletSwitchedStatusNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 | ||||||
rPDU2OutletSwitchedStatusStatemandatory Indicates the present switch state of the RackPDU switched outlet being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 | ||||||
| Indicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's po… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 | ||||||
| Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web b… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 |
.1.3.6.1.4.1.318.1.1.26.9.2.4
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletSwitchedControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletSwitchedControlTable'
A table of Rack PDU switched outlet control data
Control data for currently queried Rack
PDU switched outlet
PDU switched outlet
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedControlIndexmandatory The index to the Rack PDU switched outletcontrol data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 | ||||||||||||||||
rPDU2OutletSwitchedControlModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 | ||||||||||||||||
rPDU2OutletSwitchedControlNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 | ||||||||||||||||
rPDU2OutletSwitchedControlNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 | ||||||||||||||||
rPDU2OutletSwitchedControlCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot b… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 |
.1.3.6.1.4.1.318.1.1.26.9.4.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletMeteredConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletMeteredConfigTable'
A table of Rack PDU metered outlet configuration data
Configuration data from currently queried
Rack PDU metered outlet
Rack PDU metered outlet
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2OutletMeteredConfigIndexmandatory The index to the Rack PDU metered outletconfiguration table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 |
rPDU2OutletMeteredConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 |
rPDU2OutletMeteredConfigNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 |
rPDU2OutletMeteredConfigNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 |
| User-defined low load outlet current threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 |
| User-defined near outlet overload warning threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 |
| User-defined outlet overload current threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 |
rPDU2OutletMeteredConfigExternalLinkmandatory User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications… | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.9.4.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletMeteredPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletMeteredPropertiesTable'
A table of Rack PDU metered outlet properties
Properties of currently queried Rack PDU
metered outlet
metered outlet
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletMeteredPropertiesIndexmandatory The index to the Rack PDU metered properties tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 | ||||||||||||
rPDU2OutletMeteredPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 | ||||||||||||
rPDU2OutletMeteredPropertiesNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 | ||||||||||||
rPDU2OutletMeteredPropertiesNumbermandatory The numeric metered outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 | ||||||||||||
rPDU2OutletMeteredPropertiesLayoutmandatory This OID describes the phase connections ofthe referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicat… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 | ||||||||||||
| Maximum power rating of Rack PDU metered outlet | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 | ||||||||||||
rPDU2OutletMeteredPropertiesBankmandatory This outlet's numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.26.9.4.3
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2OutletMeteredStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2OutletMeteredStatusTable'
A table of Rack PDU metered outlet status data
Status data from currently queried Rack PDU
metered outlet
metered outlet
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletMeteredStatusIndexmandatory The index to the Rack PDU metered status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 | ||||||||
rPDU2OutletMeteredStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 | ||||||||
rPDU2OutletMeteredStatusNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 | ||||||||
rPDU2OutletMeteredStatusNumbermandatory The numeric metered outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 | ||||||||
rPDU2OutletMeteredStatusStatemandatory Indicates the present load status of the RackPDU metered outlet being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 | ||||||||
rPDU2OutletMeteredStatusCurrentmandatory Indicates the current draw, in tenthsof Amps, of the load on the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 | ||||||||
rPDU2OutletMeteredStatusPowermandatory Indicates the power draw of the loadon the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 | ||||||||
rPDU2OutletMeteredStatusPeakPowermandatory Indicates the peak power load drawon the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 | ||||||||
| Indicates the date and time that this metered outlet's peak power consumption occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 | ||||||||
| Indicates the start date and time that this metered outlet began recording peak power observations | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 | ||||||||
rPDU2OutletMeteredStatusEnergymandatory A user resettable energy meter measuring Rack PDU loadenergy consumption in tenths of kilowatt-hours | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 | ||||||||
| Indicates receptacle type for the outlet. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 | ||||||||
rPDU2OutletMeteredStatusExternalLinkmandatory Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web br… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 |
.1.3.6.1.4.1.318.1.1.26.10.2.1
·
1 row entry
·
16 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorTempHumidityConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorTempHumidityConfigTable'
A table of temperature-humidity sensor configuration data
Configuration data from temperature-humidity sensor
being queried
being queried
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
rPDU2SensorTempHumidityConfigIndexmandatory The index to the temperature-humidity sensorconfiguration data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 | ||||
rPDU2SensorTempHumidityConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 | ||||
rPDU2SensorTempHumidityConfigNamemandatory The user-defined temperature-humiditysensor ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 | ||||
rPDU2SensorTempHumidityConfigNumbermandatory The temperature-humidity sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 | ||||
| Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 | ||||
| Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 | ||||
| Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshF will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 | ||||
| Sensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshF will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 | ||||
| Sensor temperature hysteresis setting in Fahrenheit | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 | ||||
| Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshC will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 | ||||
| Sensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshC will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 | ||||
| Sensor temperature hysteresis setting in Celsius | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 | ||||
| Sensor low humidity warning alarm threshold in percent relative humidity. May be 10% to 90%, but must be greater than rPDU2SensorTempHumidityConfigHumidityMinThresh. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 | ||||
| Sensor minimum humidity alarm threshold in percent relative humidity. May be 10% to 90%, but must be less than rPDU2SensorTempHumidityConfigHumidityLowThresh. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 | ||||
| Sensor humidity hysteresis setting in percent relative humidity | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 | ||||
| Setting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 |
.1.3.6.1.4.1.318.1.1.26.10.2.2
·
1 row entry
·
15 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorTempHumidityStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorTempHumidityStatusTable'
A table of temperature-humidity sensor status data
Status information from temperature-humidity sensor
being queried
being queried
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2SensorTempHumidityStatusIndexmandatory The index to the temperature-humiditystatus data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 | ||||||||||||
rPDU2SensorTempHumidityStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 | ||||||||||||
rPDU2SensorTempHumidityStatusNamemandatory The user-defined temperature-humiditysensor ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 | ||||||||||||
rPDU2SensorTempHumidityStatusNumbermandatory The temperature-humidity sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 | ||||||||||||
rPDU2SensorTempHumidityStatusTypemandatory The type of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 | ||||||||||||
| The communications status of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 | ||||||||||||
rPDU2SensorTempHumidityStatusTempFmandatory Sensor temperature reading in tenths of degrees Fahrenheit | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 | ||||||||||||
rPDU2SensorTempHumidityStatusTempCmandatory Sensor temperature reading in tenths of degrees Celsius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 | ||||||||||||
| This OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured tem… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 | ||||||||||||
| Sensor humidity reading in percent relative humidity | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 | ||||||||||||
| This OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured humidi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 | ||||||||||||
| Sensor peak temperature in tenths of degrees Fahrenheit | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 | ||||||||||||
| Sensor peak temperature in tenths of degrees Celsius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 | ||||||||||||
| Indicates the date and time that the peak temperature occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 | ||||||||||||
| Indicates the date and time of the last temperature peak reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 |
.1.3.6.1.4.1.318.1.1.26.10.4.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorDiscreteConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorDiscreteConfigTable'
A table of discrete sensor configuration data
Configuration data from discreste sensor
being queried
being queried
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2SensorDiscreteConfigIndexmandatory The index to the discrete sensor configurationdata table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 | ||||||
rPDU2SensorDiscreteConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 | ||||||
rPDU2SensorDiscreteConfigNamemandatory The user-defined discrete sensor ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 | ||||||
rPDU2SensorDiscreteConfigNumbermandatory The discrete sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 | ||||||
rPDU2SensorDiscreteConfigNormalStatemandatory Indicates the normal state of the discrete inputcontact | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 | ||||||
| Indicates the severity of alarm triggered by abnormal discrete input contact state | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 |
.1.3.6.1.4.1.318.1.1.26.10.4.2
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorDiscreteStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorDiscreteStatusTable'
A table of discrete sensor status data
Status information from discrete sensor
being queried
being queried
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2SensorDiscreteStatusIndexmandatory The index to the discrete sensor status datatable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 | ||||||||||||||
rPDU2SensorDiscreteStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 | ||||||||||||||
rPDU2SensorDiscreteStatusNamemandatory The user-defined discrete sensor ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 | ||||||||||||||
rPDU2SensorDiscreteStatusNumbermandatory The discrete sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 | ||||||||||||||
rPDU2SensorDiscreteStatusTypemandatory The type of discrete sensor currently being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 | ||||||||||||||
rPDU2SensorDiscreteStatusCommStatusmandatory The communications status of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 | ||||||||||||||
| The current open/close state of the discrete sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 | ||||||||||||||
rPDU2SensorDiscreteStatusAlarmStatemandatory Indicates alarm status of discrete sensor input | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 |
.1.3.6.1.4.1.318.1.1.26.10.6.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorAnalogVoltageStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorAnalogVoltageStatusTable'
A table of voltage sensor status data. Not supported by rPDU series 9000 or older.
Status information from voltage sensor
being queried
being queried
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2SensorAnalogVoltageStatusIndexmandatory The index to the voltage sensor status datatable entry | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.1 | ||||||||||||
rPDU2SensorAnalogVoltageStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.2 | ||||||||||||
rPDU2SensorAnalogVoltageStatusNumbermandatory The voltage sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.3 | ||||||||||||
rPDU2SensorAnalogVoltageStatusNamemandatory The user-defined voltage sensor ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.4 | ||||||||||||
| The communications status of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.6.1.1.5 | ||||||||||||
| Sensor voltage reading in hundredths of volts. Returns -1 for indices without voltage probes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.1.1.6 | ||||||||||||
| This OID reports the current state of the voltage probe: A notPresent (1) response indicates that no probe is attached, or that the attached probe isn't a voltage probe. A belowMin (2) response indicates … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.6.1.1.7 |
.1.3.6.1.4.1.318.1.1.26.10.6.2
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2SensorAnalogVoltageConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2SensorAnalogVoltageConfigTable'
A table of analog voltage sensor configuration data. Not supported by rPDU series 9000 or older.
Configuration data from analog voltage sensor
being queried
being queried
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
rPDU2SensorAnalogVoltageConfigIndexmandatory The index to the voltage sensor configurationdata table entry | Integer32 Constraints: range: 0-255 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.1 | ||||
rPDU2SensorAnalogVoltageConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.2 | ||||
rPDU2SensorAnalogVoltageConfigNumbermandatory The voltage sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.3 | ||||
rPDU2SensorAnalogVoltageConfigNamemandatory The user-defined voltage sensor ID string. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.4 | ||||
| Sensor minimum voltage alarm threshold in hundredths of volts. This value may be as low as zero and must be less than rPDU2SensorAnalogVoltageConfigThreshMax. Returns -1 for indices without voltage probes. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.5 | ||||
| Sensor minimum voltage alarm threshold in hundredths of volts. This value must be greater than rPDU2SensorAnalogVoltageConfigThreshMin and may be as high as 50. Returns -1 for indices without voltage probes. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.6 | ||||
| Sensor voltage hysteresis in hundredths of volts. This value may be 0 to 20. If either of the alarm thresholds are crossed, the measured voltage must recover by this amount before the alarm will be cleared. Returns -1 f… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.6.2.1.7 | ||||
| This OID may be used to enable or disable voltage alarm generation. Disabling alarm generation while alarms are active clears the active alarms. Returns -1 for indices without voltage probes. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.6.2.1.8 |
.1.3.6.1.4.1.318.1.1.26.13.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2PhaseToPhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2PhaseToPhaseStatusTable'
A table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs.
Status data from currently queried Rack PDU
phase to phase outputs
phase to phase outputs
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2PhaseToPhaseStatusIndexmandatory The index to the Rack PDU phase to phase status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.1 |
rPDU2PhaseToPhaseStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.2 |
rPDU2PhaseToPhaseStatusVoltage1to2mandatory Indicates the Voltage, in Volts, of the RackPDU phase 1 to phase 2 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.3 |
rPDU2PhaseToPhaseStatusVoltage2to3mandatory Indicates the Voltage, in Volts, of the RackPDU phase 2 to phase 3 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.4 |
rPDU2PhaseToPhaseStatusVoltage3to1mandatory Indicates the Voltage, in Volts, of the RackPDU phase 3 to phase 2 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.5 |
.1.3.6.1.4.1.318.1.1.26.14.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2AdvBankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2AdvBankConfigTable'
A table of Rack PDU bank configuration data
Configuration data from currently queried
Rack PDU bank
Rack PDU bank
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2AdvBankConfigIndexmandatory The index to the Rack PDU bank configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.1 | ||||||||
rPDU2AdvBankConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.2 | ||||||||
rPDU2AdvBankConfigNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.3 | ||||||||
| This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alway… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.14.1.1.4 | ||||||||
| User-defined low load bank current threshold in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.5 | ||||||||
| User-defined near bank overload current warning threshold in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.6 | ||||||||
| User-defined bank overload current threshold in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.14.1.1.7 | ||||||||
| Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.14.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.15.1
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk rPDU2AdvPhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::rPDU2AdvPhaseConfigTable'
A table of Rack PDU phase configuration data
Configuration data from currently queried Rack
PDU phase
PDU phase
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2AdvPhaseConfigIndexmandatory The index to the Rack PDU phase configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.1 | ||||||||
rPDU2AdvPhaseConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.2 | ||||||||
rPDU2AdvPhaseConfigNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.3 | ||||||||
| This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alwa… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.15.1.1.4 | ||||||||
| User-defined low load phase current threshold measured in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.5 | ||||||||
| User-defined near phase overload warning threshold measured in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.6 | ||||||||
| User-defined phase overload current threshold measured in tenths of Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.7 | ||||||||
| Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.15.1.1.8 |
.1.3.6.1.4.1.318.1.1.27.1.2
·
1 row entry
·
1 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitTable'
A table of cooling unit level data.
An element of coolingUnitTable.
Indexes
| Column | Syntax | OID |
|---|---|---|
coolingUnitTableIndexmandatory The unit reference identifier for this table and all other table entries subordinate to coolingUnits. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.2.1.1 |
.1.3.6.1.4.1.318.1.1.27.1.3.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitAboutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitAboutTable'
A table of unit reference information.
An element of coolingUnitAboutTable.
| Column | Syntax | OID |
|---|---|---|
coolingUnitAboutTableIndexmandatory The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.3.2.1.1 |
coolingUnitAboutDescriptionmandatory A text description of the information presented in coolingUnitAboutValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.3.2.1.2 |
coolingUnitAboutValuemandatory The actual value of the current table entry. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.3.2.1.3 |
.1.3.6.1.4.1.318.1.1.27.1.4.1.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitStatusAnalogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitStatusAnalogTable'
A table of analog unit status data.
An element of coolingUnitStatusAnalogTable.
| Column | Syntax | OID |
|---|---|---|
coolingUnitStatusAnalogTableIndexmandatory The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.1 |
coolingUnitStatusAnalogDescriptionmandatory A text description of the information presented in coolingUnitStatusAnalogValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.2 |
coolingUnitStatusAnalogValuemandatory The scaled value of the current table entry (multiplied by coolingUnitStatusAnalogScale for integer presentation). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3 |
coolingUnitStatusAnalogUnitsmandatory The unit of measure by which coolingUnitStatusAnalogValue is expressed. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.4 |
coolingUnitStatusAnalogScalemandatory The factor by which coolingUnitStatusAnalogValue is expressed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.5 |
.1.3.6.1.4.1.318.1.1.27.1.4.2.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitStatusDiscreteTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitStatusDiscreteTable'
A table of discrete unit status data.
An element of coolingUnitStatusDiscreteTable.
| Column | Syntax | OID |
|---|---|---|
coolingUnitStatusDiscreteTableIndexmandatory The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.1 |
coolingUnitStatusDiscreteDescriptionmandatory A text description of the information presented in this table's 'value' OIDs. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.2 |
| The actual value of the current table entry expressed as a string. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.3 |
| The actual value of the current table entry expressed as an integer value. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.4 |
| A complete listing of all possible coolingUnitStatusDiscreteValueAsInteger values paired with their identifying strings. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.5 |
.1.3.6.1.4.1.318.1.1.27.1.5.1.2
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitConfigurationAnalogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitConfigurationAnalogTable'
A table of analog unit configuration data.
An element of coolingUnitConfigurationAnalogTable.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.1 | ||||
| A text description of the information presented in coolingUnitConfigurationAnalogValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.2 | ||||
coolingUnitConfigurationAnalogValuemandatory The scaled value of the current table entry (multiplied by coolingUnitConfigurationAnalogScale for integer presentation). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3 | ||||
coolingUnitConfigurationAnalogUnitsmandatory The unit of measure by which coolingUnitConfigurationAnalogValue is expressed. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.4 | ||||
coolingUnitConfigurationAnalogScalemandatory The factor by which coolingUnitConfigurationAnalogValue is expressed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.5 | ||||
coolingUnitConfigurationAnalogAccessmandatory A description of available access to coolingUnitConfigurationAnalogValue via SNMP client. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.6 | ||||
| The minimum possible value of coolingUnitConfigurationAnalogValue. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.7 | ||||
| The maximum possible value of coolingUnitConfigurationAnalogValue. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.8 |
.1.3.6.1.4.1.318.1.1.27.1.5.2.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitConfigurationDiscreteTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitConfigurationDiscreteTable'
A table of discrete unit configuration data.
An element of coolingUnitConfigurationDiscreteTable.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.1 | ||||
| A text description of the information presented in this table's 'value' OIDs. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.2 | ||||
| The actual value of the current table entry expressed as a string. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.3 | ||||
| The actual value of the current table entry expressed as an integer value. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.4 | ||||
| A complete listing of all possible coolingUnitConfigurationDiscreteValueAsInteger values paired with their identifying strings. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.5 | ||||
| A description of available access to coolingUnitConfigurationDiscreteValueAsInteger via SNMP client. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.27.1.5.3.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitConfigurationStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitConfigurationStringTable'
A table of unit configuration strings.
An element of coolingUnitConfigurationStringTable.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| The static reference identifier for each table entry. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.1 | ||||
| A text description of the information presented in coolingUnitConfigurationStringValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.2 | ||||
coolingUnitConfigurationStringValuemandatory The actual value of the current table entry. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.3 | ||||
| The maximum string length supported by coolingUnitConfigurationStringValue. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.4 | ||||
coolingUnitConfigurationStringAccessmandatory A description of available access to coolingUnitConfigurationStringValue via SNMP client. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.5 |
.1.3.6.1.4.1.318.1.1.27.1.6.1.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitExtendedAnalogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitExtendedAnalogTable'
A table of secondary analog data for the cooling unit or one of its components.
An element of coolingUnitExtendedAnalogTable.
| Column | Syntax | OID |
|---|---|---|
coolingUnitExtendedAnalogTableIndexmandatory The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.1 |
coolingUnitExtendedAnalogDescriptionmandatory A text description of the information presented in coolingUnitExtendedAnalogValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.2 |
coolingUnitExtendedAnalogValuemandatory The scaled value of the current table entry (multiplied by coolingUnitExtendedAnalogScale for integer presentation). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.3 |
coolingUnitExtendedAnalogUnitsmandatory The unit of measure by which coolingUnitExtendedAnalogValue is expressed. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.4 |
coolingUnitExtendedAnalogScalemandatory The factor by which coolingUnitExtendedAnalogValue is expressed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.5 |
.1.3.6.1.4.1.318.1.1.27.1.6.2.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitExtendedDiscreteTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitExtendedDiscreteTable'
A table of secondary discrete cooling unit data.
An element of coolingUnitExtendedDiscreteTable.
| Column | Syntax | OID |
|---|---|---|
| The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.1 |
| A text description of the information presented in this table's 'value' OIDs. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.2 |
| The actual value of the current table entry expressed as a string. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.3 |
| The actual value of the current table entry expressed as an integer value. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.4 |
| A complete listing of all possible coolingUnitExtendedDiscreteValueAsInteger values paired with their identifying strings. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.5 |
.1.3.6.1.4.1.318.1.1.27.1.6.3.2
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk coolingUnitExtendedStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::coolingUnitExtendedStringTable'
A table of secondary unit reference data.
An element of coolingUnitExtendedStringTable.
| Column | Syntax | OID |
|---|---|---|
coolingUnitExtendedStringTableIndexmandatory The static reference identifier for each table entry. This identifier may reference different table entries in different unit models. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.1 |
coolingUnitExtendedStringDescriptionmandatory A text description of the information presented in coolingUnitExtendedStringValue. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.2 |
coolingUnitExtendedStringValuemandatory The actual value of the current table entry. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.3 |
.1.3.6.1.4.1.318.1.1.28.3.1.2
·
1 row entry
·
56 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmInputTable'
A list of input meter entries.
An entry containing information applicable to a
particular input meter.
particular input meter.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
pmmInputMeterIndexmandatory The input meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.1 | ||||||||||||||||||||
pmmInputFrequencymandatory The input frequency in tenths of Hertz. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.2 | ||||||||||||||||||||
pmmInputTotalActivePowermandatory Shows the total input active power in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.3 | ||||||||||||||||||||
pmmInputTotalApparentPowermandatory Shows the total input apparent power in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.4 | ||||||||||||||||||||
pmmInputTotalPowerFactormandatory Indicates the total power factor. A value of 100 representinga unity power factor (1.00). Specified in hundredths. Returns -255 if unsupported | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.5 | ||||||||||||||||||||
pmmInputActiveEnergyDeliveredmandatory Shows the input active energy delivered in tenths of kWh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.6 | ||||||||||||||||||||
pmmInputActiveEnergyReceivedmandatory Shows the input active energy received in tenths of kWh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.7 | ||||||||||||||||||||
pmmInputApparentEnergyDeliveredmandatory Shows the input apparent energy delivered in tenths of kVAh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.8 | ||||||||||||||||||||
pmmInputApparentEnergyReceivedmandatory Shows the input apparent energy received in tenths of kVAh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.9 | ||||||||||||||||||||
pmmInputFrequencyDeviationmandatory Displays the input frequency deviation in Hertz.Threshold write returns as unsuccessful if one of the breaker threshold groups does not meet conditions. In this case, read the thresholds to know which threshold group… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.1.2.1.10 | ||||||||||||||||||||
pmmInputPowerFactorDeviationmandatory Displays the input power factor deviation. Specified in tenths.A value of zero indicates that the threshold is disabled. Returns -1 if unsupported. Threshold write returns as unsuccessful if one of the breaker threshol… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.11 | ||||||||||||||||||||
pmmInputMinVoltThresholdmandatory Threshold below which an input minimum voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the thr… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.12 | ||||||||||||||||||||
pmmInputLowVoltThresholdmandatory Threshold below which an input low voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the thresho… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.13 | ||||||||||||||||||||
pmmInputHighVoltThresholdmandatory Threshold above which an input high voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the thresh… | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.14 | ||||||||||||||||||||
pmmInputMaxVoltThresholdmandatory Threshold above which an input maximum voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalInputVoltage. A value of zero indicates that the thr… | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.15 | ||||||||||||||||||||
pmmInputMinCurrentThresholdmandatory Threshold below which an input minimum current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsucc… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.16 | ||||||||||||||||||||
pmmInputLowCurrentThresholdmandatory Threshold below which an input low current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccessf… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.17 | ||||||||||||||||||||
pmmInputHighCurrentThresholdmandatory Threshold above which an input high current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsuccess… | Integer32r/w Constraints: range: 0-110 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.18 | ||||||||||||||||||||
pmmInputMaxCurrentThresholdmandatory Threshold above which an input maximum current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. Threshold write returns as unsucc… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.19 | ||||||||||||||||||||
pmmInputMinApparentPowerThresholdmandatory Threshold below which an input minimum apparent power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write re… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.20 | ||||||||||||||||||||
pmmInputMaxApparentPowerThresholdmandatory Threshold above which an input maximum apparent power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write re… | Integer32r/w Constraints: range: 0-110 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.21 | ||||||||||||||||||||
pmmInputOverActivePowerThresholdmandatory Threshold above which an input over active power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. Threshold write returns… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.22 | ||||||||||||||||||||
pmmInputBreakerStatemandatory This value indicates the current state of input breaker.1 will indicate open, 2 will indicate closed, 3 will indicate unknown. Returns -1 if unsupported or failed. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.1.2.1.23 | ||||||||||||||||||||
pmmInputBreakerOpenAlarmmandatory Breaker open alarm status.1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.1.2.1.24 | ||||||||||||||||||||
pmmInputAverageCurrentmandatory Input Average current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.25 | ||||||||||||||||||||
pmmInputNeturalCurrentmandatory Input Neutral current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.26 | ||||||||||||||||||||
| Input maximum instantaneous neutral current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.27 | ||||||||||||||||||||
pmmInputAverageCurrentTHDmandatory Input average harmonic distortions.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.28 | ||||||||||||||||||||
pmmInputAverageVoltageLtoLmandatory Input Average Line to Line voltage. Measured in tenths of Volts.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.29 | ||||||||||||||||||||
pmmInputAverageVoltageLtoNmandatory Input Average Line to Neutral voltage. Measured in tenths of Volts.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.30 | ||||||||||||||||||||
pmmInputLoadmandatory Total load of input breaker in percentage. Measured in tenths of percent.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.31 | ||||||||||||||||||||
pmmInputMeterFirmwareVersionmandatory Shows the input meter firmware version.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.32 | ||||||||||||||||||||
pmmInputMeterSerialNumbermandatory Shows the input meter serial number.Returns -1 if unsupported or failed. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.33 | ||||||||||||||||||||
pmmInputEnergyUsageAccumulatedTotalmandatory Shows the total accumulated input energy usage in kWh.Measured in tenths of kWh. Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.34 | ||||||||||||||||||||
pmmInputPhaseLossmandatory Threshold below which an input phase loss condition will be generated.Specified as a percent deviation from phase to neutral nominal voltage. A value of zero indicates that the threshold is disabled. Returns -1 if unsu… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.35 | ||||||||||||||||||||
pmmInputBreakerCTSizemandatory Shows the input breaker CT size.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.36 | ||||||||||||||||||||
pmmInputBreakerRatingmandatory Shows the input breaker rating in Amps(A).Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.37 | ||||||||||||||||||||
pmmInputKWHResetDatemandatory The date that the kWh usage was reset, in the format mm/dd/yyyy. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.38 | ||||||||||||||||||||
pmmInputAlarmGenerationmandatory Alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.39 | ||||||||||||||||||||
pmmInputVoltageMaximumAlarmmandatory Voltage maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.40 | ||||||||||||||||||||
pmmInputVoltageHighAlarmmandatory Voltage high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.41 | ||||||||||||||||||||
pmmInputVoltageLowAlarmmandatory Voltage low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.42 | ||||||||||||||||||||
pmmInputVoltageMinimumAlarmmandatory Voltage minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.43 | ||||||||||||||||||||
pmmInputCurrentMaximumAlarmmandatory Current maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.44 | ||||||||||||||||||||
pmmInputCurrentHighAlarmmandatory Current high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.45 | ||||||||||||||||||||
pmmInputCurrentLowAlarmmandatory Current low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.46 | ||||||||||||||||||||
pmmInputCurrentMinimumAlarmmandatory Current minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.47 | ||||||||||||||||||||
pmmInputApparentPowerMaximumAlarmmandatory Apparent Power maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.48 | ||||||||||||||||||||
pmmInputApparentPowerMinimumAlarmmandatory Apparent Power minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.49 | ||||||||||||||||||||
pmmInputKWOverAlarmmandatory Over active power alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.50 | ||||||||||||||||||||
pmmInputPhaseLossAlarmmandatory Phase loss alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.51 | ||||||||||||||||||||
pmmInputPowerFactorTotalAlarmmandatory Total power factor alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.52 | ||||||||||||||||||||
pmmInputFrequencyDeviationAlarmmandatory Frequency deviation alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.53 | ||||||||||||||||||||
pmmInputNeutralOverCurrentAlarmmandatory Neutral Overcurrent alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.54 | ||||||||||||||||||||
pmmInputNeutralOverCurrentThresholdmandatory Threshold above which an input neutral overcurrent condition will be generated.Specified as a percent deviation from nominal current. A value of zero indicates that the threshold is disabled. Returns -1 if unsupported … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.55 | ||||||||||||||||||||
pmmInputAveragePowerFactormandatory Indicates the average power factor. A value of 100 representinga unity power factor (1.00). Specified in hundredths. Returns -255 if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.2.1.56 |
.1.3.6.1.4.1.318.1.1.28.3.1.3
·
1 row entry
·
13 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmInputPhaseTable'
A list of input table entries. The number of entries is given by the value of pmmInputMeterTableSize OID.
An entry containing information applicable to a
particular input phase.
particular input phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
pmmInputMeterNummandatory The input meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.1 |
pmmInputPhasemandatory Input phase index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.2 |
pmmInputVoltageLtoLmandatory Line-to-line input voltage available.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.3 |
pmmInputVoltageLtoNmandatory Line-to-neutral input voltage available.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.4 |
pmmInputPhaseCurrentmandatory Input current per phase. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.5 |
pmmInputActivePowermandatory Input active power per phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.6 |
pmmInputApparentPowermandatory Input apparent power per phase. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.7 |
pmmInputPowerFactormandatory Indicates the power factor of the input per phase.A value of 100 representing a unity power factor (1.00). Specified in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.8 |
pmmInputMaxInstantaneousCurrentmandatory Input maximum phase instantaneous current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.9 |
pmmInputPhaseAnglemandatory Current phase Angle. Measured in tenths of decimalReturns -255 if unsupported | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.10 |
pmmInputTHDLtoLmandatory Input harmonic distortions line to line for the present input voltage.Measured in tenths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.11 |
pmmInputTHDLtoNmandatory Input harmonic distortions line to neutral for the present input voltage.Measured in tenths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.12 |
pmmInputCurrentTHDmandatory Input harmonic distortions for each phase, for the present input current.Returns -1 if unsupported or failed. Specified in tenths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.1.3.1.13 |
.1.3.6.1.4.1.318.1.1.28.3.2.2
·
1 row entry
·
25 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmOutputTable'
A list of output meter entries.
An entry containing information applicable to a
particular output meter.
particular output meter.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
pmmOutputMeterIndexmandatory The output meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.1 | ||||||||||||||||||||
pmmOutputFrequencymandatory The output frequency in tenths of Hertz. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.2 | ||||||||||||||||||||
pmmOutputTotalActivePowermandatory Shows the total output active power in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.3 | ||||||||||||||||||||
pmmOutputTotalApparentPowermandatory Shows the total output apparent power in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.4 | ||||||||||||||||||||
pmmOutputTotalPowerFactormandatory Indicates the total power factor. A value of 100 representinga unity power factor (1.00). Specified in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.5 | ||||||||||||||||||||
pmmOutputActiveEnergyDeliveredmandatory Shows the output active energy delivered in tenths of kWh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.6 | ||||||||||||||||||||
pmmOutputActiveEnergyReceivedmandatory Shows the output active energy received in tenths of kWh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.7 | ||||||||||||||||||||
pmmOutputApparentEnergyDeliveredmandatory Shows the output apparent energy delivered in tenths of kVAh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.8 | ||||||||||||||||||||
pmmOutputApparentEnergyReceivedmandatory Shows the output apparent energy received in tenths of kVAh. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.9 | ||||||||||||||||||||
pmmOutputFrequencyDeviationmandatory Shows the output frequency deviation in Hertz. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.2.2.1.10 | ||||||||||||||||||||
pmmOutputPowerFactorDeviationmandatory Shows the output power factor deviation. Specified in tenths.A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.11 | ||||||||||||||||||||
pmmOutputMinVoltThresholdmandatory Threshold below which an output minimum voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the t… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.12 | ||||||||||||||||||||
pmmOutputLowVoltThresholdmandatory Threshold below which an output low voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the thres… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.13 | ||||||||||||||||||||
pmmOutputHighVoltThresholdmandatory Threshold above which an output high voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the thre… | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.14 | ||||||||||||||||||||
pmmOutputMaxVoltThresholdmandatory Threshold above which an output maximum voltage conditionwill be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the t… | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.15 | ||||||||||||||||||||
pmmOutputMinCurrentThresholdmandatory Threshold below which an output minimum current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.16 | ||||||||||||||||||||
pmmOutputLowCurrentThresholdmandatory Threshold below which an output low current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.17 | ||||||||||||||||||||
pmmOutputHighCurrentThresholdmandatory Threshold above which an output high current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-110 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.18 | ||||||||||||||||||||
pmmOutputMaxCurrentThresholdmandatory Threshold above which an output maximum current condition will be generated.Specified as a percent of the panel breaker rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.19 | ||||||||||||||||||||
pmmOutputMinApparentPowerThresholdmandatory Threshold below which an output minimum apparent power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.20 | ||||||||||||||||||||
pmmOutputMaxApparentPowerThresholdmandatory Threshold above which an output maximum apparent power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-110 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.21 | ||||||||||||||||||||
pmmOutputOverActivePowerThresholdmandatory Threshold above which an output over active power condition will be generated.Specified as a percent deviation from nominal power rating. A value of zero indicates that the threshold is disabled. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.22 | ||||||||||||||||||||
pmmOutputPhaseLossThresholdmandatory Threshold below which an output phase loss condition will be generated.Specified as a percent deviation from nominal voltage represented in the OID pmmDeviceNominalOutputVoltage. A value of zero indicates that the thre… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.2.2.1.23 | ||||||||||||||||||||
pmmOutputBreakerStatemandatory This value indicates the current state of output breaker.1 will indicate open, 2 will indicate closed, 3 will indicate unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.2.2.1.24 | ||||||||||||||||||||
pmmOutputBreakerOpenAlarmmandatory Breaker open alarm status.1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.2.2.1.25 |
.1.3.6.1.4.1.318.1.1.28.3.2.3
·
1 row entry
·
8 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmOutputPhaseTable'
A list of output table entries. The number of entries is given by the value of pmmOutputMeterTableSize OID.
An entry containing information applicable to a
particular output phase.
particular output phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
pmmOutputMeterNummandatory The output meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.1 |
pmmOutputPhasemandatory Output phase index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.2 |
pmmOutputVoltageLtoLmandatory Line-to-line output voltage available.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.3 |
pmmOutputVoltageLtoNmandatory Line-to-neutral output voltage available.Measured in tenths of Volts. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.4 |
pmmOutputPhaseCurrentmandatory Load current per phase. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.5 |
pmmOutputActivePowermandatory Output power per phase. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.6 |
pmmOutputApparentPowermandatory Output power per phase. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.7 |
pmmOutputPowerFactormandatory Indicates the power factor of the output per phase.A value of 100 representing a unity power factor (1.00). Specified in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.2.3.1.8 |
.1.3.6.1.4.1.318.1.1.28.3.3.3
·
1 row entry
·
41 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmBranchBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmBranchBreakerTable'
A list of branch breaker table entries. The number of entries is contained in the pmmBranchBreakerTableSize OID.
An entry containing information applicable to a
particular branch breaker (panel/circuit position).
particular branch breaker (panel/circuit position).
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
pmmBranchCircuitMeterIndexmandatory Index of branch circuit meter in the table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.1 | ||||||
pmmBranchCircuitIndexmandatory The branch circuit index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.2 | ||||||
pmmBranchCircuitNumberOfPolesmandatory The number of poles. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.3 | ||||||
pmmBranchCircuitPhasemandatory The phase associated with branch circuit. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.4 | ||||||
pmmBranchCircuitBreakerIdentifiermandatory The branch circuit identifier.Returns (-1) if not supported. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.5 | ||||||
pmmBranchCircuitLoadIdentifiermandatory Identifies the name or location of the branch circuit load. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.6 | ||||||
pmmBranchCircuitCurrentmandatory The branch circuit current Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.7 | ||||||
pmmBranchCircuitBreakerRatingmandatory The rating of the branch circuit breaker in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.8 | ||||||
pmmBranchCircuitTotalActivePowermandatory Branch circuit total active power. Measured in tenthsof kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.9 | ||||||
pmmBranchCircuitTotalApparentPowermandatory Branch circuit total apparent power. Measured intenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.10 | ||||||
pmmBranchCircuitEnergyUsagemandatory Indicates the accumulated energy usage per phase in tenths of kWh.Displayed as 0 when not available or no energy used. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.11 | ||||||
pmmBranchCircuitEnergyUsageResetDatemandatory The date that the kWh usage was reset, in the format mm/dd/yyyy.The default energy usage reset date is Not Available. Displayed as NA when breaker is not installed or if not first pole of breaker. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.12 | ||||||
pmmBranchCircuitTotalPowerFactormandatory Indicates the total power factor of the branch circuit.A value of 100 representing a unity power factor (1.00) Specified in hundredths. Returns -1 if unsupported. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.13 | ||||||
pmmBranchCircuitBreakerStatemandatory This value indicates the current state of branchcircuit breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.3.3.1.14 | ||||||
pmmBranchCircuitMinCurrentThresholdmandatory Threshold below which a branch circuit minimum currentcondition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates t… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.15 | ||||||
pmmBranchCircuitLowCurrentThresholdmandatory Threshold below which a branch circuit low currentcondition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that … | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.16 | ||||||
pmmBranchCircuitHighCurrentThresholdmandatory Threshold above which a branch circuit high currentcondition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates that… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.17 | ||||||
pmmBranchCircuitMaxCurrentThresholdmandatory Threshold above which a branch circuit maximum currentcondition will be generated. Specified as a percentage of the branch breaker rating represented in the OID pmmBranchCircuitBreakerRating A value of zero indicates t… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.18 | ||||||
| Threshold below which a branch circuit minimum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. A value of zero indicates that the threshold is disabled. Th… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.19 | ||||||
| Threshold above which a branch circuit maximum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. A value of zero indicates that the threshold is disabled. Th… | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.20 | ||||||
pmmBranchCircuitAlaramGenerationmandatory Alarm generation status.1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.3.3.1.21 | ||||||
pmmBranchCircuitBreakerOpenAlarmmandatory Breaker open alarm status.1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.3.3.1.22 | ||||||
| Average branch breaker current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.23 | ||||||
| Branch circuit maximum instantaneous current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.24 | ||||||
| Average branch breaker maximum instantaneous current. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.25 | ||||||
pmmBranchCircuitAnglemandatory Branch circuit phase angle. Measured in tenths of Decimal. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.26 | ||||||
pmmBranchCircuitActivePowermandatory Branch circuit Active power. Measured in tenths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.27 | ||||||
pmmBranchCircuitApparentPowermandatory Branch circuit apparent power. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.28 | ||||||
| Indicates the circuit Breaker total accumulated energy usage in tenths of kWh. Displayed as 0 when not available or no energy used. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.29 | ||||||
pmmBranchCircuitPowerFactormandatory Indicates the power factor of the branch circuit.A value of 100 representing a unity power factor (1.00) Specified in hundredths. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.30 | ||||||
pmmBranchCircuitTHDmandatory Branch circuit current harmonic distortion.Specified in tenths of percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.31 | ||||||
pmmBranchCircuitBreakerTHDmandatory Average branch breaker current harmonic distortion.Specified in tenths of percent. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.32 | ||||||
pmmBranchCircuitBreakerLoadmandatory Total load on the Breaker.Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.33 | ||||||
pmmBranchCircuitBranchNumbermandatory The branch number.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.34 | ||||||
pmmBranchCircuitChannelCTSizemandatory The branch CT Size.Returns -1 if unsupported or failed. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.35 | ||||||
pmmBranchCircuitCurrentMaxAlarmmandatory Current maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.36 | ||||||
pmmBranchCircuitCurrentHighAlarmmandatory Current high alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.37 | ||||||
pmmBranchCircuitCurrentLowAlarmmandatory Current low alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.38 | ||||||
pmmBranchCircuitCurrentMinAlarmmandatory Current minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.39 | ||||||
| Apparent power maximum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.40 | ||||||
| Apparent power minimum alarm generation status. 1 - enabled 2 - disabled 3 - unknown | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.3.3.1.41 |
.1.3.6.1.4.1.318.1.1.28.3.4.2
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pmmSiteConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pmmSiteConfigTable'
A list of PMM site configurable entries.
An entry containing information applicable to a
particular site configuration.
particular site configuration.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
pmmSiteConfigIndexmandatory PMM site configuration identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.1 | ||||
pmmSiteConfigNominalPtoPVoltagemandatory The nominal input phase to phase voltage to the PMM. Measured in Volts,line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.2 | ||||
pmmSiteConfigNominalPtoNVoltagemandatory The nominal input phase to neutral voltage to the PMM. Measured in Volts,line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.3 | ||||
pmmSiteConfigNominalCurrentmandatory The nominal input current to the PMM. Measured in tenths of Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.4 | ||||
pmmSiteConfigNominalFrequencymandatory The nominal input frequency to the PMM. Measured in tenths of Hertz. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.5 | ||||
pmmSiteConfigNominalApparentPowermandatory The nominal input apparent power to the PMM. Measured in tenths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.28.3.4.2.1.6 | ||||
pmmSiteConfigServiceTypemandatory The type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.28.3.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.29.2.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk chargerInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::chargerInputPhaseTable'
A list of input table entries. The number of entries is given by the sum of the Charger input phases.
An entry containing information applicable to a
particular input phase.
particular input phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
chargerInputPhaseTableIndexmandatory The input identifier.If not supported, return 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.29.2.1.1.1 |
chargerInputPhaseVoltagemandatory The input voltage in VAC, or -1 if it's unsupportedby this Charger. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.29.2.1.1.2 |
chargerInputPhaseMinVoltagemandatory The lowest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupportedby this Charger. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.29.2.1.1.3 |
chargerInputPhaseMaxVoltagemandatory The highest input voltage to the Charger during the previous minute of operation, or -1 if it's unsupportedby this Charger. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.29.2.1.1.4 |
chargerInputPhaseCurrentmandatory The input current in 0.1 amperes, or -1 if it'sunsupported by this Charger. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.29.2.1.1.5 |
.1.3.6.1.4.1.318.1.1.30.2.1
·
1 row entry
·
12 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUDeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUDeviceStatusTable'
A table of Easy PDU status information
Status information from the Easy PDU being queried
Indexes
| Column | Syntax | OID |
|---|---|---|
ePDUDeviceStatusIndexmandatory The index to the Easy PDU status table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.1 |
ePDUDeviceStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.2 |
ePDUDeviceStatusVersionmandatory The Easy PDU firmware and hardware version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.30.2.1.1.3 |
ePDUDeviceStatusModelNumbermandatory The Easy PDU model number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.30.2.1.1.4 |
ePDUDeviceStatusSerialNumbermandatory The Easy PDU serial number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.30.2.1.1.5 |
ePDUDeviceStatusNumPhasesmandatory The number of phases present in the Easy PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.6 |
ePDUDeviceStatusActivePowermandatory Indicates the PDU Active Power. Units:1 Watt.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.7 |
ePDUDeviceStatusReactivePowermandatory Indicates the PDU Reactive Power. Units:1 Var.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.8 |
ePDUDeviceStatusApparentPowermandatory Indicates the PDU Apparent Power. Units:1 VA.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.9 |
ePDUDeviceStatusPowerFactormandatory Indicates the PDU Power Factor. Units:0.1%.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.10 |
ePDUDeviceStatusEnergymandatory Indicates the PDU Energy. Units:1 Wh.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.11 |
ePDUDeviceStatusFrequencymandatory Indicates the PDU Frequency. Units:0.001 Hz.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.1.1.12 |
.1.3.6.1.4.1.318.1.1.30.2.2
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUDeviceControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUDeviceControlTable'
A table of Easy PDU control data
Control data from Easy PDU being queried
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
ePDUDeviceControlIndexmandatory The index to the Easy PDU control table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.2.1.1 | ||||
ePDUDeviceControlModulemandatory The user-defined Easy PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.2.2.1.2 | ||||
ePDUDeviceControlRebootmandatory Setting this OID to reboot (1) will cause the device reboot immediately.Getting this OID in models that support this feature will do nothing and return the noOperation(0) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.30.2.2.1.3 | ||||
ePDUDeviceControlEnergyResetmandatory Setting this OID to reset (1) will cause the device energy meter valueto be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(0) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.30.2.2.1.4 | ||||
ePDUDeviceControlBeepAlarmmandatory User-defined Beep alarm, 1 for turn off Beep, 2 for turn on Beep.Models that do not support this feature will respond to this OID with a value of -1. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.30.2.2.1.5 |
.1.3.6.1.4.1.318.1.1.30.4.1
·
1 row entry
·
7 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUPhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUPhaseConfigTable'
A table of Easy PDU phase configuration data
Configuration data from currently queried Easy PDU phase
Indexes
| Column | Syntax | OID |
|---|---|---|
ePDUPhaseConfigIndexmandatory The index to the Easy PDU phase configuration table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.1 |
ePDUPhaseConfigModulemandatory The user-defined Easy PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.2 |
ePDUPhaseConfigNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.3 |
ePDUPhaseConfigOverVoltageThresholdmandatory User-defined Phase Over Voltage alarm threshold. Units:0.1 V.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.4 |
ePDUPhaseConfigLowVoltageThresholdmandatory User-defined Phase Low Voltage alarm threshold. Units:0.1 V.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.5 |
ePDUPhaseConfigOverCurrentThresholdmandatory User-defined Phase Over Current alarm threshold. Units:0.01 A.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.6 |
ePDUPhaseConfigLowCurrentThresholdmandatory User-defined Phase Low Current alarm threshold. Units:0.01 A.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.1.1.7 |
.1.3.6.1.4.1.318.1.1.30.4.2
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUPhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUPhaseStatusTable'
A table of Rack PDU phase status data
Status data from currently queried Easy PDU phase
Indexes
| Column | Syntax | OID |
|---|---|---|
ePDUPhaseStatusIndexmandatory The index to the Easy PDU phase configuration table entry | Integer32 Constraints: range: 1-12 | .1.3.6.1.4.1.318.1.1.30.4.2.1.1 |
ePDUPhaseStatusModulemandatory The user-defined Easy PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.2 |
ePDUPhaseStatusNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.3 |
ePDUPhaseStatusVoltagemandatory Indicates the Phase Voltage. Units:0.1 V | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.4 |
ePDUPhaseStatusCurrentmandatory Indicates the Phase Current. Units:0.01 A | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.5 |
ePDUPhaseStatusActivePowermandatory Indicates the Phase Active Power. Units:1 Watt | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.6 |
ePDUPhaseStatusReactivePowermandatory Indicates the Phase Reactive Power. Units:1 Var.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.7 |
ePDUPhaseStatusApparentPowermandatory Indicates the Phase Apparent Power. Units:1 VA.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.8 |
ePDUPhaseStatusPowerFactormandatory Indicates the Phase Power Factor. Units:0.1% | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.9 |
ePDUPhaseStatusEnergymandatory Indicates the Phase Energy. Units:1 Wh | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.4.2.1.10 |
.1.3.6.1.4.1.318.1.1.30.6.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUOutletStatusTable'
The number of switched outlets on connected Rack PDUs
Switched Outlet status from currently queried
Easy PDU switched outlet
Easy PDU switched outlet
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
ePDUOutletStatusIndexmandatory The index to the Easy PDU switched outlet status information table entry.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Constraints: range: 1-128 | .1.3.6.1.4.1.318.1.1.30.6.1.1.1 | ||||
ePDUOutletStatusModulemandatory The user-defined Easy PDU numeric ID.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.6.1.1.2 | ||||
ePDUOutletStatusNumbermandatory The numeric switched outlet ID.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.6.1.1.3 | ||||
ePDUOutletStatusStatemandatory Indicates the present switch state of the Easy PDU switched outlet being queried.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.30.6.1.1.4 |
.1.3.6.1.4.1.318.1.1.30.6.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUOutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUOutletControlTable'
A table of Easy PDU switched outlet control data
Control data for currently queried Easy PDU switched outlet
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
ePDUOutletControlIndexmandatory The index to the Easy PDU switched outlet configuration table entry.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Constraints: range: 1-128 | .1.3.6.1.4.1.318.1.1.30.6.2.1.1 | ||||||
ePDUOutletControlModulemandatory The user-defined Easy PDU numeric ID.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.6.2.1.2 | ||||||
ePDUOutletControlNumbermandatory The numeric switched outlet ID.Models that do not support this feature, will respond to this OID with a value of notSupported (-1). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.6.2.1.3 | ||||||
ePDUOutletControlCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot b… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.30.6.2.1.4 |
.1.3.6.1.4.1.318.1.1.30.8.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUSensorConfigTable'
A table of temperature-humidity sensor configuration data
Configuration data from temperature-humidity sensor being queried
Indexes
| Column | Syntax | OID |
|---|---|---|
ePDUSensorConfigIndexmandatory The index to the temperature-humidity sensor configuration data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.1 |
ePDUSensorConfigModulemandatory The user-defined Easy PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.2 |
ePDUSensorConfigTempMaxThresholdmandatory User-defined Max Temperature alarm threshold. Units: 0.1 degrees Celsius.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.3 |
ePDUSensorConfigTempMinThresholdmandatory User-defined Min Temperature alarm threshold. Units: 0.1 degrees Celsius.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.4 |
ePDUSensorConfigHumidityMaxThresholdmandatory User-defined Max Humidity alarm threshold. Units: 0.1% relative humidity.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.5 |
ePDUSensorConfigHumidityMinThresholdmandatory User-defined Min Humidity alarm threshold. Units: 0.1% relative humidity.Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.1.1.6 |
.1.3.6.1.4.1.318.1.1.30.8.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ePDUSensorStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ePDUSensorStatusTable'
A table of temperature-humidity sensor status data
Status information from temperature-humidity sensor being queried
Indexes
| Column | Syntax | OID |
|---|---|---|
ePDUSensorStatusIndexmandatory The index to the temperature-humidity status data table entry | Integer32 Constraints: range: 1-4 | .1.3.6.1.4.1.318.1.1.30.8.2.1.1 |
ePDUSensorStatusModulemandatory The user-defined Easy PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.2.1.2 |
ePDUSensorStatusTemperaturemandatory Sensor temperature reading in tenths of degrees Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.2.1.3 |
ePDUSensorStatusHumiditymandatory Sensor humidity reading in 0.1 percent relative humidity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.30.8.2.1.4 |
.1.3.6.1.4.1.318.1.1.31.2.2.1
·
1 row entry
·
2 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcUpsInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcUpsInputTable'
A list of UPS input table entries. The number of entries is given by the value of mdcUpsNumUnits.
An entry containing information applicable to a
particular input of UPS.
particular input of UPS.
Indexes
| Column | Syntax | OID |
|---|---|---|
mdcUpsInputTableIndexmandatory The UPS identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.2.2.1.1.1 |
mdcUpsInputVoltagemandatory The current utility line voltage in VAC. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.2.1.1.2 |
.1.3.6.1.4.1.318.1.1.31.2.3.1
·
1 row entry
·
5 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcUpsOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcUpsOutputTable'
A list of UPS output table entries. The number of entries is given by the value of mdcUpsNumUnits.
An entry containing information applicable to a
output of particular UPS.
output of particular UPS.
Indexes
| Column | Syntax | OID |
|---|---|---|
mdcUpsOutputTableIndexmandatory The UPS identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.2.3.1.1.1 |
mdcUpsOutputVoltagemandatory The output voltage of the UPS system in VAC. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.3.1.1.2 |
mdcUpsOutputCurrentmandatory The current in amperes drawn by the load on the UPS. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.3.1.1.3 |
mdcUpsOutputActivePowermandatory The total output active power of the UPS system in W. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.2.3.1.1.4 |
mdcUpsOutputFrequencymandatory The current output frequency of the UPS system in Hz. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.3.1.1.5 |
.1.3.6.1.4.1.318.1.1.31.2.4.1
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcUpsBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcUpsBatteryTable'
Table of Battery details. The number of entries is given by the value of mdcUpsNumUnits.
An entry containing information applicable to
battery of individual UPS.
battery of individual UPS.
Indexes
| Column | Syntax | OID |
|---|---|---|
mdcUpsBatteryTableIndexmandatory The UPS identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.2.4.1.1.1 |
mdcUpsBatteryRunTimeRemainingmandatory The UPS battery run time remaining before batteryexhaustion. | RFC1155-SMITimeTicks Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.4.1.1.2 |
mdcUpsBatteryCapacitymandatory The remaining battery capacity expressed inpercent of full capacity. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.1.31.2.4.1.1.3 |
.1.3.6.1.4.1.318.1.1.31.3.2.1
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcCoolingStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcCoolingStatusTable'
A list of cooling status table entries. The number of entries is given by the value of mdcCoolingNumUnits.
An entry containing information applicable to a
particular status of cooling unit.
particular status of cooling unit.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
mdcCoolingStatusTableIndexmandatory The cooling unit identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.3.2.1.1.1 | ||||||||||||||||
mdcCoolingStatusSupplyAirTempmandatory The unit supply air temperature in degree Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.3.2.1.1.2 | ||||||||||||||||
mdcCoolingStatusReturnAirTempmandatory The unit return air temperature in degree Celsius. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.3.2.1.1.3 | ||||||||||||||||
mdcCoolingStatusOperateModemandatory The cooling unit operating mode. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.31.3.2.1.1.4 |
.1.3.6.1.4.1.318.1.1.31.3.3.4
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcCoolingConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcCoolingConfigTable'
A list of cooling configuration table entries. The number of entries is given by the value of mdcCoolingNumUnits.
An entry containing information applicable to
configuration of particular cooling unit.
configuration of particular cooling unit.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
mdcCoolingConfigTableIndexmandatory The cooling unit identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.3.3.4.1.1 | ||||||
mdcCoolingConfigOutletAirTempmandatory Outlet air temperature set point. This OID represents the value sent tothe particular cooling unit in degree Celsius. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.3.3.4.1.2 | ||||||
mdcCoolingConfigPTCHeatermandatory The status of PTC heater of particular cooling unit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.31.3.3.4.1.3 | ||||||
mdcCoolingConfigCondensationpumpmandatory The status of condensation pump of particular cooling unit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.31.3.3.4.1.4 |
.1.3.6.1.4.1.318.1.1.31.5.2.1
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcMeterStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcMeterStatusTable'
A list of meter status table entries. The number of entries is given by the value of mdcMeterNumUnits.
An entry containing information applicable to a
particular status of meter.
particular status of meter.
Indexes
| Column | Syntax | OID |
|---|---|---|
mdcMeterStatusTableIndexmandatory The meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.1 |
mdcMeterFrequencymandatory The frequency in Hertz. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.2 |
mdcMeterVoltagemandatory The voltage in Volts as measured by the meter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.3 |
mdcMeterCurrentmandatory The current in Amps as measured by the meter. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.4 |
mdcMeterActivePowermandatory Shows the active power measured by the meter in hundreths of kW. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.5 |
mdcMeterApparentPowermandatory Shows the apparent power measured by the meter in hundreths of kVA. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.2.1.1.6 |
.1.3.6.1.4.1.318.1.1.31.5.3.1
·
1 row entry
·
9 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mdcMeterConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mdcMeterConfigTable'
A list of meter configuration table entries. The number of entries is given by the value of mdcMeterNumUnits.
An entry containing information applicable to
configuration of particular meter.
configuration of particular meter.
Indexes
| Column | Syntax | OID |
|---|---|---|
mdcMeterConfigTableIndexmandatory The meter identifier. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.1 |
mdcMeterMinVoltThresholdmandatory Threshold below which an input minimum voltage conditionwill be generated. Specified as percent deviation from nominal voltage. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.2 |
mdcMeterLowVoltThresholdmandatory Threshold below which an input low voltage conditionwill be generated. Specified as percent deviation from nominal voltage. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.3 |
mdcMeterHighVoltThresholdmandatory Threshold above which an input high voltage conditionwill be generated. Specified as percent deviation from nominal voltage. | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.4 |
mdcMeterMaxVoltThresholdmandatory Threshold above which an input maximum voltage conditionwill be generated. Specified as percent deviation from nominal voltage. | Integer32r/w Constraints: range: 0-120 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.5 |
mdcMeterMinCurrentThresholdmandatory Threshold below which an input minimum current condition will be generated. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.6 |
mdcMeterLowCurrentThresholdmandatory Threshold below which an input low current condition will be generated. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.7 |
mdcMeterHighCurrentThresholdmandatory Threshold above which an input high current condition will be generated. | Integer32r/w Constraints: range: 0-110 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.8 |
mdcMeterMaxCurrentThresholdmandatory Threshold above which an input maximum current condition will be generated. | Integer32r/w Constraints: range: 0-100 | .1.3.6.1.4.1.318.1.1.31.5.3.1.1.9 |
.1.3.6.1.4.1.318.1.1.33.2
·
1 row entry
·
14 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ats5gDeviceIdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ats5gDeviceIdentTable'
This table organizes the identifying data of devices in the device group.
This entry organizes the identity data of a single device.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ats5gIdentDeviceIndexmandatory This value is the data entry's index in the identity table. | Integer32 Constraints: range: 1-65535 | .1.3.6.1.4.1.318.1.1.33.2.1.1 | ||||||||||||||||
ats5gIdentConfigModuleIDmandatory This value is ID number that can be configured for each device. It cannot begreater than the maximum number of devices in the network port sharing (NPS) group (32). Changing this value causes the device to reboot, whic… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.2.1.2 | ||||||||||||||||
ats5gIdentModuleTypemandatory This value describes the role the specified device holds in the device group:notNPS(1) specifies that the device is not in a group host(2) specifies that a device will broadcast firmware updates to guests guest(3) spec… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.2.1.3 | ||||||||||||||||
ats5gIdentModuleStatusmandatory This value tracks the communication status of a device within the group. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.2.1.4 | ||||||||||||||||
ats5gIdentSerialNumbermandatory This is the serial number of the automatic transfer switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.5 | ||||||||||||||||
ats5gIdentModelNumbermandatory This is the model number of the automatic transfer switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.6 | ||||||||||||||||
ats5gIdentHardwareRevmandatory This is the hardware revision of the automatic transfer switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.7 | ||||||||||||||||
ats5gIdentManufactureDatemandatory This is the manufacture date of the automatic transfer switch. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.8 | ||||||||||||||||
ats5gIdentBootmonRevmandatory This is the boot monitor firmware revision of the network management card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.9 | ||||||||||||||||
ats5gIdentAOSRevmandatory This is the operating system firmware revision of the network management card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.10 | ||||||||||||||||
ats5gIdentAppRevmandatory This is the application firmware revision of the network management card. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.2.1.11 | ||||||||||||||||
ats5gIdentConfigNamemandatory This is the configurable name of the device. It may be up to 255 characters long. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.33.2.1.12 | ||||||||||||||||
ats5gIdentConfigLocationmandatory This is the configurable location of the device. It may be up to 255 characters long. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.33.2.1.13 | ||||||||||||||||
ats5gIdentConfigContactmandatory This is the configurable contact information of the device. It may be up to 255 characters long. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.33.2.1.14 |
.1.3.6.1.4.1.318.1.1.33.3
·
1 row entry
·
41 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ats5gDeviceSwitchTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ats5gDeviceSwitchTable'
This table organizes the data specific to the automatic transfer switch.
This entry organizes the switch data of a single device.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
ats5gSwitchDeviceIndexmandatory This value is the data entry's index in the switching table. | Integer32 Constraints: range: 1-65535 | .1.3.6.1.4.1.318.1.1.33.3.1.1 | ||||||||||
ats5gSwitchModuleIDmandatory This value is the ats5gIdentConfigModuleID of the device being queried. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.2 | ||||||||||
ats5gSwitchOrientationmandatory This value describes the voltage orientation of the ATS. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.3 | ||||||||||
ats5gSwitchCumulativeAlarmStatusmandatory This is the severity of the most severe alarm currently active. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.4 | ||||||||||
ats5gSwitchCommunicationStatusmandatory This is the communication status between the network management cardand the automatic transfer switch. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.5 | ||||||||||
ats5gSwitchConfigFrontPanelLockoutmandatory This is the configurable lockout status of the source preference toggle buttonon the front panel. The button does nothing while the front panel is locked. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.6 | ||||||||||
ats5gSwitchConfigPreferredSourcemandatory This is the configurable source preference. If the ATS is fully redundant thepreferred source will be the selected source. If the preferred source is none(3), the ATS will switch sources only in response to measured ch… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.7 | ||||||||||
ats5gSwitchSelectedSourcemandatory This is the selected source that will be used to power downstream devices. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.8 | ||||||||||
ats5gSwitchRedundancyStatemandatory This is the ATS redundancy status. While this value is atsFullyRedundant(2),either input may be used to power downstream devices. While this value is atsRedundancyLost(1), one input has failed validation and downstream… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.9 | ||||||||||
ats5gSwitchSourceAStatusmandatory This is the input status of source A. The ATS will use source B as the selected sourcewhile this value is fail(1). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.10 | ||||||||||
ats5gSwitchSourceBStatusmandatory This is the input status of source B. The ATS will use source A as the selected sourcewhile this value is fail(1). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.11 | ||||||||||
ats5gSwitchRatedVoltagemandatory This is the default nominal line VRMS in volts (V) for this unit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.12 | ||||||||||
ats5gSwitchConfigNominalVoltagemandatory This is the configurable line VRMS in volts (V) that will be used to select sources. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.13 | ||||||||||
| This value specifies which voltage transfer range should be used to disqualify sources and raise alarms. The narrow transfer voltage must be less than the medium transfer voltage, which must be less than the wide transf… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.14 | ||||||||||
ats5gSwitchConfigTransferVoltageWidemandatory This is the configurable transfer range in volts (V) used to disqualify sources whenats5gSwitchConfigTransferVoltageRange is wide(1). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.15 | ||||||||||
| This is the configurable transfer range in volts (V) used to disqualify sources when ats5gSwitchConfigTransferVoltageRange is medium(2). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.16 | ||||||||||
| This is the configurable transfer range in volts (V) used to disqualify sources when ats5gSwitchConfigTransferVoltageRange is narrow(3). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.17 | ||||||||||
ats5gSwitchConfigVoltageSensitivitymandatory This is the configured sensitivity threshold for rapid changes to input voltage.It is recommended to use high(1) unless frequent small changes are expected. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.18 | ||||||||||
ats5gSwitchSourceAVoltagemandatory This is the measured line VRMS of source A reported in volts (V). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.19 | ||||||||||
ats5gSwitchSourceBVoltagemandatory This is the measured line VRMS of source B reported in volts (V). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.20 | ||||||||||
ats5gSwitchRatedFrequencymandatory This is the default nominal line frequency for this unit reported in Hertz (Hz). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.21 | ||||||||||
ats5gSwitchConfigNominalFrequencymandatory This is the configurable line frequency in Hertz (Hz) that will be used to selectsources. If the difference between ats5gSwitchConfigNominalFrequency and a source's measured frequency is greater than ats5gSwitchConfigF… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.22 | ||||||||||
ats5gSwitchConfigFrequencyDeviationmandatory This is the configurable frequency deviation in Hertz (Hz) that will be used to selectsources. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.23 | ||||||||||
ats5gSwitchSourceAFrequencymandatory This is the measured line frequency of source A reported in Hertz (Hz). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.24 | ||||||||||
ats5gSwitchSourceBFrequencymandatory This is the measured line frequency of source B reported in Hertz (Hz). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.25 | ||||||||||
ats5gSwitchEventCountStartTimemandatory This value is the time and date of the last event count reset action. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.3.1.26 | ||||||||||
ats5gSwitchEventCountRedundancyLossmandatory This value tracks the number of redundancy loss events. It increments each timea source becomes invalid. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.27 | ||||||||||
ats5gSwitchEventCountSourceSwitchmandatory This value tracks the number of source switch events. It increments each time theselected source changes. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.28 | ||||||||||
| This value tracks the number of preferred source configuration change events. It increments each time the user updates their source preference. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.29 | ||||||||||
ats5gSwitchEventCountSpikeOrDropmandatory This value tracks voltage spike and drop events. It increments each time asource's measured instantaneous voltage increases or decreases rapidly. This depends on configured voltage sensitivity. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.30 | ||||||||||
ats5gSwitchEventCountSurgeOrDroopmandatory This value tracks voltage surge or droop events. It increments each time asource's calculated VRMS increases or decreases rapidly. This does not depend on any user configurations. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.31 | ||||||||||
ats5gSwitchEventCountFreqOutOfRangemandatory This value tracks frequency threshold violations. It increments each time a sourceis disqualified because the difference between its measured frequency and the configured nominal frequency is greater than the configure… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.3.1.32 | ||||||||||
ats5gSwitchControlEventCountResetmandatory This control resets the event counts when the value is set to reset(2). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.33 | ||||||||||
ats5gSwitchVoltageOutStatusmandatory This value is on(2) while the output outlets are powered. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.34 | ||||||||||
ats5gSwitchOverCurrentStatemandatory This value is atsOverCurrent(1) when the ATS has exceeded the outputcurrent threshold and will not allow a switch over to the alternate power source if the current source fails. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.35 | ||||||||||
ats5gSwitchPhaseSyncStatusmandatory This value tracks the phase sync status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.36 | ||||||||||
ats5gSwitchSourceA24VSupplyStatusmandatory This value tracks the internal source A 24VDC power supply status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.37 | ||||||||||
ats5gSwitchSourceB24VSupplyStatusmandatory This value tracks the internal source B 24VDC power supply status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.38 | ||||||||||
ats5gSwitchSourceA48VSupplyStatusmandatory This value tracks the internal source A 48VDC power supply status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.39 | ||||||||||
ats5gSwitchSourceB48VSupplyStatusmandatory This value tracks the internal source B 48VDC power supply status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.40 | ||||||||||
ats5gSwitch3p3VSupplyStatusmandatory This value tracks the internal 3.3VDC power supply status. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.3.1.41 |
.1.3.6.1.4.1.318.1.1.33.4
·
1 row entry
·
18 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ats5gDeviceEnvironmentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ats5gDeviceEnvironmentTable'
This table organizes the data specific to the environment monitoring accessories.
This entry organizes the switch data of a single device.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
ats5gEnvDeviceIndexmandatory This value is the data entry's index in the environment table. | Integer32 Constraints: range: 1-65535 | .1.3.6.1.4.1.318.1.1.33.4.1.1 | ||||||||||
ats5gEnvModuleIDmandatory This value is the ats5gIdentConfigModuleID of the device being queried. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.2 | ||||||||||
ats5gEnvSensorTypemandatory This value is the type of the currently attached sensor accessory. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.4.1.3 | ||||||||||
ats5gEnvAlarmStatusmandatory This is the severity of the most severe environment-specific alarm currently active. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.4.1.4 | ||||||||||
ats5gEnvTemperaturemandatory This is the measured temperature of the attached sensor reported in tenth-degreesFahrenheit. The value reports as -1 if the attached sensor does not support temperature measurements. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.5 | ||||||||||
ats5gEnvConfigTempMaxThresholdmandatory This is the configured maximum temperature threshold reported in degrees Fahrenheit.The value reports as -1 if the attached sensor does not support temperature measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.6 | ||||||||||
ats5gEnvConfigTempHighThresholdmandatory This is the configured high temperature threshold reported in degrees Fahrenheit.The value reports as -1 if the attached sensor does not support temperature measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.7 | ||||||||||
ats5gEnvConfigTempHysteresismandatory This is the configured temperature threshold hysteresis reported in degrees Fahrenheit.The value reports as -1 if the attached sensor does not support temperature measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.8 | ||||||||||
ats5gEnvConfigTempAlarmsEnabledmandatory This is the configured temperature monitoring status. While this value is disabled(1),no temperature-related alarms will be active. The value reports as -1 if the attached sensor does not support temperature measuremen… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.4.1.9 | ||||||||||
ats5gEnvHumiditymandatory This is the measured humidity around the attached sensor reported in percent relativehumidity. The value reports as -1 if the attached sensor does not support humidity measurements. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.10 | ||||||||||
ats5gEnvConfigHumLowThresholdmandatory This is the configured low humidity threshold reported in %RH. The value reports as -1if the attached sensor does not support humidity measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.11 | ||||||||||
ats5gEnvConfigHumMinThresholdmandatory This is the configured minimum humidity threshold reported in %RH. The value reportsas -1 if the attached sensor does not support humidity measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.12 | ||||||||||
ats5gEnvConfigHumHysteresismandatory This is the configured humidity threshold hysteresis reported in %RH. The value reportsas -1 if the attached sensor does not support humidity measurements. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.13 | ||||||||||
ats5gEnvConfigHumAlarmsEnabledmandatory This is the configured humidity monitoring status. While this value is disabled(1),no humidity-related alarms will be active. The value reports as -1 if the attached sensor does not support humidity measurements. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.4.1.14 | ||||||||||
ats5gEnvPeakTemperaturemandatory This is the highest temperature recorded since the last peak temperature reset,reported in degrees Fahrenheit. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.4.1.15 | ||||||||||
ats5gEnvPeakTempTimemandatory This is the date and time that the peak temperature was recorded. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.4.1.16 | ||||||||||
ats5gEnvPeakTempResetTimemandatory This is the date and time that the peak temperature was last reset. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.33.4.1.17 | ||||||||||
ats5gEnvControlPeakTempResetmandatory This control resets the peak temperature when the value is set to reset(2). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.4.1.18 |
.1.3.6.1.4.1.318.1.1.33.6
·
1 row entry
·
10 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk ats5gBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::ats5gBankTable'
This table organizes the bank data of devices in the device group.
This entry organizes the bank data of a single device.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
ats5gBankIndexmandatory This value is the data entry's index in the bank table. | Integer32 Constraints: range: 1-65535 | .1.3.6.1.4.1.318.1.1.33.6.1.1 | ||||||||
ats5gBankModuleIDmandatory This value is the ats5gIdentConfigModuleID of the device being queried. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.2 | ||||||||
ats5gBankTypemandatory This value describes the type of bank associated with this bank index. If a devicehas multiple banks, then its total(1) output will include the bank1(2) and bank2(3) outputs. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.6.1.3 | ||||||||
ats5gBankRatedAmpsmandatory This value is the rated output of the specified bank reported in amps (A). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.4 | ||||||||
ats5gBankOutputTenthAmpsmandatory This value is the measured output of the specified bank reported in tenths of amps (A). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.5 | ||||||||
ats5gBankConfigLowLoadThresholdmandatory This value is the configured low load threshold of the specified bank reportedin amps (A). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.6 | ||||||||
ats5gBankConfigNearOverLoadThresholdmandatory This value is the configured near overload threshold of the specified bank reportedin amps (A). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.7 | ||||||||
ats5gBankConfigOverloadThresholdmandatory This value is the configured overload threshold of the specified bank reportedin amps (A). | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.8 | ||||||||
ats5gBankApparentPowermandatory This value is the calculated apparent power of the specified bank reportedin kilovolt-amps (kVA). | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.33.6.1.9 | ||||||||
ats5gBankOutputCurrentStatusmandatory This value tracks the load status of the specified bank. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.33.6.1.10 |
.1.3.6.1.4.1.318.1.2.1.2.2
·
1 row entry
·
4 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk powerNetSoftwareTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::powerNetSoftwareTable'
A list of the software monitoring the UPS.
An entry containing information on a software module.
Indexes
| Column | Syntax | OID |
|---|---|---|
moduleNumbermandatory The index into the Software Entry Table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.1.2.2.1.1 |
moduleNamemandatory The name of the software module. | OctetString Constraints: range: 0-79 | .1.3.6.1.4.1.318.1.2.1.2.2.1.2 |
moduleVersionmandatory The version of the software module. | OctetString Constraints: range: 0-8 | .1.3.6.1.4.1.318.1.2.1.2.2.1.3 |
moduleDatemandatory The date of the software module represented as mm-dd-yy. | OctetString Constraints: range: 0-9 | .1.3.6.1.4.1.318.1.2.1.2.2.1.4 |
.1.3.6.1.4.1.318.1.2.3.3.4
·
1 row entry
·
3 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pcnsNmcTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pcnsNmcTable'
The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown.
Details of the NMC.
Indexes
| Column | Syntax | OID |
|---|---|---|
pcnsNmcIndexmandatory Index of the NMC within PCNS setup. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.3.4.1.1 |
pcnsNmcAddrmandatory The IP address of the NMC. | RFC1155-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.2.3.3.4.1.2 |
pcnsNmcOutletmandatory The Outlet Group which PCNS is enrolled with on the NMC. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.3.4.1.3 |
.1.3.6.1.4.1.318.1.2.3.5.9
·
1 row entry
·
11 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk pcnsAdvancedShutdownTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::pcnsAdvancedShutdownTable'
The Network Management Cards in the UPS devices, which PCNS is monitoring to provide safe shutdown.
Details of the NMC.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
pcnsAdvancedGroupNomandatory Index of the Advanced Shutdown Group. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.5.9.1.1 | ||||
pcnsAdvancedGroupNamemandatory Name of the Advanced Shutdown Group. | OctetStringr/w Constraints: range: 0-32 | .1.3.6.1.4.1.318.1.2.3.5.9.1.2 | ||||
pcnsAdvancedGroupNMCmandatory List of NMCs in the Advanced Shutdown Group. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.2.3.5.9.1.3 | ||||
| Number of UPS devices required to power load. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.3.5.9.1.4 | ||||
| Run a shutdown command file before performing graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.5 | ||||
pcnsAdvancedShutdownCommandFilemandatory Full name of the shutdown command file to run before graceful shutdown. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.2.3.5.9.1.6 | ||||
| How long in seconds shutdown command file takes to run. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.3.5.9.1.7 | ||||
pcnsAdvancedShutdownPowerchuteServermandatory Shut down PowerChute Server. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.8 | ||||
pcnsAdvancedShutdownOnLostRedundancymandatory Shut down if Redundancy lost. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.9 | ||||
pcnsAdvancedTurnOffUpsmandatory Turn off the UPS when performing a graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.10 | ||||
pcnsAdvancedTurnOffSOGmandatory Turn off the Outlet Group on the UPS when performing a graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.11 |
.1.3.6.1.4.1.318.2.1.2
·
1 row entry
·
6 columns
Uses the apc variant from
Command help
/opt/observium/mibs/apc.
Walk mconfigTrapReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::mconfigTrapReceiverTable'
A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers.
The managers to send traps to.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
trapIndexmandatory The index to a trap receiver entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.2.1.2.1.1 | ||||||
receiverAddrmandatory The IP address of the manager to send a trap to. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.2.1.2.1.2 | ||||||
communityStringmandatory The community name to use in the trap whensent to the manager. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.2.1.2.1.3 | ||||||
severityobsolete The severity threshold of traps to send to the manager.traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.2.1.2.1.4 | ||||||
acceptThisReceivermandatory The value of yes(1) indicates that trap generation for this manager is enabled.The value of no(2) indicates that trap generation for this manager is disabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.2.1.2.1.5 | ||||||
receiveTrapTypeobsolete Type of trap. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.2.1.2.1.6 |