xPDUBypassInputVoltageLtoN
OBS ✓
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.15.3.2.4.1.3
Object
Line-to-neutral bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in tenths of Volts.
Observium directly uses this object
This object is referenced by an Observium discovery or polling workflow.
Used in:
Sensors
Explore Observium network monitoring
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.15.3.2.4.1.3- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- xPDUBypassInputVoltagePhaseEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUBypassInputVoltageLtoN'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xPDUBypassInputVoltageLtoN.<xPDUBypassInputVoltagePhaseIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::xPDUBypassInputVoltageLtoN'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647