HUAWEI-POWER-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
16
Rows
16
Columns
160
.1.3.6.1.4.1.2011.6.2.1.1 · 1 row entry · 14 columns
Power basic information table. The indexes of this table are hwEnvEmuIndex 
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is 
the index of the monitoring unit. hwPowerIndex is the index of the power 
supply monitored by the monitoring unit.
hwPowerSysInfoEntry entry .1.3.6.1.4.1.2011.6.2.1.1.1
Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwPowerIndex
Index of the power supply monitored by the monitoring unit
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.1
hwPowerType
Type of the Power emu device.
Options:
1.power4875(1) - Type of the Power emu device is power4875
2.power4810(2) - Type of the Power emu device is power4810 …
Enumerationr/w
Enumerated Values:
1power4875
2power4810
3power48100
4power4850
5power48240
6power48120
7power48300
8power48240SinglePhase
9universalPower
10power4845
11rpower
15power4805
16power4820
17onps
18power4875l
100psma
101permAl175nt
102mcs1800
103mcs1800A
104mcs3000
105sm40sm60
106scu
107eltek
108dk04
109dk04C
110dpc
120power4830
121h831pmua
122power3000
123liFeBattery
125etp4830
126etp4890
127h801pmu
128etp48150
129etp4850
130etp48200
131etp4860
255other
.1.3.6.1.4.1.2011.6.2.1.1.1.2
hwPowerName
Power name.
Invalid: null string.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2011.6.2.1.1.1.3
hwPowerState
Power board status:
Refers to the status of communication between the internal monitor board
of the power device and the external upper board.
Options:
1.normal(1) - indicates the normal state
2.fault(2) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protecting
4switched
.1.3.6.1.4.1.2011.6.2.1.1.1.4
hwPowerRowStatus
RowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status.
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.1.1.5
hwPowerControlMode
Control mode of the power monitor module.
Options:
1.manualControl(1) - control by manual, the remote mode
2.autoControl(2) - auto control mode, the default is auto control mode
3.invalid(-1) - indicates that th…
Enumerationr/w
Enumerated Values:
-1invalid
1manualControl
2autoControl
.1.3.6.1.4.1.2011.6.2.1.1.1.6
hwPowerRemoteFrameID
Apply for remote power system.
It is the frame ID that the remote unit exists in
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.1.1.7
hwPowerProtect
Apply for remote power system.
It is used to enable or disable N+1 protection function.
Options:
1.protect(1) - enables the N+1 protection function
2.undoProtect(2) - disables the N+1 protection function
Enumerationr/w
Enumerated Values:
1protect
2undoProtect
.1.3.6.1.4.1.2011.6.2.1.1.1.8
hwPowerVersion
Version of power
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2011.6.2.1.1.1.9
hwPowerSupplyState
Power supply modes.
Options:
1.ac(1) - indicates the AC power supply
2.battery(2) - indicates power supply by the batteries
Enumeration
Enumerated Values:
1ac
2battery
.1.3.6.1.4.1.2011.6.2.1.1.1.10
hwPowerWiringCheckSwitch
Power wiring check switch of SMU.
Options:
1. disable(1) - indicates that the power wiring check state of SMU is disabled
2. enable(2) - indicates that the power wiring check state is enabled
3. invalid(-1) …
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.1.1.11
hwPowerLatitude
The power latitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.12
hwPowerLongitude
The power longitude value.
Invalid: -.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.1.1.13
hwPowerBluetoothSwitch
Power bluetooth state of SMU.
Options:
1. enable(0) - indicates that the power bluetooth state of SMU is enabled.
2. disable(1) - indicates that the power bluetooth state of SMU is disabled.
3. invalid(-1) - indic…
Enumerationr/w
Enumerated Values:
-1invalid
0enable
1disable
.1.3.6.1.4.1.2011.6.2.1.1.1.14
.1.3.6.1.4.1.2011.6.2.1.2 · 1 row entry · 14 columns
AC input table. Through this table, 
AC input monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 48100 power supply, and 48240 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. 
hwEnvEmuIndex is the index of the monitoring unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
hwACInputEntry entry .1.3.6.1.4.1.2011.6.2.1.2.1
AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwACLoopIndex
Column Syntax OID
hwACLoopIndex
Input loop index. There are two channels of AC current input,
which are the backup for each other.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.2.1.1
hwACPowerState
Status of power supply.
Options:
1.normal(1) - indicates that the power supply is normal
2.offline(2) - indicates that the power supply is offline
3.exceedVoltage(3) - indicates that the power supply is …
Enumeration
Enumerated Values:
-1invalid
1normal
2offline
3exceedVoltage
4belowVoltage
5backup
.1.3.6.1.4.1.2011.6.2.1.2.1.2
hwACVoltA
AC Inuput voltage A.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.3
hwACCurrentA
AC input Current A.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.4
hwACVoltB
AC input voltage B.
Unit: mv
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.5
hwACCurrentB
AC input current B.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.6
hwACVoltC
AC input voltage C.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.7
hwACCurrentC
AC input current C.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.8
hwACVoltageHigh
AC input over-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.9
hwACVoltageLow
AC input under-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.2.1.10
hwACRowStatus
Only the add operation, delete operation, and status query operation are supported.
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.2.1.11
hwACVoltageAState
Phase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.12
hwACVoltageBState
Phase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.13
hwACVoltageCState
Phase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage …
Enumeration
Enumerated Values:
-1invalid
0normal
1belowVoltage
2exceedVoltage
3missingPhase
.1.3.6.1.4.1.2011.6.2.1.2.1.14
.1.3.6.1.4.1.2011.6.2.1.3 · 1 row entry · 13 columns
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply, 
4810 power supply, 482400 power supply, and 48100 power supply can 
be set and queried.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, 
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwDCOutEntry entry .1.3.6.1.4.1.2011.6.2.1.3.1
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwDCVoltageOut
DC voltage output.
Unit: mV.
invalid: -1
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.1
hwDCCurrentOut
DC current output.
Unit: mA
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.2
hwDCVoltageOutHigh
Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.3
hwDCVoltageOutLow
Output DC below-voltage alarm point . Default value is 45V.
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.4
hwDCVoltageOutState deprecated
DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage
3. belowVol…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.5
hwDCCurrentOutHigh
Output DC exceed-current alarm point .
Unit: mA
mAMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.6
hwDCCurrentOutLow
Output below-current alarm point .
Unit: mA
mAMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.7
hwDCCurrentOutState deprecated
DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage
3.belowVoltage(3) - in…
Enumeration
Enumerated Values:
-1invalid
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.3.1.8
hwDCOutRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.3.1.9
hwDCOutLoadCurrent
Total load current of DC output .
Unit: mA.
invalid: -1
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.10
hwDCOutLoadTmpHigh
The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.3.1.11
hwDCOutRunState
DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.batteryVoltageOver(2) - indicates outpu…
Bits
Enumerated Values:
0battery1ChargeCurOver
1battery2ChargeCurOver
2batteryVoltageOver
3batteryVoltageLack
4loadOff
5batteryOff
6communicationFailure
7dcOutManual
.1.3.6.1.4.1.2011.6.2.1.3.1.12
hwDCCommunicationState
DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.3.1.13
.1.3.6.1.4.1.2011.6.2.1.4 · 1 row entry · 10 columns
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwLoadIndex is the index of the monitored load.
hwLoadinfoEntry entry .1.3.6.1.4.1.2011.6.2.1.4.1
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwLoadIndex
Column Syntax OID
hwLoadIndex
Loop index: usually each DC output loop corresponds to a load.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.1
hwLoadInfoAdminState
Load operation.
Options:
1. on(1) - indicates that the Load is enabled
2. off(2) - indicates that the Load is disabled
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not s…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.2
hwLoadInfoOperStatus
Status of power supply.
Options:
1. normal(1) - indicates that the state of power supply is normal
2. abnormal(2) - indicates that the state of power supply is abnormal
3. stop(3) - indicates that the state …
Enumeration
Enumerated Values:
-1invalid
1normal
2abnormal
3stop
.1.3.6.1.4.1.2011.6.2.1.4.1.3
hwLoadCurrent
Present current .
Unit: mA
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.4.1.4
hwLoadVoltage
Present voltage .
Unit: mV
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.4.1.5
hwLoadVoltageHigh
Off voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off.
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.4.1.6
hwLoadLoadName
Load name: usually each DC output loop corresponds to a load.
SNMPv2-TCDisplayStringr/w
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2011.6.2.1.4.1.7
hwLoadInfoRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.4.1.8
hwLoadFuseState
Load fuse state, including the auxiliary load fuse.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.4.1.9
hwLoadHoreIndex
load hore index
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.4.1.10
.1.3.6.1.4.1.2011.6.2.1.5 · 1 row entry · 9 columns
Rectifier module table. 
Through this table, the status information of the rectifier module 
can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable,
is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRectifierIndex is the index of the monitored rectifier module under the power supply.
hwRectifierEntry entry .1.3.6.1.4.1.2011.6.2.1.5.1
Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwRectifierIndex
Column Syntax OID
hwRectifierIndex
Rectifier Module index. There are multiple rectifier
modules to a power source.
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.5.1.1
hwRectifierAdminState
Switch operation of rectifier module.
Options:
1.on(1) - indicates that the Rectifier module is enabled
2.off(2) - indicates that the Rectifier module is disabled
3.invalid(-1) - indicates that the devic…
Enumerationr/w
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.5.1.2
hwRectifierOperState
Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options:
1. normal(1) - indicates that the Rectifier operation state is normal
2.…
Enumeration
Enumerated Values:
-1invalid
1normal
2fault
3protect
4communicationFailure
5on
6noConfig
7offline
8close
.1.3.6.1.4.1.2011.6.2.1.5.1.3
hwRectifierVoltage
Output voltage .
Unit: mV
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.5.1.4
hwRectifierCurrent
Output current .
Unit: mA
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.5.1.5
hwRectifierRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.5.1.6
hwRectifierCurrentLimit
current limit switch
SNMPv2-TCTruthValuer/w
Textual Convention: SNMPv2-TCTruthValue Enumeration
Type Values:
1true
2false
.1.3.6.1.4.1.2011.6.2.1.5.1.7
hwRectifierRunState
Running state of rectifier module.
Options:
1.rectifierOn(0) - indicates that the module is on
2.averageCharge(1) - indicates that the module is being averagely charged.
3.output(2) - indicates that the mod…
Bits
Enumerated Values:
0rectifierOn
1averageCharge
2output
3isLimit
.1.3.6.1.4.1.2011.6.2.1.5.1.8
hwRectifierChargeState
Charging state of rectifier.
Options:
1. float(0) - indicates that the Charge state of Rectifier is float
2. average(1) - indicates that the Charge state of Rectifier is average
3. test(2) - indicates that t…
Enumeration
Enumerated Values:
0float
1average
2test
.1.3.6.1.4.1.2011.6.2.1.5.1.9
.1.3.6.1.4.1.2011.6.2.1.6.1 · 1 row entry · 15 columns
Basic information table of battery group. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryGroupEntry entry .1.3.6.1.4.1.2011.6.2.1.6.1.1
Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwBatteryGroupCapacity
Total capacity of the present battery group.
Unit: Ah
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.1.1.1
hwBatteryGroupCapcaityRemain
Total remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
Unit: Ah
Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.1.1.2
hwBatteryGroups
Number of battery group
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.1.1.3
hwBatteryGroupVoltageLow
When the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.4
hwBatteryGroupChargeLimit
Charge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percent
percentMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.5
hwBatteryGroupRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.6.1.1.6
hwBatteryGroupOperStatus
The State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal.
When the mains supply is ab…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7
hwBatteryGroupVoltageHigh
When the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.8
hwBatteryGroupTwiceOffVoltage
The twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.9
hwBatteryGroupProtectVoltage
The first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.10
hwBatteryGroupTmpOffHigh
The high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degree
0.01 degreeMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.11
hwBatteryInstallTime
The installing date of battery group.
SNMPv2-TCDisplayString
Textual Convention: SNMPv2-TCDisplayString OctetString
Type Constraints:
range: 0..255
.1.3.6.1.4.1.2011.6.2.1.6.1.1.12
hwBatteryGroupBomCode
The BOM code of battery.
Invalid: null string.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2011.6.2.1.6.1.1.13
hwBatteryGroupType
The type of lead-acid battery.
1: general.
2: tcbc.
3: tcbb.
Enumerationr/w
Enumerated Values:
1general
2tcbc
3tcbb
.1.3.6.1.4.1.2011.6.2.1.6.1.1.14
hwLiBatteryGroupChargeLimit
The charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host.
user uses it which has been lessened 1000 by SNMP.
Default: 1050.
The invalid value -1 indicates that the device can not ge…
Integer32r/w
Constraints:
range: 50-1050
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.1.1.15
.1.3.6.1.4.1.2011.6.2.1.6.2 · 1 row entry · 7 columns
Charge management table. 
Through this table, the charging parameter of the battery can be set and queried. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwChargeEntry entry .1.3.6.1.4.1.2011.6.2.1.6.2.1
Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwChargeAdminStatus
Charge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is float charge
3. auto(3) - indicate…
Enumerationr/w
Enumerated Values:
-1invalid
1average
2float
3auto
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1
hwChargeOperStatus
Charge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float charge
3. full(3) - indicates that t…
Enumeration
Enumerated Values:
-1invalid
1average
2float
3full
4noCharge
5discharge
6sleep
.1.3.6.1.4.1.2011.6.2.1.6.2.1.2
hwAverageChargeVoltage
Voltage value of average charge, in unit of mV.
Default: 56500
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.2.1.3
hwFloatChargeVoltage
Voltage value of float charge .
Default: 53500
Unit: mV
mVMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.2.1.4
hwChargeControlRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.6.2.1.5
hwAverageChargeTime
Timing average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: day
daySNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6
hwBatteryTmpRedeemingQuotiety
Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease
with the increasing of every degree ce…
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.2.1.7
.1.3.6.1.4.1.2011.6.2.1.6.3 · 1 row entry · 22 columns
Battery group state table. 
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. 
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryIndex is the index of the monitored battery group.
hwBatteryEntry entry .1.3.6.1.4.1.2011.6.2.1.6.3.1
Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwBatteryIndex
Column Syntax OID
hwBatteryIndex
Battery group loop index
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.3.1.1
hwBatteryCapacity
The permitted max battery capacity of the battery group loop charge.
Unit: Ah
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.2
hwBatteryLoopState
The battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery group is off
3. invalid(-1) - indicates…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.3
hwBatteryVoltage
The loop voltage of the battery group.
Unit: mV
invalid: -1
mVMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.3.1.4
hwBatteryOperStatus
The present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the present state of the battery group loop i…
Enumeration
Enumerated Values:
-1invalid
1charge
2discharge
.1.3.6.1.4.1.2011.6.2.1.6.3.1.5
hwBatteryCurrent
Present current .
Unit: mA
invalid: -1
mAMeasuresRange
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.3.1.6
hwBatteryTemperature
The loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.7
hwBatteryRowStatus
RowStatus standard operation
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.6.3.1.8
hwBatteryCurrentHigh
The over-current alarm point of the battery group.
Unit: mA
mAMeasuresRanger/w
Textual Convention: MeasuresRange Integer32
.1.3.6.1.4.1.2011.6.2.1.6.3.1.9
hwBatteryFuseState
Battery fuse state.
Options:
1. on(1) - indicates that the fuse is connected
2. off(2) - indicates that the fuse is disconnected
3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU …
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10
hwBatteryContactState
The state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(-1) - indicates that the device can not…
Enumeration
Enumerated Values:
-1invalid
1on
2off
.1.3.6.1.4.1.2011.6.2.1.6.3.1.11
hwBatteryRemainCapacity
Remain capacity of the battery,
invalid(-1)
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.12
hwBatteryProtectState
Protection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Protection status of the battery is overte…
Enumeration
Enumerated Values:
1normal
2overtemperature
3overCurrent
.1.3.6.1.4.1.2011.6.2.1.6.3.1.13
hwBatteryVoltageState
Voltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage
3. belowVoltage(3) - indicat…
Enumeration
Enumerated Values:
1normal
2exceedVoltage
3belowVoltage
.1.3.6.1.4.1.2011.6.2.1.6.3.1.14
hwBatteryHardwareState
Hardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is fault
Enumeration
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.6.3.1.15
hwBatteryLowTemperature
The lowest loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF)
degreeSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.16
hwBatteryAntiTheftSwitch
Anti-theft switch of Battery.
Options:
1. disable(1) - indicates that the anti-theft state of Battery is disabled
2. enable(2) - indicates that the anti-theft state of Battery is enabled
3. invalid(-1) - ind…
Enumerationr/w
Enumerated Values:
-1invalid
1disable
2enable
.1.3.6.1.4.1.2011.6.2.1.6.3.1.17
hwBatteryAntiTheftTimeout
The anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation.
hourInteger32r/w
Constraints:
range: 8-720
range: -1--1
.1.3.6.1.4.1.2011.6.2.1.6.3.1.18
hwBatterySequence
The sequence of LiBattery.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.19
hwBatteryAddress
The address of LiBattery which corresponds to the subnode of LiBattery.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.3.1.20
hwBatteryHeaterState
The state of battery heater.
Enumeration
Enumerated Values:
-1invalid
1on
2off
3noconfig
.1.3.6.1.4.1.2011.6.2.1.6.3.1.21
hwBatteryHealthState
The health state of battery.
Unit:%
invalid:-1
%Integer32
Constraints:
range: -1-100
.1.3.6.1.4.1.2011.6.2.1.6.3.1.22
.1.3.6.1.4.1.2011.6.2.1.6.4 · 1 row entry · 11 columns
Battery test table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex. 
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwBatteryTestEntry entry .1.3.6.1.4.1.2011.6.2.1.6.4.1
Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwBatteryTestAdminStatus
Battery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. enableAutoTest(3) - indicates that th…
Enumerationr/w
Enumerated Values:
1start
2terminate
3enableAutoTest
4disableAutoTest
5timeautoTest
6offautoTest
7timeoffautoTest
.1.3.6.1.4.1.2011.6.2.1.6.4.1.1
hwBatteryTestAutoDischargePeriod
Auto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day
daySNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.2
hwBatteryTestResult obsolete
Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed normally
3. alarmTerminated(3) - indicates…
Enumeration
Enumerated Values:
1testing
2complete
3alarmTerminated
4hostTerminated
5overtimeTerminated
6normal
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.4.1.3
hwBatteryTestStartTime obsolete
Time of starting test
SNMPv2-TCDateAndTime
Textual Convention: SNMPv2-TCDateAndTime OctetString
Type Constraints:
range: 8
range: 11
.1.3.6.1.4.1.2011.6.2.1.6.4.1.4
hwBatteryTestDuration
Battery discharge test duration.
Effective range is 1-100 hours.
Default :value is 10 hours
Unit: hour
hourSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5
hwBatteryTestTerminateVoltage
Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV
mVSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.6
hwBatteryTestTotalDischargeAH obsolete
Total discharge AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.7
hwBatteryTestOperStatus
Battery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto discharge test is disabled
3. timeautoTestPer…
Enumeration
Enumerated Values:
1autoTestPermit
2autoTestForbid
3timeautoTestPermit
4offautoTestPermit
5timeoffautoTestPermit
.1.3.6.1.4.1.2011.6.2.1.6.4.1.8
hwBatteryTestPhase
Battery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. record(3) - indicates the powe…
Enumeration
Enumerated Values:
1charge
2discharge
3record
4finish
5waitingfordischarge
.1.3.6.1.4.1.2011.6.2.1.6.4.1.9
hwBatteryTestStartHour
Discharge start time.
Effective range is 0 23
Default: 0
Unit: hour
hourSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.10
hwBatteryTestAlarmThreshold
The battery discharge test alarm threshold in ratio of the range:1~79.
percentSNMPv2-SMIInteger32r/w
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.4.1.11
.1.3.6.1.4.1.2011.6.2.1.6.5 · 1 row entry · 10 columns
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryLogTestIndex is the index of the monitored battery.
hwBatteryLogTestEntry entry .1.3.6.1.4.1.2011.6.2.1.6.5.1
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwBatteryLogTestIndex
Column Syntax OID
hwBatteryLogTestIndex
Battery discharge test result index
Integer32
Constraints:
range: 0-255
.1.3.6.1.4.1.2011.6.2.1.6.5.1.1
hwBatteryLogTestStartTime
Battery discharge test start time
SNMPv2-TCDateAndTime
Textual Convention: SNMPv2-TCDateAndTime OctetString
Type Constraints:
range: 8
range: 11
.1.3.6.1.4.1.2011.6.2.1.6.5.1.2
hwBatteryLogTestDischargeDuration
Duration of discharge.
Unit: minute
minuteSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.3
hwBatteryLogTestTerminateVoltage
End voltage of battery discharge test .
Unit: mV
mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.4
hwBatteryLogTestBatteryStatus
Battery status.
Options:
1. expectant(1) - indicates the batter test state is expectant
2. unexpected(2) - indicates the batter test state is unexpected
3. unknown(3) - indicates the batter test state is unknown
Enumeration
Enumerated Values:
1expectant
2unexpected
3unknown
.1.3.6.1.4.1.2011.6.2.1.6.5.1.5
hwBatteryLogTestTotalDischargeAH
Discharge cumulate AH.
Unit: mAH
mAHSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.6
hwBatteryLogTestFinish
Battery Test result.
Options:
1. testing(1) - indicates that it is during testing
2. completed(2) - indicates that the test is completed normally
3. alarmTerminated(3) - indicates that the test is …
Enumeration
Enumerated Values:
1testing
2completed
3alarmTerminated
4hostTerminated
5overtimeTerminated
6notTest
7supplyRecoverAutotestTerminated
.1.3.6.1.4.1.2011.6.2.1.6.5.1.7
hwBatteryLogTestEfficiency
The information of battery test efficiency.
percentSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.8
hwBatteryLogTestBatteryTemperature
Battery discharge test end Temperature.
Unit: 0.01 Degree
Invaild: 0X7FFFFFFF
0.01 DegreeSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.9
hwBatteryLogTestBatteryCurrent
Battery discharge test average Current.
Unit: mA
mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.5.1.10
.1.3.6.1.4.1.2011.6.2.1.6.6 · 1 row entry · 3 columns
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit. 
hwPowerIndex is the index of the power supply monitored by the monitoring unit. 
hwBatteryCellIndex is the index of the battery cell.
hwBatteryCellEntry entry .1.3.6.1.4.1.2011.6.2.1.6.6.1
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex hwBatteryCellIndex
Column Syntax OID
hwBatteryCellIndex
The index of battery cell.
Integer32
Constraints:
range: 0-15
.1.3.6.1.4.1.2011.6.2.1.6.6.1.1
hwBatteryCellTemperature
The temperature of battery cell.
Unit: C
Non-value: 0x7FFFFFFF
CSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.2
hwBatteryCellVoltage
The voltage of battery cell.
Unit: mV
Non-value: -1
mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.6.6.1.3
.1.3.6.1.4.1.2011.6.2.1.7 · 1 row entry · 10 columns
Remote provide power basic information table. 
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit, 
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
hwRemoteProvidePowerInfoEntry entry .1.3.6.1.4.1.2011.6.2.1.7.1
Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwPowerCentralState
State of the central module.
Options:
1. normal(1) - indicates the normal state
2. temOver(2) - indicates the over-temperature
Enumeration
Enumerated Values:
1normal
2temOver
.1.3.6.1.4.1.2011.6.2.1.7.1.1
hwPowerCentralDCInPutState
State of central module DC input:
Options:
1.normal(1) - indicates the normal state
2.lack(2) - indicates the voltage underflow
3.over(3) - indicates the voltage overflow
Enumeration
Enumerated Values:
1normal
2lack
3over
.1.3.6.1.4.1.2011.6.2.1.7.1.2
hwPowerCentralDCOutputState
State of central module DC output.
Options:
1. normal(1) - indicates the normal state
2. volLack(2) - indicates the voltage underflow
3. volOver(3) - indicates the voltage overflow
4. loadOver(4) …
Enumeration
Enumerated Values:
1normal
2volLack
3volOver
4loadOver
5shortCircuit
6noLoad
.1.3.6.1.4.1.2011.6.2.1.7.1.3
hwPowerCentralDCOutputMode
Mode of central module DC output.
Options:
1. highVolMode(1) - indicates the high voltage output mode
2. lowVolMode(2) - indicates the low voltage output mode
Enumeration
Enumerated Values:
1highVolMode
2lowVolMode
.1.3.6.1.4.1.2011.6.2.1.7.1.4
hwPowerRemoteCommState
Remote power module communications state.
Options:
1. normal(1) - indicates the normal state
2. revfault(2) - indicates the receiving of fault
3. sendfault(3) - indicates the sending of fault
Enumerationr/w
Enumerated Values:
1normal
2revfault
3sendfault
.1.3.6.1.4.1.2011.6.2.1.7.1.5
hwPowerRemoteDCInputState
State of remote module DC input.
Options:
1. normal(1) - indicates the normal state
2. lack(2) - indicates that the voltage is underflow
Enumerationr/w
Enumerated Values:
1normal
2lack
.1.3.6.1.4.1.2011.6.2.1.7.1.6
hwPowerRemoteLineCurState
state of line between central and remote module.
Options:
1.normal(1) - indicates the normal state
2.cablejoining(2) - indicates the cable joining
3.curLeakage(3) - indicates the cur Leakage
4.curOver(4) - …
Enumerationr/w
Enumerated Values:
1normal
2cablejoining
3curLeakage
4curOver
.1.3.6.1.4.1.2011.6.2.1.7.1.7
hwPowerRemotePowerState
state of remote UA60 power.
Options:
1. normal(1) - indicates the normal state
2. fault(2) - indicates the faulty state
Enumerationr/w
Enumerated Values:
1normal
2fault
.1.3.6.1.4.1.2011.6.2.1.7.1.8
hwPowerRemoteLineState
State of line U1.
Options:
1. u1state(0) - indicates the power remote line state is u1 state
2. u2state(1) - indicates the power remote line state is u2 state
3. u3state(2) - indicates the power remote line state is u3 …
Bitsr/w
Enumerated Values:
0u1state
1u2state
2u3state
3u4state
4a1state
5a2state
6a3state
7a4state
.1.3.6.1.4.1.2011.6.2.1.7.1.9
hwPowerCentralLoadState
state of central load.
Options:
1. normal(1) - indicates the normal state
2. overload(2) - indicates overload
3. nonload(3) - indicates non-load
Enumerationr/w
Enumerated Values:
1normal
2overload
3nonload
.1.3.6.1.4.1.2011.6.2.1.7.1.10
.1.3.6.1.4.1.2011.6.2.1.8 · 1 row entry · 6 columns
AC infomation table.  The table is not supported.
The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
hwACInfomationEntry entry .1.3.6.1.4.1.2011.6.2.1.8.1
AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
Column Syntax OID
hwACInfoCommState
communication state of AC input module.
The node is not supported.
Options:
1. normal(0) - indicates the communication state of AC is normal
2. fault(1) - indicates the communication state of AC is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.1
hwACInfoThunderState
Thunder's state.
The node is not supported.
Options:
1. normal(0) - indicates the state of Thunder is normal
2. fault(1) - indicates the state of Thunder is fault
Enumeration
Enumerated Values:
0normal
1fault
.1.3.6.1.4.1.2011.6.2.1.8.1.2
hwACInfoCurrentLoop
Current AC input working loop.
The leaf is not supported.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.3
hwACInfoMCBTrigger
AC input MCB trigger state.
The leaf is not supported.
Options:
1. normal(0) - indicates the AC input MCB trigger state is normal
2. breakDown(1)- indicates the AC input MCB trigger state is break-down
Enumeration
Enumerated Values:
0normal
1breakDown
.1.3.6.1.4.1.2011.6.2.1.8.1.4
hwACInfoFrequency
The infomation of AC input frequency.
This leaf is not supported.
Unit: HZ
HZSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.1.8.1.5
hwACInfoRowStatus
RowStatus standard operation
The leaf is not supported.
SNMPv2-TCRowStatusr/w
Textual Convention: SNMPv2-TCRowStatus Enumeration
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
.1.3.6.1.4.1.2011.6.2.1.8.1.6
.1.3.6.1.4.1.2011.6.2.5.1 · 1 row entry · 4 columns
Remote power system, remote unit basic information table. The indexes of 
this entry is hwEnvEmuIndex.
hwRemoteUnitSysInfoEntry entry .1.3.6.1.4.1.2011.6.2.5.1.1
Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
Indexes
Column Syntax OID
hwRemoteUnitPowerSystype
Type of the remote unit power system.
Options:
1.rftv(1) - Type of the remote unit power system is RFT-V
2.rftc(2) - Type of the remote unit power system is RFT-C …
Enumeration
Enumerated Values:
1rftv
2rftc
255invalid
.1.3.6.1.4.1.2011.6.2.5.1.1.1
hwRemoteUnitDCOutputVol
The remote unit DC output voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.2
hwRemoteUnitDCOutputCur
The remote unit DC output current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.3
hwRemoteUnitSlotNum
The remote unit slot number.
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.1.1.4
.1.3.6.1.4.1.2011.6.2.5.2 · 1 row entry · 8 columns
Remote power system, remote unit slot information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
hwRemoteUnitSlotEntry entry .1.3.6.1.4.1.2011.6.2.5.2.1
Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwRemoteUnitSlotIndex
Column Syntax OID
hwRemoteUnitSlotIndex
The remote unit slot index.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.1
hwRemoteUnitSlotCircuitNum
The remote unit slot circuit number.
Invalid:-1.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.2
hwRemoteUnitSlotHardVersion
The remote unit slot hard version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.3
hwRemoteUnitSlotSoftVersion
The remote unit slot soft version.
Invalid: null string.
OctetString
Constraints:
range: 1-128
.1.3.6.1.4.1.2011.6.2.5.2.1.4
hwRemoteUnitSlotStatus
The state of the remote unit slot.
Options:
1.normal(1) - The state of the remote unit slot is normal
2.fault(2) - The state of the remote unit slot is fault
3.null(3) - The sta…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.5
hwRemoteUnitSlotAdminStatus
Delete the remote unit slot.
Options:
1.delete(1) - Delete the remote unit slot
2.invalid(255) - Unknown
Enumerationr/w
Enumerated Values:
1delete
255invalid
.1.3.6.1.4.1.2011.6.2.5.2.1.6
hwRemoteUnitSlotDCOutputVol
The remote unit slot DC output voltage.
Invalid:-1.
mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.7
hwRemoteUnitSlotDCOutputCur
The remote unit slot DC output current.
Invalid:-1.
mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.2.1.8
.1.3.6.1.4.1.2011.6.2.5.3 · 1 row entry · 4 columns
Remote power system, remote unit circuit information table. The indexes of 
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
hwRemoteUnitCircuitEntry entry .1.3.6.1.4.1.2011.6.2.5.3.1
Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwRemoteUnitSlotIndex hwRemoteUnitCircuitIndex
Column Syntax OID
hwRemoteUnitCircuitIndex
The remote unit circuit index.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.1
hwRemoteUnitCircuitInputVol
The remote unit circuit input voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mVSNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.2
hwRemoteUnitCircuitInputCur
The remote unit circuit input current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
mASNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2011.6.2.5.3.1.3
hwRemoteUnitCircuitState
The state of the remote unit circuit.
Options:
1.normal(1) - The state of the remote unit circuit is normal
2.fault(2) - The state of the remote unit circuit is fault
3.null(3) -…
Enumeration
Enumerated Values:
1normal
2fault
3null
255invalid