HUAWEI-POWER-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
16
Rows
16
Columns
160
hwPowerSysInfoTable
table.1.3.6.1.4.1.2011.6.2.1.1
·
1 row entry
·
14 columns
Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Power basic information table. The indexes of this entry are hwEnvEmuIndex
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is
the index of the monitoring unit. hwPowerIndex is the index of the po…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwPowerIndex
Index of the power supply monitored by the monitoring unit
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.1.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerType
Type of the Power emu device.
Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerName
Power name.
Invalid: null string. |
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.2011.6.2.1.1.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerState
Power board status:
Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - in… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerRowStatus
RowStatus standard operation. The values 1 and 2 are supported currently.
1 indicates the activation status, and 2 indicates the non-activation status. |
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerControlMode
Control mode of the power monitor module.
Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that th… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerRemoteFrameID
Apply for remote power system.
It is the frame ID that the remote unit exists in |
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.1.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerProtect
Apply for remote power system.
It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerVersion
Version of power
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.2011.6.2.1.1.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerSupplyState
Power supply modes.
Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.10 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerWiringCheckSwitch
Power wiring check switch of SMU.
Options: 1. disable(1) - indicates that the power wiring check state of SMU is disabled 2. enable(2) - indicates that the power wiring check state is enabled 3. invalid(-1) … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.11 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerLatitude
The power latitude value.
Invalid: -. |
OctetString Constraints: range: 0-32 |
.1.3.6.1.4.1.2011.6.2.1.1.1.12 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerLongitude
The power longitude value.
Invalid: -. |
OctetString Constraints: range: 0-32 |
.1.3.6.1.4.1.2011.6.2.1.1.1.13 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
hwPowerBluetoothSwitch
Power bluetooth state of SMU.
Options: 1. enable(0) - indicates that the power bluetooth state of SMU is enabled. 2. disable(1) - indicates that the power bluetooth state of SMU is disabled. 3. invalid(-1) - indic… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.1.1.14 |
hwACInputTable
table.1.3.6.1.4.1.2011.6.2.1.2
·
1 row entry
·
14 columns
AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit.
AC input table. Through this table,
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
AC input monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 48100 power supply, and 48240 power supply can
be set and queried.
The indexes of this ent…
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwACLoopIndex
Input loop index. There are two channels of AC current input,
which are the backup for each other. |
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.2.1.1 |
||||||||||||
|
hwACPowerState
Status of power supply.
Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.2.1.2 |
||||||||||||
|
hwACVoltA
AC Inuput voltage A.
Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.3 |
||||||||||||
|
hwACCurrentA
AC input Current A.
Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.4 |
||||||||||||
|
hwACVoltB
AC input voltage B.
Unit: mv invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.5 |
||||||||||||
|
hwACCurrentB
AC input current B.
Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.6 |
||||||||||||
|
hwACVoltC
AC input voltage C.
Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.7 |
||||||||||||
|
hwACCurrentC
AC input current C.
Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.8 |
||||||||||||
|
hwACVoltageHigh
AC input over-voltage alarm threshold.
Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.9 |
||||||||||||
|
hwACVoltageLow
AC input under-voltage alarm threshold.
Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.2.1.10 |
||||||||||||
|
hwACRowStatus
Only the add operation, delete operation, and status query operation are supported.
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.2.1.11 |
||||||||||||
|
hwACVoltageAState
Phase AB/A of AC input state.
Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.2.1.12 |
||||||||||||
|
hwACVoltageBState
Phase BC/B of AC input state.
Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.2.1.13 |
||||||||||||
|
hwACVoltageCState
Phase CA/C of AC input state.
Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.2.1.14 |
hwDCOutTable
table.1.3.6.1.4.1.2011.6.2.1.3
·
1 row entry
·
13 columns
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
DC output table. Through this table,
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
DC output monitoring parameters of 4875 power supply, 4845 power supply,
4810 power supply, 482400 power supply, and 48100 power supply can
be set and queried.
The indexes of this …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwDCVoltageOut
DC voltage output.
Unit: mV. invalid: -1 |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.1 |
||||||||||||||||
|
hwDCCurrentOut
DC current output.
Unit: mA |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.2 |
||||||||||||||||
|
hwDCVoltageOutHigh
Output DC exceed-voltage alarm point.
Default: 58000 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.3 |
||||||||||||||||
|
hwDCVoltageOutLow
Output DC below-voltage alarm point . Default value is 45V.
Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.4 |
||||||||||||||||
|
hwDCVoltageOutState
deprecated
DC output voltage status.
Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVol… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.3.1.5 |
||||||||||||||||
|
hwDCCurrentOutHigh
Output DC exceed-current alarm point .
Unit: mA |
mAMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.6 |
||||||||||||||||
|
hwDCCurrentOutLow
Output below-current alarm point .
Unit: mA |
mAMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.7 |
||||||||||||||||
|
hwDCCurrentOutState
deprecated
DC output current status.
Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - in… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.3.1.8 |
||||||||||||||||
|
hwDCOutRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.3.1.9 |
||||||||||||||||
|
hwDCOutLoadCurrent
Total load current of DC output .
Unit: mA. invalid: -1 |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.10 |
||||||||||||||||
|
hwDCOutLoadTmpHigh
The off protection point under the load temperature, by default,
it is 65 degrees centigrade. Unit: 0.01 degree |
0.01 degreeMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.3.1.11 |
||||||||||||||||
|
hwDCOutRunState
DC output running status.
Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates outpu… |
Bits Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.3.1.12 |
||||||||||||||||
|
hwDCCommunicationState
DC communication status.
Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.3.1.13 |
hwLoadinfoTable
table.1.3.6.1.4.1.2011.6.2.1.4
·
1 row entry
·
10 columns
Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load.
Load information table. Through this table, the load parameter can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex.
hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, …
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwLoadIndex
Loop index: usually each DC output loop corresponds to a load.
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.4.1.1 |
||||||||||||
|
hwLoadInfoAdminState
Load operation.
Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not s… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.4.1.2 |
||||||||||||
|
hwLoadInfoOperStatus
Status of power supply.
Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.4.1.3 |
||||||||||||
|
hwLoadCurrent
Present current .
Unit: mA |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.4.1.4 |
||||||||||||
|
hwLoadVoltage
Present voltage .
Unit: mV |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.4.1.5 |
||||||||||||
|
hwLoadVoltageHigh
Off voltage (Stop external voltage), in unit of mV,
When DC output voltage exceeds the value, the load will be automatically cut off. Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.4.1.6 |
||||||||||||
|
hwLoadLoadName
Load name: usually each DC output loop corresponds to a load.
|
SNMPv2-TCDisplayStringr/w Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.2011.6.2.1.4.1.7 |
||||||||||||
|
hwLoadInfoRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.4.1.8 |
||||||||||||
|
hwLoadFuseState
Load fuse state, including the auxiliary load fuse.
Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.4.1.9 |
||||||||||||
|
hwLoadHoreIndex
load hore index
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.4.1.10 |
hwRectifierTable
table.1.3.6.1.4.1.2011.6.2.1.5
·
1 row entry
·
9 columns
Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply.
Rectifier module table.
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Through this table, the status information of the rectifier module
can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex.
hwEnvEmuIndex, which …
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwRectifierIndex
Rectifier Module index. There are multiple rectifier
modules to a power source. |
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.5.1.1 |
||||||||||||||||||
|
hwRectifierAdminState
Switch operation of rectifier module.
Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the devic… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.2 |
||||||||||||||||||
|
hwRectifierOperState
Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device.
Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2.… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.3 |
||||||||||||||||||
|
hwRectifierVoltage
Output voltage .
Unit: mV Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.5.1.4 |
||||||||||||||||||
|
hwRectifierCurrent
Output current .
Unit: mA Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.5.1.5 |
||||||||||||||||||
|
hwRectifierRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.6 |
||||||||||||||||||
|
hwRectifierCurrentLimit
current limit switch
|
SNMPv2-TCTruthValuer/w Textual Convention: SNMPv2-TCTruthValue EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.7 |
||||||||||||||||||
|
hwRectifierRunState
Running state of rectifier module.
Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the mod… |
Bits Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.8 |
||||||||||||||||||
|
hwRectifierChargeState
Charging state of rectifier.
Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that t… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.5.1.9 |
hwBatteryGroupTable
table.1.3.6.1.4.1.2011.6.2.1.6.1
·
1 row entry
·
15 columns
Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Basic information table of battery group.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by …
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwBatteryGroupCapacity
Total capacity of the present battery group.
Unit: Ah |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.1 |
||||||||||||
|
hwBatteryGroupCapcaityRemain
Total remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah |
Integer32 Constraints: range: -1-100 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.2 |
||||||||||||
|
hwBatteryGroups
Number of battery group
|
Integer32r/w Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.3 |
||||||||||||
|
hwBatteryGroupVoltageLow
When the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.4 |
||||||||||||
|
hwBatteryGroupChargeLimit
Charge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed. Default: 15 Unit: percent |
percentMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.5 |
||||||||||||
|
hwBatteryGroupRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.1.1.6 |
||||||||||||
|
hwBatteryGroupOperStatus
The State of the battery supply which was connected with Power EMU.
To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is ab… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7 |
||||||||||||
|
hwBatteryGroupVoltageHigh
When the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.8 |
||||||||||||
|
hwBatteryGroupTwiceOffVoltage
The twice off protection voltage of the battery group. Its unit is mV.
Default: 44000 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.9 |
||||||||||||
|
hwBatteryGroupProtectVoltage
The first off protection voltage of the battery,
whose default is 43V. Default: 43000 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.10 |
||||||||||||
|
hwBatteryGroupTmpOffHigh
The high temperature off protection point of the battery group,
whose default is 50 degrees centigrade. Unit: 0.01 degree |
0.01 degreeMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.11 |
||||||||||||
|
hwBatteryInstallTime
The installing date of battery group.
|
SNMPv2-TCDisplayString Textual Convention: SNMPv2-TCDisplayString OctetStringType Constraints: range: 0..255 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.12 |
||||||||||||
|
hwBatteryGroupBomCode
The BOM code of battery.
Invalid: null string. |
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.13 |
||||||||||||
|
hwBatteryGroupType
The type of lead-acid battery.
1: general. 2: tcbc. 3: tcbb. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.1.1.14 |
||||||||||||
|
hwLiBatteryGroupChargeLimit
The charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host. user uses it which has been lessened 1000 by SNMP. Default: 1050. The invalid value -1 indicates that the device can not ge… |
Integer32r/w Constraints: range: 50-1050range: -1--1 |
.1.3.6.1.4.1.2011.6.2.1.6.1.1.15 |
hwChargeTable
table.1.3.6.1.4.1.2011.6.2.1.6.2
·
1 row entry
·
7 columns
Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Charge management table.
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Through this table, the charging parameter of the battery can be set and queried.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwChargeAdminStatus
Charge management mode.
Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicate… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1 |
||||||||||||||
|
hwChargeOperStatus
Charge operation status.
Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that t… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.2.1.2 |
||||||||||||||
|
hwAverageChargeVoltage
Voltage value of average charge, in unit of mV.
Default: 56500 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.2.1.3 |
||||||||||||||
|
hwFloatChargeVoltage
Voltage value of float charge .
Default: 53500 Unit: mV |
mVMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.2.1.4 |
||||||||||||||
|
hwChargeControlRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.2.1.5 |
||||||||||||||
|
hwAverageChargeTime
Timing average charge time interval, effective range is 190 days.
Default :value is 60 days Unit: day |
daySNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6 |
||||||||||||||
|
hwBatteryTmpRedeemingQuotiety
Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree ce… |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.2.1.7 |
hwBatteryTable
table.1.3.6.1.4.1.2011.6.2.1.6.3
·
1 row entry
·
22 columns
Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group.
Battery group state table.
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Through this table, the status parameter of a battery group can be set and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex.
hwEnvEmuIndex is the index …
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwBatteryIndex
Battery group loop index
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.1 |
||||||||||||
|
hwBatteryCapacity
The permitted max battery capacity of the battery group loop charge.
Unit: Ah Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
SNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.2 |
||||||||||||
|
hwBatteryLoopState
The battery group present status.
Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.3 |
||||||||||||
|
hwBatteryVoltage
The loop voltage of the battery group.
Unit: mV invalid: -1 |
mVMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.4 |
||||||||||||
|
hwBatteryOperStatus
The present state of the battery group loop.
Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop i… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.5 |
||||||||||||
|
hwBatteryCurrent
Present current .
Unit: mA invalid: -1 |
mAMeasuresRange Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.6 |
||||||||||||
|
hwBatteryTemperature
The loop temperature of the battery group.
Unit: degree Invaild:2147483647(0X7FFFFFFF) |
degreeSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.7 |
||||||||||||
|
hwBatteryRowStatus
RowStatus standard operation
|
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.8 |
||||||||||||
|
hwBatteryCurrentHigh
The over-current alarm point of the battery group.
Unit: mA |
mAMeasuresRanger/w Textual Convention: MeasuresRange Integer32 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.9 |
||||||||||||
|
hwBatteryFuseState
Battery fuse state.
Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10 |
||||||||||||
|
hwBatteryContactState
The state of the battery contactor.
Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.11 |
||||||||||||
|
hwBatteryRemainCapacity
Remain capacity of the battery,
invalid(-1) |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.12 |
||||||||||||
|
hwBatteryProtectState
Protection status of the battery.
Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overte… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.13 |
||||||||||||
|
hwBatteryVoltageState
Voltage state of Battery.
Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicat… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.14 |
||||||||||||
|
hwBatteryHardwareState
Hardware State of Battery.
Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.15 |
||||||||||||
|
hwBatteryLowTemperature
The lowest loop temperature of the battery group.
Unit: degree Invaild:2147483647(0X7FFFFFFF) |
degreeSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.16 |
||||||||||||
|
hwBatteryAntiTheftSwitch
Anti-theft switch of Battery.
Options: 1. disable(1) - indicates that the anti-theft state of Battery is disabled 2. enable(2) - indicates that the anti-theft state of Battery is enabled 3. invalid(-1) - ind… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.17 |
||||||||||||
|
hwBatteryAntiTheftTimeout
The anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation. |
hourInteger32r/w Constraints: range: 8-720range: -1--1 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.18 |
||||||||||||
|
hwBatterySequence
The sequence of LiBattery.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.19 |
||||||||||||
|
hwBatteryAddress
The address of LiBattery which corresponds to the subnode of LiBattery.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.20 |
||||||||||||
|
hwBatteryHeaterState
The state of battery heater.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.3.1.21 |
||||||||||||
|
hwBatteryHealthState
The health state of battery.
Unit:% invalid:-1 |
%Integer32 Constraints: range: -1-100 |
.1.3.6.1.4.1.2011.6.2.1.6.3.1.22 |
hwBatteryTestTable
table.1.3.6.1.4.1.2011.6.2.1.6.4
·
1 row entry
·
11 columns
Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Battery test table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwBatteryTestAdminStatus
Battery test admin status.
Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that th… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.4.1.1 |
||||||||||||||
|
hwBatteryTestAutoDischargePeriod
Auto discharge test period.
Effective range is 30 -240 days. Default: 120 Unit: day |
daySNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.2 |
||||||||||||||
|
hwBatteryTestResult
obsolete
Test result:
Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.4.1.3 |
||||||||||||||
|
hwBatteryTestStartTime
obsolete
Time of starting test
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.4 |
||||||||||||||
|
hwBatteryTestDuration
Battery discharge test duration.
Effective range is 1-100 hours. Default :value is 10 hours Unit: hour |
hourSNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5 |
||||||||||||||
|
hwBatteryTestTerminateVoltage
Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV |
mVSNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.6 |
||||||||||||||
|
hwBatteryTestTotalDischargeAH
obsolete
Total discharge AH.
Unit: mAH |
mAHSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.7 |
||||||||||||||
|
hwBatteryTestOperStatus
Battery discharge test operate status.
Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPer… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.4.1.8 |
||||||||||||||
|
hwBatteryTestPhase
Battery test phase.
Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the powe… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.4.1.9 |
||||||||||||||
|
hwBatteryTestStartHour
Discharge start time.
Effective range is 0 23 Default: 0 Unit: hour |
hourSNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.10 |
||||||||||||||
|
hwBatteryTestAlarmThreshold
The battery discharge test alarm threshold in ratio of the range:1~79.
|
percentSNMPv2-SMIInteger32r/w Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.4.1.11 |
hwBatteryLogTestTable
table.1.3.6.1.4.1.2011.6.2.1.6.5
·
1 row entry
·
10 columns
Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery.
Battery test result table,
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Through this table, the discharging test result of the battery group can be saved and queried.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex.
hwEnvEmuInd…
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwBatteryLogTestIndex
Battery discharge test result index
|
Integer32 Constraints: range: 0-255 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.1 |
||||||||||||||
|
hwBatteryLogTestStartTime
Battery discharge test start time
|
SNMPv2-TCDateAndTime Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.2 |
||||||||||||||
|
hwBatteryLogTestDischargeDuration
Duration of discharge.
Unit: minute |
minuteSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.3 |
||||||||||||||
|
hwBatteryLogTestTerminateVoltage
End voltage of battery discharge test .
Unit: mV |
mVSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.4 |
||||||||||||||
|
hwBatteryLogTestBatteryStatus
Battery status.
Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.5.1.5 |
||||||||||||||
|
hwBatteryLogTestTotalDischargeAH
Discharge cumulate AH.
Unit: mAH |
mAHSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.6 |
||||||||||||||
|
hwBatteryLogTestFinish
Battery Test result.
Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.6.5.1.7 |
||||||||||||||
|
hwBatteryLogTestEfficiency
The information of battery test efficiency.
|
percentSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.8 |
||||||||||||||
|
hwBatteryLogTestBatteryTemperature
Battery discharge test end Temperature.
Unit: 0.01 Degree Invaild: 0X7FFFFFFF |
0.01 DegreeSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.9 |
||||||||||||||
|
hwBatteryLogTestBatteryCurrent
Battery discharge test average Current.
Unit: mA |
mASNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.5.1.10 |
hwBatteryCellTable
table.1.3.6.1.4.1.2011.6.2.1.6.6
·
1 row entry
·
3 columns
The state of battery cell. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryCellIndex is the index of the battery cell.
The state of battery cell.
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryCellIndex.
hwEnvEmuIndex is the index of the monitored unit.
hwPowerIndex is the index of the power supply monitored by…
Indexes
| Column | Syntax | OID |
|---|---|---|
|
hwBatteryCellIndex
The index of battery cell.
|
Integer32 Constraints: range: 0-15 |
.1.3.6.1.4.1.2011.6.2.1.6.6.1.1 |
|
hwBatteryCellTemperature
The temperature of battery cell.
Unit: C Non-value: 0x7FFFFFFF |
CSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.6.1.2 |
|
hwBatteryCellVoltage
The voltage of battery cell.
Unit: mV Non-value: -1 |
mVSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.6.6.1.3 |
.1.3.6.1.4.1.2011.6.2.1.7
·
1 row entry
·
10 columns
Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Remote provide power basic information table.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
hwEnvEmuIndex is the index of the monitored unit,
and hwPowerIndex is the index of the power supply monitored…
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwPowerCentralState
State of the central module.
Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.1 |
||||||||||||||||
|
hwPowerCentralDCInPutState
State of central module DC input:
Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.2 |
||||||||||||||||
|
hwPowerCentralDCOutputState
State of central module DC output.
Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.3 |
||||||||||||||||
|
hwPowerCentralDCOutputMode
Mode of central module DC output.
Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.4 |
||||||||||||||||
|
hwPowerRemoteCommState
Remote power module communications state.
Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.5 |
||||||||||||||||
|
hwPowerRemoteDCInputState
State of remote module DC input.
Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.6 |
||||||||||||||||
|
hwPowerRemoteLineCurState
state of line between central and remote module.
Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.7 |
||||||||||||||||
|
hwPowerRemotePowerState
state of remote UA60 power.
Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.8 |
||||||||||||||||
|
hwPowerRemoteLineState
State of line U1.
Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 … |
Bitsr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.9 |
||||||||||||||||
|
hwPowerCentralLoadState
state of central load.
Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.7.1.10 |
hwACInfomationTable
table.1.3.6.1.4.1.2011.6.2.1.8
·
1 row entry
·
6 columns
AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
AC infomation table. The table is not supported.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwPowerIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
hwACInfoCommState
communication state of AC input module.
The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.8.1.1 |
||||||||||||
|
hwACInfoThunderState
Thunder's state.
The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.8.1.2 |
||||||||||||
|
hwACInfoCurrentLoop
Current AC input working loop.
The leaf is not supported. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.8.1.3 |
||||||||||||
|
hwACInfoMCBTrigger
AC input MCB trigger state.
The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. breakDown(1)- indicates the AC input MCB trigger state is break-down |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.1.8.1.4 |
||||||||||||
|
hwACInfoFrequency
The infomation of AC input frequency.
This leaf is not supported. Unit: HZ |
HZSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.1.8.1.5 |
||||||||||||
|
hwACInfoRowStatus
RowStatus standard operation
The leaf is not supported. |
SNMPv2-TCRowStatusr/w Textual Convention: SNMPv2-TCRowStatus EnumerationType Values:
|
.1.3.6.1.4.1.2011.6.2.1.8.1.6 |
hwRemoteUnitSysInfoTable
table.1.3.6.1.4.1.2011.6.2.5.1
·
1 row entry
·
4 columns
Remote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex.
Remote power system, remote unit basic information table. The indexes of
this entry is hwEnvEmuIndex.
this entry is hwEnvEmuIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
hwRemoteUnitPowerSystype
Type of the remote unit power system.
Options: 1.rftv(1) - Type of the remote unit power system is RFT-V 2.rftc(2) - Type of the remote unit power system is RFT-C … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.5.1.1.1 |
||||||
|
hwRemoteUnitDCOutputVol
The remote unit DC output voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mVSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.1.1.2 |
||||||
|
hwRemoteUnitDCOutputCur
The remote unit DC output current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mASNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.1.1.3 |
||||||
|
hwRemoteUnitSlotNum
The remote unit slot number.
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.1.1.4 |
hwRemoteUnitSlotTable
table.1.3.6.1.4.1.2011.6.2.5.2
·
1 row entry
·
8 columns
Remote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Remote power system, remote unit slot information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
Indexes
HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwRemoteUnitSlotIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
hwRemoteUnitSlotIndex
The remote unit slot index.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.2.1.1 |
||||||||
|
hwRemoteUnitSlotCircuitNum
The remote unit slot circuit number.
Invalid:-1. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.2.1.2 |
||||||||
|
hwRemoteUnitSlotHardVersion
The remote unit slot hard version.
Invalid: null string. |
OctetString Constraints: range: 1-128 |
.1.3.6.1.4.1.2011.6.2.5.2.1.3 |
||||||||
|
hwRemoteUnitSlotSoftVersion
The remote unit slot soft version.
Invalid: null string. |
OctetString Constraints: range: 1-128 |
.1.3.6.1.4.1.2011.6.2.5.2.1.4 |
||||||||
|
hwRemoteUnitSlotStatus
The state of the remote unit slot.
Options: 1.normal(1) - The state of the remote unit slot is normal 2.fault(2) - The state of the remote unit slot is fault 3.null(3) - The sta… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.5.2.1.5 |
||||||||
|
hwRemoteUnitSlotAdminStatus
Delete the remote unit slot.
Options: 1.delete(1) - Delete the remote unit slot 2.invalid(255) - Unknown |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.5.2.1.6 |
||||||||
|
hwRemoteUnitSlotDCOutputVol
The remote unit slot DC output voltage.
Invalid:-1. |
mVSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.2.1.7 |
||||||||
|
hwRemoteUnitSlotDCOutputCur
The remote unit slot DC output current.
Invalid:-1. |
mASNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.2.1.8 |
hwRemoteUnitCircuitTable
table.1.3.6.1.4.1.2011.6.2.5.3
·
1 row entry
·
4 columns
Remote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Remote power system, remote unit circuit information table. The indexes of
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
hwRemoteUnitCircuitIndex
The remote unit circuit index.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.3.1.1 |
||||||||
|
hwRemoteUnitCircuitInputVol
The remote unit circuit input voltage.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mVSNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.3.1.2 |
||||||||
|
hwRemoteUnitCircuitInputCur
The remote unit circuit input current.
Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
mASNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.2011.6.2.5.3.1.3 |
||||||||
|
hwRemoteUnitCircuitState
The state of the remote unit circuit.
Options: 1.normal(1) - The state of the remote unit circuit is normal 2.fault(2) - The state of the remote unit circuit is fault 3.null(3) -… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.2011.6.2.5.3.1.4 |