isxModularDistModuleOutputKwhUsage
PowerNet-MIB ·
.1.3.6.1.4.1.318.1.1.22.2.6.1.21
Object
The total energy consumed by the load equipment fed by this distribution cable. This is the total since the date specified in the isxModularDistModuleOutputKwhResetDate OID, and may be cleared using the isxModularDistModuleOutputKwhReset OID. Measured in tenths of kWh.
Context
- MIB
- PowerNet-MIB
- OID
.1.3.6.1.4.1.318.1.1.22.2.6.1.21- Type
- column
- Access
- readonly
- Status
- mandatory
- Parent
- isxModularDistModuleOutputEntry
Net-SNMP examples
How SNMP and these commands workWalk the column to discover its indexed instances, or supply every index to read one instance.
Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistModuleOutputKwhUsage'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::isxModularDistModuleOutputKwhUsage.<isxModularDistModuleOutputModIndex>.<isxModularDistModuleOutputCordIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::isxModularDistModuleOutputKwhUsage'
Syntax
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647