hwBatteryGroupOperStatus
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7
Object
column
Enumeration
The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is abnormal, the battery group usually supplies power in an emergency. Options: 1.on(1) - indicates that the state of the battery power supply is on 2.off(2) - indicates that the state of the battery power supply is off 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.1.1.7- Type
- column
- Access
- readonly
- Status
- current
- Parent
- hwBatteryGroupEntry
- Table
- hwBatteryGroupTable
- Siblings
- 14
Syntax
Enumeration
Values & Constraints
Enumerated Values
-1 | invalid |
1 | on |
2 | off |
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwBatteryGroupCapacity Total capacity of the present battery group.
Unit: Ah | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.1 |
| hwBatteryGroupProtectVoltage The first off protection voltage of the battery,
whose default is 43V.
Default: 43000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.10 |
| hwBatteryGroupTmpOffHigh The high temperature off protection point of the battery group,
whose default is 50 degrees centigrade.
Unit: 0.01 degree | column | 0.01 degree MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.11 |
| hwBatteryInstallTime The installing date of battery group. | column | SNMPv2-TCDisplayString | .1.3.6.1.4.1.2011.6.2.1.6.1.1.12 |
| hwBatteryGroupBomCode The BOM code of battery.
Invalid: null string. | column | OctetString | .1.3.6.1.4.1.2011.6.2.1.6.1.1.13 |
| hwBatteryGroupType The type of lead-acid battery.
1: general.
2: tcbc.
3: tcbb. | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.1.1.14 |
| hwLiBatteryGroupChargeLimit The charge limit quotiety of the LiBattery.
SNMP uses it which has been enlarged 1000 by host.
user uses it which has been lessened 1000 by SNMP.
Default: 1050.
The invalid value… | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.15 |
| hwBatteryGroupCapcaityRemain Total remain capacity of the present battery group .
invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is… | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.2 |
| hwBatteryGroups Number of battery group | column | Integer32 | .1.3.6.1.4.1.2011.6.2.1.6.1.1.3 |
| hwBatteryGroupVoltageLow When the voltage of the battery group is lower than the value set,
the battery group will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.4 |
| hwBatteryGroupChargeLimit Charge limit point quotient, the product of which and the max capacity
of the battery group is the max charge current allowed.
Default: 15
Unit: percent | column | percent MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.5 |
| hwBatteryGroupRowStatus RowStatus standard operation | column | SNMPv2-TCRowStatus | .1.3.6.1.4.1.2011.6.2.1.6.1.1.6 |
| hwBatteryGroupVoltageHigh When the voltage of the battery group is higher than the value set, the battery group
will no longer supply power. Its unit is mV.
Default: 43000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.8 |
| hwBatteryGroupTwiceOffVoltage The twice off protection voltage of the battery group. Its unit is mV.
Default: 44000
Unit: mV | column | mV MeasuresRange | .1.3.6.1.4.1.2011.6.2.1.6.1.1.9 |