xATSTestingStatusTestStatus

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.17.5.1.2

Object

scalar mandatory Enumeration
The present system test status/state.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.17.5.1.2
Type
scalar
Access
readonly
Status
mandatory
Parent
xATSTestingStatus

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSTestingStatusTestStatus.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::xATSTestingStatusTestStatus'

Syntax

Enumeration

Values & Constraints

Enumerated Values
1noTestInProcess
2testPending
3startingEngine
4engineWarmingUp
5awaitingTransferToS2
6testingWithLoad
7awaitingRetransferToS1
8testingWithoutLoad
9stoppingEngine
10holdingOnGenerator