hwChargeAdminStatus
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1
Object
column
r/w
Enumeration
Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicates that the charge management mode is auto-control charge 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.2.1.1- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- hwChargeEntry
- Table
- hwChargeTable
- Siblings
- 6
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | invalid |
1 | average |
2 | float |
3 | auto |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwChargeOperStatus Charge operation status.
Options:
1. average(1) - indicates that the charge operation state is average charge
2. float(2) - indicates that the charge operation state is float … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.2.1.2 |
| hwAverageChargeVoltage Voltage value of average charge, in unit of mV.
Default: 56500
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.2.1.3 |
| hwFloatChargeVoltage Voltage value of float charge .
Default: 53500
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.2.1.4 |
| hwChargeControlRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.6.2.1.5 |
| hwAverageChargeTime Timing average charge time interval, effective range is 190 days.
Default :value is 60 days
Unit: day | column | day SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.2.1.6 |
| hwBatteryTmpRedeemingQuotiety Temperature redeeming quotient, used to set the co-relation
between the float charge voltage and the battery temperature.
It means How much will the float charge voltage decrease… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.2.1.7 |