upsBatteryStatsReset
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.1.22.1.1
Object
scalar mandatory
r/w
Enumeration
Setting this OID to reset(3) will reset the Battery Stats timer. Getting this OID will return: notSupported(1) - reset feature is not supported. noOperation(2) - indicates reset is supported, does nothing.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.1.22.1.1- Type
- scalar
- Access
- readwrite
- Status
- mandatory
- Parent
- upsBatteryStats
Net-SNMP examples
How SNMP and these commands workScalars have one instance, identified by the .0 suffix.
Read the scalar instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryStatsReset.0'
More examples
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsBatteryStatsReset'
Syntax
Enumeration
Values & Constraints
Enumerated Values
1 | notSupported |
2 | noOperation |
3 | reset |