emsStatusHardwareStatus
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.10.3.12.13
Object
The status of the EMS hardware. This integer should be interpreted
as a bit map, with each bit representing the presence or absence of
a specific hardware error condition.
0 indicates there are no error conditions detected in the EMS hardware.
1 indicates a Current Limit error condition related to the Alink port.
2 indicates incorrect hardware is plugged into an EMS port.
3 indicates that both of these error conditions are present.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.10.3.12.13- Type
- scalar
- Access
- readonly
- Status
- mandatory
- Parent
- emsStatus
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::emsStatusHardwareStatus.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::emsStatusHardwareStatus'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647