xATSSwitchSettingsMinPhaseBalance

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.17.3.2.4

Object

scalar mandatory r/w Integer32
The minimum required phase balance at source 1.
When the percentage difference between the minimum and maximum
phase voltage measurements at source 1 is greater than this value,
source quality is considered bad and the generator run signal
is asserted to begin generator operation.
Specified as a percentage. A value of zero indicates that phase balance
is ignored when determining source quality. -1 if not available.

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.17.3.2.4
Type
scalar
Access
readwrite
Status
mandatory
Parent
xATSSwitchSettings

Scalars have one instance, identified by the .0 suffix.

Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::xATSSwitchSettingsMinPhaseBalance.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::xATSSwitchSettingsMinPhaseBalance'

Syntax

Source
SNMPv2-SMIInteger32
Base type
Integer32

Values & Constraints

Type Constraints
range: -2147483648..2147483647