hwDCOutRowStatus
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.3.1.9
Object
RowStatus standard operation
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.3.1.9- Type
- column
- Access
- readwrite
- Status
- current
- Parent
- hwDCOutEntry
- Table
- hwDCOutTable
- Siblings
- 12
Values & Constraints
Type Values
1 | active |
2 | notInService |
3 | notReady |
4 | createAndGo |
5 | createAndWait |
6 | destroy |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwDCVoltageOut DC voltage output.
Unit: mV.
invalid: -1 | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.1 |
| hwDCOutLoadCurrent Total load current of DC output .
Unit: mA.
invalid: -1 | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.10 |
| hwDCOutLoadTmpHigh The off protection point under the load temperature, by default,
it is 65 degrees centigrade.
Unit: 0.01 degree | column | 0.01 degree MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.11 |
| hwDCOutRunState DC output running status.
Options:
1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current
2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current
3.ba… | column | Bits | .1.3.6.1.4.1.2011.6.2.1.3.1.12 |
| hwDCCommunicationState DC communication status.
Options:
1.normal(0) - indicates that the DC communication state is normal
2.fault(1) - indicates that the DC communication state is fault | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.13 |
| hwDCCurrentOut DC current output.
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.2 |
| hwDCVoltageOutHigh Output DC exceed-voltage alarm point.
Default: 58000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.3 |
| hwDCVoltageOutLow Output DC below-voltage alarm point . Default value is 45V.
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.4 |
| hwDCVoltageOutState deprecated DC output voltage status.
Options:
1. normal(1) - indicates that the DC output voltage state is normal
2. exceedVoltage(2) - indicates that the DC output voltage stat… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.5 |
| hwDCCurrentOutHigh Output DC exceed-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.6 |
| hwDCCurrentOutLow Output below-current alarm point .
Unit: mA | column | mA MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.3.1.7 |
| hwDCCurrentOutState deprecated DC output current status.
Options:
1.normal(1) - indicates that the DC output current state is normal
2.exceedVoltage(2) - indicates that the DC output current state is… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.3.1.8 |