hwACPowerState
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.2.1.2
Object
column
Enumeration
Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is overvoltage 4.belowVoltage(4) - indicates that the power supply is undervoltage 5.backup(5) - indicates that the power supply is not supported currently 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.2.1.2- Type
- column
- Access
- readonly
- Status
- current
- Parent
- hwACInputEntry
- Table
- hwACInputTable
- Siblings
- 13
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | invalid |
1 | normal |
2 | offline |
3 | exceedVoltage |
4 | belowVoltage |
5 | backup |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwACLoopIndex Input loop index. There are two channels of AC current input,
which are the backup for each other. | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.2.1.1 |
| hwACVoltageLow AC input under-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU s… | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.10 |
| hwACRowStatus Only the add operation, delete operation, and status query operation are supported. | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.2.1.11 |
| hwACVoltageAState Phase AB/A of AC input state.
Options:
1. normal(0) - indicates that the Phase AB/A of AC input state is normal
2. belowVoltage(1) - indicates that the Phase AB/A … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.2.1.12 |
| hwACVoltageBState Phase BC/B of AC input state.
Options:
1. normal(0) - indicates that the Phase BC/B of AC input state is normal
2. belowVoltage(1) - indicates that the Phase BC/B… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.2.1.13 |
| hwACVoltageCState Phase CA/C of AC input state.
Options:
1. normal(0) - indicates that the Phase CA/C of AC input state is normal
2. belowVoltage(1) - indicates that the Phase CA/C … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.2.1.14 |
| hwACVoltA AC Inuput voltage A.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.3 |
| hwACCurrentA AC input Current A.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.4 |
| hwACVoltB AC input voltage B.
Unit: mv
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.5 |
| hwACCurrentB AC input current B.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.6 |
| hwACVoltC AC input voltage C.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.7 |
| hwACCurrentC AC input current C.
Unit: mA
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.8 |
| hwACVoltageHigh AC input over-voltage alarm threshold.
Unit: mV
invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU st… | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.2.1.9 |