upsDiagBatteryHealth
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.11
Object
column mandatory
OctetString
The battery health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement module bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement module bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement module bit 6 Battery measured lifetime near end acknowledged, order replacement module
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.13.3.2.1.11- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- upsDiagBatteryEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagBatteryHealth'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsDiagBatteryHealth.<upsDiagBatteryIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsDiagBatteryHealth'
Syntax
OctetString
Values & Constraints
No enumerated values or constraints recorded.