hwAverageChargeTime
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6
Object
Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.2.1.6- Type
- column
- Access
- readwrite
- Status
- current
- Units
- day
- Parent
- hwChargeEntry
- Table
- hwChargeTable
- Siblings
- 6
Syntax
day SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwChargeAdminStatus Charge management mode.
Options:
1. average(1) - indicates that the charge management mode is average charge
2. float(2) - indicates that the charge management mode is f… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.2.1.1 |
| hwChargeOperStatus Charge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.2.1.2 |
| hwAverageChargeVoltage Voltage value of average charge, in unit of mV.
Default: 56500
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.2.1.3 |
| hwFloatChargeVoltage Voltage value of float charge .
Default: 53500
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.2.1.4 |
| hwChargeControlRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.6.2.1.5 |
| hwBatteryTmpRedeemingQuotiety Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.2.1.7 |