hwBatteryTestDuration
HUAWEI-POWER-MIB ·
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5
Object
Battery discharge test duration. Effective range is 1-100 hours. Default :value is 10 hours Unit: hour
Context
- MIB
- HUAWEI-POWER-MIB
- OID
.1.3.6.1.4.1.2011.6.2.1.6.4.1.5- Type
- column
- Access
- readwrite
- Status
- current
- Units
- hour
- Parent
- hwBatteryTestEntry
- Table
- hwBatteryTestTable
- Siblings
- 10
Syntax
hour SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| hwBatteryTestAdminStatus Battery test admin status.
Options:
1. start(1) - indicates that the Battery starts testing
2. terminate(2) - indicates that the Battery terminates testing
3. … | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.1 |
| hwBatteryTestStartHour Discharge start time.
Effective range is 0 23
Default: 0
Unit: hour | column | hour SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.10 |
| hwBatteryTestAlarmThreshold The battery discharge test alarm threshold in ratio of the range:1~79. | column | percent SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.11 |
| hwBatteryTestAutoDischargePeriod Auto discharge test period.
Effective range is 30 -240 days.
Default: 120
Unit: day | column | day SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.2 |
| hwBatteryTestResult obsolete Test result:
Options:
1. testing(1) - indicates that the Battery test is in operation
2. complete(2) - indicates that the Battery test is completed norma… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.3 |
| hwBatteryTestStartTime obsolete Time of starting test | column | SNMPv2-TCDateAndTime | .1.3.6.1.4.1.2011.6.2.1.6.4.1.4 |
| hwBatteryTestTerminateVoltage Battery discharge test end voltage.
Effective range (DC lack alarm voltage+0.5V-voltage of floating charge).
Default: 45600
Unit: mV | column | mV SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.6 |
| hwBatteryTestTotalDischargeAH obsolete Total discharge AH.
Unit: mAH | column | mAH SNMPv2-SMIInteger32 | .1.3.6.1.4.1.2011.6.2.1.6.4.1.7 |
| hwBatteryTestOperStatus Battery discharge test operate status.
Options:
1. autoTestPermit(1) - indicates that auto discharge test is enabled
2. autoTestForbid(2) - indicates that auto disch… | column | Enumeration | .1.3.6.1.4.1.2011.6.2.1.6.4.1.8 |
| hwBatteryTestPhase Battery test phase.
Options:
1. charge(1) - indicates the batter test phase is charge
2. discharge(2) - indicates the batter test phase is discharge