hwDCCurrentOutState
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.3.1.8
Object
column
deprecated
Enumeration
DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.3.1.8- Type
- column
- Access
- readonly
- Status
- deprecated
- Parent
- hwDCOutEntry
- Table
- hwDCOutTable
- Siblings
- 12
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | invalid |
1 | normal |
2 | exceedVoltage |
3 | belowVoltage |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwDCVoltageOut DC voltage output.
Unit: mV.
invalid: -1 | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.1 |
| hwDCOutLoadCurrent Total load current of DC output .
Unit: mA.
invalid: -1 | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.10 |
| hwDCOutLoadTmpHigh The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree | column | 0.01 degree MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.11 |
| hwDCOutRunState DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.ba… | column | Bits | .1.3.6.1.4.1.2011.6.2.1.3.1.12 |
| hwDCCommunicationState DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.13 |
| hwDCCurrentOut DC current output.
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.2 |
| hwDCVoltageOutHigh Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.3 |
| hwDCVoltageOutLow Output DC below-voltage alarm point . Default value is 45V.
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.4 |
| hwDCVoltageOutState deprecated DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage stat… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.5 |
| hwDCCurrentOutHigh Output DC exceed-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.6 |
| hwDCCurrentOutLow Output below-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.7 |
| hwDCOutRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.3.1.9 |