unitTable
table.1.3.6.1.4.1.534.6.6.7.1.2
·
1 row entry
·
22 columns
A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object.
An entry for a PDU.
Indexes
strappingIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
strappingIndex
For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will always be '0'. |
Integer32 Constraints: range: 0-23 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.1 |
||||||||||||||
|
productName
Name of the product.
|
OctetString Constraints: range: 1-127 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.2 |
||||||||||||||
|
partNumber
Part number of the unit.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.3 |
||||||||||||||
|
serialNumber
Serial number of the unit.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.4 |
||||||||||||||
|
firmwareVersion
Firmware version.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.5 |
||||||||||||||
|
unitName
Descriptive name for the unit.
|
OctetStringr/w Constraints: range: 1-63 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.6 |
||||||||||||||
|
lcdControl
Control the local LCD.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.7 |
||||||||||||||
|
clockValue
Clock value. This could be from either a real-time clock (in which case
it is likely writeable) or from a time server via NTP (probably read-only). |
SNMPv2-TCDateAndTimer/w Textual Convention: SNMPv2-TCDateAndTime OctetStringType Constraints: range: 8range: 11 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.8 |
||||||||||||||
|
temperatureScale
Scale used to return temperature objects.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.9 |
||||||||||||||
|
unitType
Technical capabilities of the PDU. Functionality is as follows:
Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.10 |
||||||||||||||
|
systemType
Architecture of the ePDU electronic.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.11 |
||||||||||||||
|
inputCount
Number of inputs on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.20 |
||||||||||||||
|
groupCount
Number of groups on this ePDU. Groups include breakers, outlet sections,
and user-defined groups. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.21 |
||||||||||||||
|
outletCount
Number of outlets on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.22 |
||||||||||||||
|
temperatureCount
Max number of temperature measurements on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.23 |
||||||||||||||
|
humidityCount
Max number of humidity measurements on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.24 |
||||||||||||||
|
contactCount
Max number of contact sensors on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.25 |
||||||||||||||
|
communicationStatus
Status of the internal communication with the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.30 |
||||||||||||||
|
internalStatus
Status of the internal failure inside the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.31 |
||||||||||||||
|
strappingStatus
Status of the external communication with a strapping unit.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.32 |
||||||||||||||
|
userName
Username used to log into the PDU.
|
OctetString Constraints: range: 0-31 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.40 |
||||||||||||||
|
commInterface
Communications interface used to log into the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.41 |
unitControlTable
table.1.3.6.1.4.1.534.6.6.7.1.3
·
1 row entry
·
2 columns
A list of units that have controllable outlets.
An entry for a PDU which has controllable outlets.
Indexes
strappingIndex
| Column | Syntax | OID |
|---|---|---|
|
unitControlOffCmd
Unit-level outlet control command.
Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.1.3.1.2 |
|
unitControlOnCmd
Unit-level outlet control command.
Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds until the outlet Sequence On command is issue… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.1.3.1.3 |
inputTable
table.1.3.6.1.4.1.534.6.6.7.3.1
·
1 row entry
·
10 columns
List of inputs to the PDU.
An entry for a particular input.
Indexes
strappingIndex inputIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inputIndex
A unique value for each input. Its value ranges from 1 to inputCount.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputType
Type of input - single phase, split phase, three phase delta, or three
phase wye. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputFrequency
Units are 0.1 Hz; divide by ten to get Hz.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputFrequencyStatus
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputVoltageCount
Number of input voltage measurements on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputCurrentCount
Number of input current measurements on this ePDU.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputPowerCount
Number of rows in the inputPowerTable.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputPlugType
Identifies which plug is on the input.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputFeedColor
Color code of the input feed.
|
Unsigned32r/w Constraints: range: 0-16777215 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
inputFeedName
A descriptive name for the input.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.10 |
inputVoltageTable
table.1.3.6.1.4.1.534.6.6.7.3.2
·
1 row entry
·
8 columns
A list of input voltage measurements. The number of entries is given by inputVoltageCount.
An entry for a particular input voltage measurement.
Indexes
strappingIndex inputIndex inputVoltageIndex
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inputVoltageIndex
A unique value for each input voltage measurement. Its value ranges
from 1 to inputVoltageCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.1 |
||||||||||||||
|
inputVoltageMeasType
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.2.1.2 |
||||||||||||||
|
inputVoltage
An input voltage measurement value. Units are millivolts.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.3 |
||||||||||||||
|
inputVoltageThStatus
Status of the measured input voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.2.1.4 |
||||||||||||||
|
inputVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.5 |
||||||||||||||
|
inputVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.6 |
||||||||||||||
|
inputVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.7 |
||||||||||||||
|
inputVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.8 |
inputCurrentTable
table.1.3.6.1.4.1.534.6.6.7.3.3
·
1 row entry
·
12 columns
A list of input current measurements. The number of entries is given by inputCurrentCount.
An entry for a particular input current measurement.
Indexes
strappingIndex inputIndex inputCurrentIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inputCurrentIndex
A unique value for each input current measurement. Its value ranges
from 1 to inputCurrentCount. |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.1 |
||||||||||
|
inputCurrentMeasType
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.3.1.2 |
||||||||||
|
inputCurrentCapacity
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.3 |
||||||||||
|
inputCurrent
An input current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.4 |
||||||||||
|
inputCurrentThStatus
Status of the measured input current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.3.1.5 |
||||||||||
|
inputCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.6 |
||||||||||
|
inputCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.7 |
||||||||||
|
inputCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.8 |
||||||||||
|
inputCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.9 |
||||||||||
|
inputCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.10 |
||||||||||
|
inputCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.11 |
||||||||||
|
inputPhaseDesignator
Alphanumeric physical name for the input.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.12 |
inputPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.4
·
1 row entry
·
8 columns
A list of input power measurements. The number of entries is given by inputPowerCount.
An entry for an input power measurement.
Indexes
strappingIndex inputIndex inputPowerIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
inputPowerIndex
A unique value for each input power measurement. Its value ranges
from 1 to inputPowerCount. |
Integer32 Constraints: range: 1-12 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.1 |
||||||||||
|
inputPowerMeasType
Value indicates what is being measured in this table row.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.4.1.2 |
||||||||||
|
inputVA
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.3 |
||||||||||
|
inputWatts
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.4 |
||||||||||
|
inputWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.5 |
||||||||||
|
inputWhTimer
Timestamp of when input Watt-hours (inputWh) was last reset.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.6 |
||||||||||
|
inputPowerFactor
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.7 |
||||||||||
|
inputVAR
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.8 |
inputTotalPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.5
·
1 row entry
·
7 columns
A list of total input power measurements.
An entry for a total input power measurement.
Indexes
strappingIndex inputIndex
| Column | Syntax | OID |
|---|---|---|
|
inputTotalVA
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.3 |
|
inputTotalWatts
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.4 |
|
inputTotalWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.5 |
|
inputTotalWhTimer
Timestamp of when input Watt-hours (inputWh) was last reset.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.6 |
|
inputTotalPowerFactor
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.7 |
|
inputTotalVAR
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.8 |
|
inputPowerCapacity
Typical power capacity of the input. A negative value indicates that
the hardware current capacity is unknown. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.9 |
groupTable
table.1.3.6.1.4.1.534.6.6.7.5.1
·
1 row entry
·
9 columns
A list of groups. The number of entries is given by groupCount.
An entry for a particular group.
Indexes
strappingIndex groupIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
groupIndex
A unique value for each group. Its value ranges from 1 to groupCount.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.1 |
||||||||||||
|
groupID
Alphanumeric designator for the group. This value may be written
on the face of the unit. |
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.2 |
||||||||||||
|
groupName
A descriptive name for the group.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.3 |
||||||||||||
|
groupType
The type of the group.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.1.1.4 |
||||||||||||
|
groupBreakerStatus
Only applicable to breaker-groups. Indicates whether a breaker is turned
off or on. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.1.1.5 |
||||||||||||
|
groupChildCount
Number of children for this group.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.6 |
||||||||||||
|
groupColor
Background color code of the group. Color codes are decimal values.
|
Unsigned32 Constraints: range: 0-16777215 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.7 |
||||||||||||
|
groupDesignator
Alphanumeric physical name for the group. This value may be written
on the face of the unit. |
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.8 |
||||||||||||
|
groupInputIndex
Identifies the input on which the group is connected.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.9 |
groupChildTable
table.1.3.6.1.4.1.534.6.6.7.5.2
·
1 row entry
·
3 columns
A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group.
An entry for a particular child.
Indexes
strappingIndex groupIndex groupChildIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
groupChildIndex
A unique value for each child. Its value ranges from 1 to groupChildCount.
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.534.6.6.7.5.2.1.1 |
||||||||
|
groupChildType
The type of the child.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.2.1.2 |
||||||||
|
groupChildOID
Object ID of a child object.
|
ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.5.2.1.3 |
groupVoltageTable
table.1.3.6.1.4.1.534.6.6.7.5.3
·
1 row entry
·
7 columns
A list of group voltage measurements. There can be only one voltage measurement for each group.
An entry for a group voltage measurement.
Indexes
strappingIndex groupIndex
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
groupVoltageMeasType
Value indicates what voltage is being measured in this table row.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.3.1.2 |
||||||||||||||||
|
groupVoltage
Units are millivolts.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.3 |
||||||||||||||||
|
groupVoltageThStatus
Status of the measured group voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.3.1.4 |
||||||||||||||||
|
groupVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.5 |
||||||||||||||||
|
groupVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.6 |
||||||||||||||||
|
groupVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.7 |
||||||||||||||||
|
groupVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.8 |
groupCurrentTable
table.1.3.6.1.4.1.534.6.6.7.5.4
·
1 row entry
·
9 columns
A list of group current measurements. There can be only one current measurement for each group.
An entry for a group current measurement.
Indexes
strappingIndex groupIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
groupCurrentCapacity
Rated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.2 |
||||||||||
|
groupCurrent
A group current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.3 |
||||||||||
|
groupCurrentThStatus
Status of the measured group current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.4.1.4 |
||||||||||
|
groupCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.5 |
||||||||||
|
groupCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.6 |
||||||||||
|
groupCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.7 |
||||||||||
|
groupCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.8 |
||||||||||
|
groupCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.9 |
||||||||||
|
groupCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.10 |
groupPowerTable
table.1.3.6.1.4.1.534.6.6.7.5.5
·
1 row entry
·
6 columns
A list of group power measurements. There can be only one power measurement for each group.
An entry for a group power measurement.
Indexes
strappingIndex groupIndex
| Column | Syntax | OID |
|---|---|---|
|
groupVA
A group VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.2 |
|
groupWatts
A group Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.3 |
|
groupWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.4 |
|
groupWhTimer
Timestamp of when group Watt-hours (groupWh) was last reset.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.5 |
|
groupPowerFactor
A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.6 |
|
groupVAR
A group VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.7 |
groupControlTable
table.1.3.6.1.4.1.534.6.6.7.5.6
·
1 row entry
·
4 columns
A list of controllable groups.
An entry for a controllable group.
Indexes
strappingIndex groupIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
groupControlStatus
Current state of a controlled group. A value of 'mixed' means that
that the outlets within the group have differing states. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.6.1.2 |
||||||||
|
groupControlOffCmd
Group-level outlet control command.
Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-leve… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.3 |
||||||||
|
groupControlOnCmd
Group-level outlet control command.
Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.4 |
||||||||
|
groupControlRebootCmd
Group-level outlet control command.
For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and… |
Integer32r/w Constraints: range: -1-0 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.5 |
outletTable
table.1.3.6.1.4.1.534.6.6.7.6.1
·
1 row entry
·
7 columns
A list of outlets. The number of entries is given by outletCount.
An entry for a particular outlet.
Indexes
strappingIndex outletIndex
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletIndex
A unique value for each outlet. its value ranges from 1 to outletCount.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.1 |
||||||||||||||||||||||||||||||||||||||||
|
outletID
Alphanumeric designator for the outlet.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.2 |
||||||||||||||||||||||||||||||||||||||||
|
outletName
A descriptive name for the outlet.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.3 |
||||||||||||||||||||||||||||||||||||||||
|
outletParentCount
Number of parents for this outlet.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.4 |
||||||||||||||||||||||||||||||||||||||||
|
outletType
The physical type of outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.1.1.5 |
||||||||||||||||||||||||||||||||||||||||
|
outletDesignator
Alphanumeric physical name for the outlet.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.6 |
||||||||||||||||||||||||||||||||||||||||
|
outletPhaseID
Value indicates which phases are connected to each outlet in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, phase 3 to phase 1,… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.1.1.7 |
outletParentTable
table.1.3.6.1.4.1.534.6.6.7.6.2
·
1 row entry
·
3 columns
A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child.
An entry for a particular parent.
Indexes
strappingIndex outletIndex outletParentIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
outletParentIndex
A unique value for each parent. Its value ranges from 1 to outletParentCount.
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.534.6.6.7.6.2.1.1 |
||||||||
|
outletParentType
The type of the parent.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.2.1.2 |
||||||||
|
outletParentOID
Object ID of a parent object.
|
ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.6.2.1.3 |
outletVoltageTable
table.1.3.6.1.4.1.534.6.6.7.6.3
·
1 row entry
·
6 columns
A list of outlet voltage measurements.
An entry for an outlet voltage measurement.
Indexes
strappingIndex outletIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletVoltage
Units are millivolts.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.2 |
||||||||||
|
outletVoltageThStatus
Status of the measured outlet voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.3.1.3 |
||||||||||
|
outletVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.4 |
||||||||||
|
outletVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.5 |
||||||||||
|
outletVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.6 |
||||||||||
|
outletVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.7 |
outletCurrentTable
table.1.3.6.1.4.1.534.6.6.7.6.4
·
1 row entry
·
9 columns
A list of outlet current measurements.
An entry for an outlet current measurement.
Indexes
strappingIndex outletIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
outletCurrentCapacity
Rated current capacity of the outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.2 |
||||||||||
|
outletCurrent
An outlet current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.3 |
||||||||||
|
outletCurrentThStatus
Status of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.4.1.4 |
||||||||||
|
outletCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.5 |
||||||||||
|
outletCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.6 |
||||||||||
|
outletCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.7 |
||||||||||
|
outletCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.8 |
||||||||||
|
outletCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.9 |
||||||||||
|
outletCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.10 |
outletPowerTable
table.1.3.6.1.4.1.534.6.6.7.6.5
·
1 row entry
·
6 columns
A list of outlet power measurements.
An entry for an outlet power measurement.
Indexes
strappingIndex outletIndex
| Column | Syntax | OID |
|---|---|---|
|
outletVA
An outlet VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.2 |
|
outletWatts
An outlet Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.3 |
|
outletWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.4 |
|
outletWhTimer
Timestamp of when outlet Watt-hours (outletWh) was last reset.
|
UnixTimeStamp Textual Convention: UnixTimeStamp Unsigned32 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.5 |
|
outletPowerFactor
An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.6 |
|
outletVAR
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.7 |
outletControlTable
table.1.3.6.1.4.1.534.6.6.7.6.6
·
1 row entry
·
9 columns
A list of controllable outlets.
An entry for a controllable outlet.
Indexes
strappingIndex outletIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
outletControlStatus
Current state of a controlled outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.2 |
||||||||
|
outletControlOffCmd
Outlet control command.
Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet Off command … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.3 |
||||||||
|
outletControlOnCmd
Outlet control command.
Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet On command Wh… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.4 |
||||||||
|
outletControlRebootCmd
Outlet control command.
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.5 |
||||||||
|
outletControlPowerOnState
Determines the outlet state when power is applied to the unit.
0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.6 |
||||||||
|
outletControlSequenceDelay
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.7 |
||||||||
|
outletControlRebootOffTime
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
|
Integer32r/w Constraints: range: 1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.8 |
||||||||
|
outletControlSwitchable
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled 2 : control On/Off disabled. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.9 |
||||||||
|
outletControlShutoffDelay
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd. |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.10 |
outletGlobalTable
table.1.3.6.1.4.1.534.6.6.7.6.7
·
1 row entry
·
1 columns
A list of globlal configuration on all outlets.
An entry for a global variable on all outlets.
Indexes
strappingIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
outletAutomaticShutoff
Determines the state of all outlets when the unit is power off:
0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU is powered down 2 : Makes the outlet relays go to the positi… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.7.1.2 |
temperatureTable
table.1.3.6.1.4.1.534.6.6.7.7.1
·
1 row entry
·
9 columns
A list of temperature probe measurements. The number of entries is given by temperatureCount.
An entry for a temperature measurement.
Indexes
strappingIndex temperatureIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
temperatureIndex
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.1 |
||||||||||
|
temperatureName
A descriptive name for the temperature probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.2 |
||||||||||
|
temperatureProbeStatus
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.1.1.3 |
||||||||||
|
temperatureValue
Units are in tenths of a degree according to the scale specified by
temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. |
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.4 |
||||||||||
|
temperatureThStatus
Status of the measured temperature relative to the configured
thresholds. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.1.1.5 |
||||||||||
|
temperatureThLowerWarning
Lower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.6 |
||||||||||
|
temperatureThLowerCritical
Lower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.7 |
||||||||||
|
temperatureThUpperWarning
Upper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.8 |
||||||||||
|
temperatureThUpperCritical
Upper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.9 |
humidityTable
table.1.3.6.1.4.1.534.6.6.7.7.2
·
1 row entry
·
9 columns
A list of humidity probe measurements. The number of entries is given by humidityCount.
An entry for a humidity measurement.
Indexes
strappingIndex humidityIndex
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
humidityIndex
A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.1 |
||||||||||
|
humidityName
A descriptive name for the humidity probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.2 |
||||||||||
|
humidityProbeStatus
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.2.1.3 |
||||||||||
|
humidityValue
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
|
SNMPv2-SMIInteger32 Textual Convention: SNMPv2-SMIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.4 |
||||||||||
|
humidityThStatus
Status of the measured humidity relative to the configured
thresholds. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.2.1.5 |
||||||||||
|
humidityThLowerWarning
Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.6 |
||||||||||
|
humidityThLowerCritical
Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.7 |
||||||||||
|
humidityThUpperWarning
Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.8 |
||||||||||
|
humidityThUpperCritical
Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.9 |
contactTable
table.1.3.6.1.4.1.534.6.6.7.7.3
·
1 row entry
·
4 columns
A list of contact sensors. The number of entries is given by contactCount.
An entry for a contact sensor
Indexes
strappingIndex contactIndex
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
contactIndex
A unique value for each contact sensor. Its value ranges from 1 to
contactCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.534.6.6.7.7.3.1.1 |
||||||
|
contactName
A descriptive name for the contact sensor.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.3.1.2 |
||||||
|
contactProbeStatus
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.3.1.3 |
||||||
|
contactState
The state of the contact sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.3.1.4 |