hwBatteryFuseState
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10
Object
column
Enumeration
Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.3.1.10- Type
- column
- Access
- readonly
- Status
- current
- Parent
- hwBatteryEntry
- Table
- hwBatteryTable
- Siblings
- 21
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | invalid |
1 | on |
2 | off |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwBatteryIndex Battery group loop index | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.1 |
| hwBatteryContactState The state of the battery contactor.
Options:
1. on(1) - indicates that the contactor is connected
2. off(2) - indicates that the contactor is disconnected
3. invalid(… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.11 |
| hwBatteryRemainCapacity Remain capacity of the battery,
invalid(-1) | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.12 |
| hwBatteryProtectState Protection status of the battery.
Options:
1. normal(1) - indicates that the Protection status of the battery is normal
2. overtemperature(2) - indicates that the Pr… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.13 |
| hwBatteryVoltageState Voltage state of Battery.
Options:
1. normal(1) - indicates that Voltage state of Battery is normal
2. exceedVoltage(2) - indicates that Voltage state of Battery is exce… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.14 |
| hwBatteryHardwareState Hardware State of Battery.
Options:
1. normal(1) - indicates that the hardware state of Battery is normal
2. fault(2) - indicates that the hardware state of Battery is fault | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.15 |
| hwBatteryLowTemperature The lowest loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF) | column | degree SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.16 |
| hwBatteryAntiTheftSwitch Anti-theft switch of Battery.
Options:
1. disable(1) - indicates that the anti-theft state of Battery is disabled
2. enable(2) - indicates that the anti-theft state of Batt… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.17 |
| hwBatteryAntiTheftTimeout The anti-theft timeout time of battery.
The invalid value -1 indicates that the device can not get the value, e.g. the EMU does not support this operation. | column | hour Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.18 |
| hwBatterySequence The sequence of LiBattery. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.19 |
| hwBatteryCapacity The permitted max battery capacity of the battery group loop charge.
Unit: Ah
Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.2 |
| hwBatteryAddress The address of LiBattery which corresponds to the subnode of LiBattery. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.20 |
| hwBatteryHeaterState The state of battery heater. | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.21 |
| hwBatteryHealthState The health state of battery.
Unit:%
invalid:-1 | column | % Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.22 |
| hwBatteryLoopState The battery group present status.
Options:
1. on(1) - indicates that the present state of battery group is on
2. off(2) - indicates that the present state of battery … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.3 |
| hwBatteryVoltage The loop voltage of the battery group.
Unit: mV
invalid: -1 | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.3.1.4 |
| hwBatteryOperStatus The present state of the battery group loop.
Options:
1. charge(1) - indicates that the present state of the battery group loop is charge
2. discharge(2) - indicates that the p… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.3.1.5 |
| hwBatteryCurrent Present current .
Unit: mA
invalid: -1 | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.3.1.6 |
| hwBatteryTemperature The loop temperature of the battery group.
Unit: degree
Invaild:2147483647(0X7FFFFFFF) | column | degree SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.3.1.7 |
| hwBatteryRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.6.3.1.8 |
| hwBatteryCurrentHigh The over-current alarm point of the battery group.
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.3.1.9 |