upsBatteryCabinetBreaker

PowerNet-MIB · .1.3.6.1.4.1.318.1.1.1.2.5.1.13

Object

column optional Enumeration
The value indicates the battery cabinet breaker status. Reports 1 if no breaker is present.
1 = No breaker
2 = Unknown
3 = Breaker open
4 = Breaker closed

Context

MIB
PowerNet-MIB
OID
.1.3.6.1.4.1.318.1.1.1.2.5.1.13
Type
column
Access
readonly
Status
optional
Parent
upsBatteryCabinetEntry

Walk the column to discover its indexed instances, or supply every index to read one instance.

Walk the column
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabinetBreaker'
More examples
Read one indexed instance
/usr/bin/snmpget -v2c -c '<community>' -Pud -Ir -OQUv -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-MIB::upsBatteryCabinetBreaker.<upsBatteryCabinetIndex>'
Translate to a numeric OID
/usr/bin/snmptranslate -Pud -Ir -On -m 'PowerNet-MIB' -M '/opt/observium/mibs/apc:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'PowerNet-MIB::upsBatteryCabinetBreaker'

Syntax

Enumeration

Values & Constraints

Enumerated Values
1noBreaker
2unknown
3breakerOpen
4breakerClosed