hwBatteryTestEntry
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.4.1
Object
row
Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.4.1- Type
- row
- Status
- current
- Parent
- hwBatteryTestTable
- Table
- hwBatteryTestTable
- Children
- 11
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwBatteryTestAdminStatus Battery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.1 |
| hwBatteryTestStartHour Discharge start time.
Effective range is 0 23
Default: 0
Unit: hour | column | hour SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.10 |
| hwBatteryTestAlarmThreshold The battery discharge test alarm threshold in ratio of the range:1~79. | column | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.11 |
| hwBatteryTestAutoDischargePeriod Auto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day | column | day SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.2 |
| hwBatteryTestResult obsolete Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed norma… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.3 |
| hwBatteryTestStartTime obsolete Time of starting test | column | SNMPv2-TCDateAndTime | .1.3.6.1.4.1.2011.6.2.1.6.4.1.4 |
| hwBatteryTestDuration Battery discharge test duration.
Effective range is 1-100 hours.
Default :value is 10 hours
Unit: hour | column | hour SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.5 |
| hwBatteryTestTerminateVoltage Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV | column | mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.6 |
| hwBatteryTestTotalDischargeAH obsolete Total discharge AH.
Unit: mAH | column | mAH SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.7 |
| hwBatteryTestOperStatus Battery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto disch… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.8 |
| hwBatteryTestPhase Battery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge
3. re… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwEnvEmuIndex is the index of the Environment monitoring unit,
used as the index of hwEnvironmentInfoTable.
Range: 0 - 2048 | column | Integer32 | .1.3.6.1.4.1.2011.6.1.1.1.1.1 |
| hwPowerIndex Index of the power supply monitored by the monitoring unit | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.1.1.1 |