hwDCOutEntry
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.3.1
Object
row
DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit.
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.3.1- Type
- row
- Status
- current
- Parent
- hwDCOutTable
- Table
- hwDCOutTable
- Children
- 13
Syntax
No syntax metadata recorded.
Values & Constraints
No enumerated values or constraints recorded.
Related Objects
Child Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwDCVoltageOut DC voltage output.
Unit: mV.
invalid: -1 | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.1 |
| hwDCOutLoadCurrent Total load current of DC output .
Unit: mA.
invalid: -1 | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.10 |
| hwDCOutLoadTmpHigh The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree | column | 0.01 degree MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.11 |
| hwDCOutRunState DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.ba… | column | Bits | .1.3.6.1.4.1.2011.6.2.1.3.1.12 |
| hwDCCommunicationState DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.13 |
| hwDCCurrentOut DC current output.
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.2 |
| hwDCVoltageOutHigh Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.3 |
| hwDCVoltageOutLow Output DC below-voltage alarm point . Default value is 45V.
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.4 |
| hwDCVoltageOutState deprecated DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage stat… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.5 |
| hwDCCurrentOutHigh Output DC exceed-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.6 |
| hwDCCurrentOutLow Output below-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.7 |
| hwDCCurrentOutState deprecated DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.8 |
| hwDCOutRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.3.1.9 |
Indexes
| Object | Type | Syntax | OID |
|---|---|---|---|
| HUAWEI-ENVIRONMENT-MIBhwEnvEmuIndex hwEnvEmuIndex is the index of the Environment monitoring unit,
used as the index of hwEnvironmentInfoTable.
Range: 0 - 2048 | column | Integer32 | .1.3.6.1.4.1.2011.6.1.1.1.1.1 |
| hwPowerIndex Index of the power supply monitored by the monitoring unit | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.1.1.1 |