EATON-EPDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
23
Rows
23
Columns
170
.1.3.6.1.4.1.534.6.6.7.1.2 · 1 row entry · 22 columns
A list of units.  In most cases this list will only contain one entry.
However, some units have a 'strapping' feature which allow units to be
daisy-chained together such that all of them can be accessed through
the SNMP interface of the master.  If strapping is enabled, the 
strapping indexes of the units that can be accessed will be listed in the
unitsPresent object.
unitEntry entry .1.3.6.1.4.1.534.6.6.7.1.2.1
An entry for a PDU.
Indexes
strappingIndex
Column Syntax OID
strappingIndex
For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will
always be '0'.
Integer32
Constraints:
range: 0-23
.1.3.6.1.4.1.534.6.6.7.1.2.1.1
productName
Name of the product.
OctetString
Constraints:
range: 1-127
.1.3.6.1.4.1.534.6.6.7.1.2.1.2
partNumber
Part number of the unit.
OctetString .1.3.6.1.4.1.534.6.6.7.1.2.1.3
serialNumber
Serial number of the unit.
OctetString .1.3.6.1.4.1.534.6.6.7.1.2.1.4
firmwareVersion
Firmware version.
OctetString .1.3.6.1.4.1.534.6.6.7.1.2.1.5
unitName
Descriptive name for the unit.
OctetStringr/w
Constraints:
range: 1-63
.1.3.6.1.4.1.534.6.6.7.1.2.1.6
lcdControl
Control the local LCD.
Enumerationr/w
Enumerated Values:
0notApplicable
1lcdScreenOff
2lcdKeyLock
3lcdScreenOffAndKeyLock
.1.3.6.1.4.1.534.6.6.7.1.2.1.7
clockValue
Clock value. This could be from either a real-time clock (in which case
it is likely writeable) or from a time server via NTP (probably read-only).
SNMPv2-TCDateAndTimer/w
Textual Convention: SNMPv2-TCDateAndTime OctetString
Type Constraints:
range: 8
range: 11
.1.3.6.1.4.1.534.6.6.7.1.2.1.8
temperatureScale
Scale used to return temperature objects.
Enumerationr/w
Enumerated Values:
0celsius
1fahrenheit
.1.3.6.1.4.1.534.6.6.7.1.2.1.9
unitType
Technical capabilities of the PDU. Functionality is as follows:
Monitored (MI) - input and usually section/group monitoring.
Advanced Monitored (AM) - input, section/group, and outlet monitoring.
Switched (SW) - input …
Enumeration
Enumerated Values:
0unknown
1switched
2advancedMonitored
3managed
4monitored
5basic
6inlineMonitored
.1.3.6.1.4.1.534.6.6.7.1.2.1.10
systemType
Architecture of the ePDU electronic.
Enumeration
Enumerated Values:
0unknown
1g3ePDU
2g3HDePDU
.1.3.6.1.4.1.534.6.6.7.1.2.1.11
inputCount
Number of inputs on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.20
groupCount
Number of groups on this ePDU. Groups include breakers, outlet sections,
and user-defined groups.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.21
outletCount
Number of outlets on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.22
temperatureCount
Max number of temperature measurements on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.23
humidityCount
Max number of humidity measurements on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.24
contactCount
Max number of contact sensors on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.25
communicationStatus
Status of the internal communication with the PDU.
Enumeration
Enumerated Values:
0good
1communicationLost
.1.3.6.1.4.1.534.6.6.7.1.2.1.30
internalStatus
Status of the internal failure inside the PDU.
Enumeration
Enumerated Values:
0good
1internalFailure
.1.3.6.1.4.1.534.6.6.7.1.2.1.31
strappingStatus
Status of the external communication with a strapping unit.
Enumeration
Enumerated Values:
0good
1communicationLost
.1.3.6.1.4.1.534.6.6.7.1.2.1.32
userName
Username used to log into the PDU.
OctetString
Constraints:
range: 0-31
.1.3.6.1.4.1.534.6.6.7.1.2.1.40
commInterface
Communications interface used to log into the PDU.
Enumeration
Enumerated Values:
0serial
1usb
2telnet
3web
4ftp
5xml
.1.3.6.1.4.1.534.6.6.7.1.2.1.41
.1.3.6.1.4.1.534.6.6.7.1.3 · 1 row entry · 2 columns
A list of units that have controllable outlets.
unitControlEntry entry .1.3.6.1.4.1.534.6.6.7.1.3.1
An entry for a PDU which has controllable outlets.
Indexes
strappingIndex
Column Syntax OID
unitControlOffCmd
Unit-level outlet control command.

Once the command is issued, outlets will turn Off.
0-n : Time in seconds until the outlet Sequence Off command is issued
-1 : Cancel a pending unit-level Off command
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.1.3.1.2
unitControlOnCmd
Unit-level outlet control command.

Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value.
0-n : Time in seconds until the outlet Sequence On command is issue…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.1.3.1.3
.1.3.6.1.4.1.534.6.6.7.3.1 · 1 row entry · 10 columns
List of inputs to the PDU.
inputEntry entry .1.3.6.1.4.1.534.6.6.7.3.1.1
An entry for a particular input.
Indexes
strappingIndex inputIndex
Column Syntax OID
inputIndex
A unique value for each input. Its value ranges from 1 to inputCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.3.1.1.1
inputType
Type of input - single phase, split phase, three phase delta, or three
phase wye.
Enumeration
Enumerated Values:
1singlePhase
2splitPhase
3threePhaseDelta
4threePhaseWye
.1.3.6.1.4.1.534.6.6.7.3.1.1.2
inputFrequency
Units are 0.1 Hz; divide by ten to get Hz.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.3
inputFrequencyStatus
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
Enumeration
Enumerated Values:
0good
1outOfRange
.1.3.6.1.4.1.534.6.6.7.3.1.1.4
inputVoltageCount
Number of input voltage measurements on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.5
inputCurrentCount
Number of input current measurements on this ePDU.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.6
inputPowerCount
Number of rows in the inputPowerTable.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.7
inputPlugType
Identifies which plug is on the input.
Enumeration
Enumerated Values:
100other1Phase
101iecC14Inlet
102iecC20Inlet
103iec316P6
104iec332P6
105iec363P6
106iecC14Plug
107iecC20Plug
120nema515
121nemaL515
122nema520
123nemaL520
124nema615
125nemaL615
126nemaL530
127nema620
128nemaL620
129nemaL630
130cs8265
131nemaL2530
140other208V2P3W
141other230V1P3W
150french
151schuko
152uk
160field208V2P3W
161field230V1P3W
200other2Phase
201nemaL1420
202nemaL1430
300other3Phase
301iec516P6
302iec460P9
303iec560P9
304iec532P6
306iec563P6
307iec4100P9
320nemaL1520
321nemaL2120
322nemaL1530
323nemaL2130
324cs8365
325nemaL2220
326nemaL2230
327nemaL2630
340other208V3P4W
341other208V3P5W
342other400V3P5W
343other480V3P5W
350bladeUps208V
351bladeUps400V
360field208V3P4W
361field400V3P5W
400universalUTP8pin
.1.3.6.1.4.1.534.6.6.7.3.1.1.8
inputFeedColor
Color code of the input feed.
Unsigned32r/w
Constraints:
range: 0-16777215
.1.3.6.1.4.1.534.6.6.7.3.1.1.9
inputFeedName
A descriptive name for the input.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.3.1.1.10
.1.3.6.1.4.1.534.6.6.7.3.2 · 1 row entry · 8 columns
A list of input voltage measurements.  The number of entries
is given by inputVoltageCount.
inputVoltageEntry entry .1.3.6.1.4.1.534.6.6.7.3.2.1
An entry for a particular input voltage measurement.
Indexes
strappingIndex inputIndex inputVoltageIndex
Column Syntax OID
inputVoltageIndex
A unique value for each input voltage measurement. Its value ranges
from 1 to inputVoltageCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.6.7.3.2.1.1
inputVoltageMeasType
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.534.6.6.7.3.2.1.2
inputVoltage
An input voltage measurement value. Units are millivolts.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.2.1.3
inputVoltageThStatus
Status of the measured input voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.3.2.1.4
inputVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.5
inputVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.6
inputVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.7
inputVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.8
.1.3.6.1.4.1.534.6.6.7.3.3 · 1 row entry · 12 columns
A list of input current measurements.  The number of entries
is given by inputCurrentCount.
inputCurrentEntry entry .1.3.6.1.4.1.534.6.6.7.3.3.1
An entry for a particular input current measurement.
Indexes
strappingIndex inputIndex inputCurrentIndex
Column Syntax OID
inputCurrentIndex
A unique value for each input current measurement. Its value ranges
from 1 to inputCurrentCount.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.534.6.6.7.3.3.1.1
inputCurrentMeasType
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.534.6.6.7.3.3.1.2
inputCurrentCapacity
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.3
inputCurrent
An input current measurement value. Units are milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.4
inputCurrentThStatus
Status of the measured input current relative to the configured thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.3.3.1.5
inputCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.6
inputCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.7
inputCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.8
inputCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.9
inputCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.10
inputCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.11
inputPhaseDesignator
Alphanumeric physical name for the input.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.3.3.1.12
.1.3.6.1.4.1.534.6.6.7.3.4 · 1 row entry · 8 columns
A list of input power measurements.  The number of entries
is given by inputPowerCount.
inputPowerEntry entry .1.3.6.1.4.1.534.6.6.7.3.4.1
An entry for an input power measurement.
Indexes
strappingIndex inputIndex inputPowerIndex
Column Syntax OID
inputPowerIndex
A unique value for each input power measurement. Its value ranges
from 1 to inputPowerCount.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.534.6.6.7.3.4.1.1
inputPowerMeasType
Value indicates what is being measured in this table row.
Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4total
.1.3.6.1.4.1.534.6.6.7.3.4.1.2
inputVA
An input VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.3
inputWatts
An input Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.4
inputWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.3.4.1.5
inputWhTimer
Timestamp of when input Watt-hours (inputWh) was last reset.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.6.7.3.4.1.6
inputPowerFactor
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.7
inputVAR
An input VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.8
.1.3.6.1.4.1.534.6.6.7.3.5 · 1 row entry · 7 columns
A list of total input power measurements.
inputTotalPowerEntry entry .1.3.6.1.4.1.534.6.6.7.3.5.1
An entry for a total input power measurement.
Indexes
strappingIndex inputIndex
Column Syntax OID
inputTotalVA
An input VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.3
inputTotalWatts
An input Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.4
inputTotalWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.3.5.1.5
inputTotalWhTimer
Timestamp of when input Watt-hours (inputWh) was last reset.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.6.7.3.5.1.6
inputTotalPowerFactor
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.7
inputTotalVAR
An input VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.8
inputPowerCapacity
Typical power capacity of the input. A negative value indicates that
the hardware current capacity is unknown.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.9
.1.3.6.1.4.1.534.6.6.7.5.1 · 1 row entry · 9 columns
A list of groups.  The number of entries is given by groupCount.
groupEntry entry .1.3.6.1.4.1.534.6.6.7.5.1.1
An entry for a particular group.
Indexes
strappingIndex groupIndex
Column Syntax OID
groupIndex
A unique value for each group. Its value ranges from 1 to groupCount.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.6.6.7.5.1.1.1
groupID
Alphanumeric designator for the group. This value may be written
on the face of the unit.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.5.1.1.2
groupName
A descriptive name for the group.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.5.1.1.3
groupType
The type of the group.
Enumeration
Enumerated Values:
0unknown
1breaker1pole
2breaker2pole
3breaker3pole
4outletSection
5userDefined
.1.3.6.1.4.1.534.6.6.7.5.1.1.4
groupBreakerStatus
Only applicable to breaker-groups. Indicates whether a breaker is turned
off or on.
Enumeration
Enumerated Values:
0notApplicable
1breakerOn
2breakerOff
.1.3.6.1.4.1.534.6.6.7.5.1.1.5
groupChildCount
Number of children for this group.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.1.1.6
groupColor
Background color code of the group. Color codes are decimal values.
Unsigned32
Constraints:
range: 0-16777215
.1.3.6.1.4.1.534.6.6.7.5.1.1.7
groupDesignator
Alphanumeric physical name for the group. This value may be written
on the face of the unit.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.5.1.1.8
groupInputIndex
Identifies the input on which the group is connected.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.1.1.9
.1.3.6.1.4.1.534.6.6.7.5.2 · 1 row entry · 3 columns
A list of children for this group.  For example, this table will link
to all of the outlets that are contained in a particular group.
groupChildEntry entry .1.3.6.1.4.1.534.6.6.7.5.2.1
An entry for a particular child.
Indexes
strappingIndex groupIndex groupChildIndex
Column Syntax OID
groupChildIndex
A unique value for each child. Its value ranges from 1 to groupChildCount.
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.534.6.6.7.5.2.1.1
groupChildType
The type of the child.
Enumeration
Enumerated Values:
0unknown
2section
3custom
4outlet
.1.3.6.1.4.1.534.6.6.7.5.2.1.2
groupChildOID
Object ID of a child object.
ObjectIdentifier .1.3.6.1.4.1.534.6.6.7.5.2.1.3
.1.3.6.1.4.1.534.6.6.7.5.3 · 1 row entry · 7 columns
A list of group voltage measurements.  There can be only one voltage
measurement for each group.
groupVoltageEntry entry .1.3.6.1.4.1.534.6.6.7.5.3.1
An entry for a group voltage measurement.
Indexes
strappingIndex groupIndex
Column Syntax OID
groupVoltageMeasType
Value indicates what voltage is being measured in this table row.
Enumeration
Enumerated Values:
0unknown
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.534.6.6.7.5.3.1.2
groupVoltage
Units are millivolts.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.3.1.3
groupVoltageThStatus
Status of the measured group voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.5.3.1.4
groupVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.5
groupVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.6
groupVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.7
groupVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.8
.1.3.6.1.4.1.534.6.6.7.5.4 · 1 row entry · 9 columns
A list of group current measurements.  There can be only one current
measurement for each group.
groupCurrentEntry entry .1.3.6.1.4.1.534.6.6.7.5.4.1
An entry for a group current measurement.
Indexes
strappingIndex groupIndex
Column Syntax OID
groupCurrentCapacity
Rated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it
will always be unknown for custom groups).
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.2
groupCurrent
A group current measurement value. Units are milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.3
groupCurrentThStatus
Status of the measured group current relative to the configured thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.5.4.1.4
groupCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.5
groupCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.6
groupCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.7
groupCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.8
groupCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.9
groupCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.10
.1.3.6.1.4.1.534.6.6.7.5.5 · 1 row entry · 6 columns
A list of group power measurements.  There can be only one power
measurement for each group.
groupPowerEntry entry .1.3.6.1.4.1.534.6.6.7.5.5.1
An entry for a group power measurement.
Indexes
strappingIndex groupIndex
Column Syntax OID
groupVA
A group VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.2
groupWatts
A group Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.3
groupWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.5.5.1.4
groupWhTimer
Timestamp of when group Watt-hours (groupWh) was last reset.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.6.7.5.5.1.5
groupPowerFactor
A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.6
groupVAR
A group VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.7
.1.3.6.1.4.1.534.6.6.7.5.6 · 1 row entry · 4 columns
A list of controllable groups.
groupControlEntry entry .1.3.6.1.4.1.534.6.6.7.5.6.1
An entry for a controllable group.
Indexes
strappingIndex groupIndex
Column Syntax OID
groupControlStatus
Current state of a controlled group. A value of 'mixed' means that
that the outlets within the group have differing states.
Enumeration
Enumerated Values:
0off
1on
2rebooting
3mixed
.1.3.6.1.4.1.534.6.6.7.5.6.1.2
groupControlOffCmd
Group-level outlet control command.

Once the command is issued, the outlets in the group will turn Off immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-leve…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.5.6.1.3
groupControlOnCmd
Group-level outlet control command.

Once the command is issued, the outlets in the group will turn On immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-level…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.5.6.1.4
groupControlRebootCmd
Group-level outlet control command.

For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and…
Integer32r/w
Constraints:
range: -1-0
.1.3.6.1.4.1.534.6.6.7.5.6.1.5
.1.3.6.1.4.1.534.6.6.7.6.1 · 1 row entry · 7 columns
A list of outlets.  The number of entries is given by outletCount.
outletEntry entry .1.3.6.1.4.1.534.6.6.7.6.1.1
An entry for a particular outlet.
Indexes
strappingIndex outletIndex
Column Syntax OID
outletIndex
A unique value for each outlet. its value ranges from 1 to outletCount.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.6.6.7.6.1.1.1
outletID
Alphanumeric designator for the outlet.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.6.1.1.2
outletName
A descriptive name for the outlet.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.6.1.1.3
outletParentCount
Number of parents for this outlet.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.1.1.4
outletType
The physical type of outlet.
Enumeration
Enumerated Values:
0unknown
1iecC13
2iecC19
3comboC39
10uk
11french
12schuko
20nema515
21nema51520
22nema520
23nemaL520
24nemaL530
25nema615
26nema620
27nemaL620
28nemaL630
29nemaL715
30rf203p277
31sdg300
32sdg400
.1.3.6.1.4.1.534.6.6.7.6.1.1.5
outletDesignator
Alphanumeric physical name for the outlet.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.6.1.1.6
outletPhaseID
Value indicates which phases are connected to each outlet in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, phase 3 to phase 1,…
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
8phase12N
9phase23N
10phase31N
11phase123
12phase123N
.1.3.6.1.4.1.534.6.6.7.6.1.1.7
.1.3.6.1.4.1.534.6.6.7.6.2 · 1 row entry · 3 columns
A list of parents for this outlet.  For example, this table will link
to all of the groups that have this outlet as a child.
outletParentEntry entry .1.3.6.1.4.1.534.6.6.7.6.2.1
An entry for a particular parent.
Indexes
strappingIndex outletIndex outletParentIndex
Column Syntax OID
outletParentIndex
A unique value for each parent. Its value ranges from 1 to outletParentCount.
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.534.6.6.7.6.2.1.1
outletParentType
The type of the parent.
Enumeration
Enumerated Values:
0unknown
1breaker
2section
3custom
.1.3.6.1.4.1.534.6.6.7.6.2.1.2
outletParentOID
Object ID of a parent object.
ObjectIdentifier .1.3.6.1.4.1.534.6.6.7.6.2.1.3
.1.3.6.1.4.1.534.6.6.7.6.3 · 1 row entry · 6 columns
A list of outlet voltage measurements.
outletVoltageEntry entry .1.3.6.1.4.1.534.6.6.7.6.3.1
An entry for an outlet voltage measurement.
Indexes
strappingIndex outletIndex
Column Syntax OID
outletVoltage
Units are millivolts.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.3.1.2
outletVoltageThStatus
Status of the measured outlet voltage relative to the configured thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.6.3.1.3
outletVoltageThLowerWarning
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.4
outletVoltageThLowerCritical
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.5
outletVoltageThUpperWarning
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.6
outletVoltageThUpperCritical
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.7
.1.3.6.1.4.1.534.6.6.7.6.4 · 1 row entry · 9 columns
A list of outlet current measurements.
outletCurrentEntry entry .1.3.6.1.4.1.534.6.6.7.6.4.1
An entry for an outlet current measurement.
Indexes
strappingIndex outletIndex
Column Syntax OID
outletCurrentCapacity
Rated current capacity of the outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.2
outletCurrent
An outlet current measurement value. Units are milliamps.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.3
outletCurrentThStatus
Status of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.6.4.1.4
outletCurrentThLowerWarning
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.5
outletCurrentThLowerCritical
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.6
outletCurrentThUpperWarning
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.7
outletCurrentThUpperCritical
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.8
outletCurrentCrestFactor
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.9
outletCurrentPercentLoad
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.10
.1.3.6.1.4.1.534.6.6.7.6.5 · 1 row entry · 6 columns
A list of outlet power measurements.
outletPowerEntry entry .1.3.6.1.4.1.534.6.6.7.6.5.1
An entry for an outlet power measurement.
Indexes
strappingIndex outletIndex
Column Syntax OID
outletVA
An outlet VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.2
outletWatts
An outlet Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.3
outletWh
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.6.5.1.4
outletWhTimer
Timestamp of when outlet Watt-hours (outletWh) was last reset.
UnixTimeStamp
Textual Convention: UnixTimeStamp Unsigned32
.1.3.6.1.4.1.534.6.6.7.6.5.1.5
outletPowerFactor
An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.6
outletVAR
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.7
.1.3.6.1.4.1.534.6.6.7.6.6 · 1 row entry · 9 columns
A list of controllable outlets.
outletControlEntry entry .1.3.6.1.4.1.534.6.6.7.6.6.1
An entry for a controllable outlet.
Indexes
strappingIndex outletIndex
Column Syntax OID
outletControlStatus
Current state of a controlled outlet.
Enumeration
Enumerated Values:
0off
1on
2pendingOff
3pendingOn
.1.3.6.1.4.1.534.6.6.7.6.6.1.2
outletControlOffCmd
Outlet control command.

Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet Off command

Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.3
outletControlOnCmd
Outlet control command.

Once the command is issued, the outlet will turn On immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet On command

Wh…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.4
outletControlRebootCmd
Outlet control command.

For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.5
outletControlPowerOnState
Determines the outlet state when power is applied to the unit.
0 : not restart at device startup
1 : should sequence back ON in line with outletControlSequenceTime
2 : should take the state the outlet had when power was…
Enumerationr/w
Enumerated Values:
0off
1on
2lastState
.1.3.6.1.4.1.534.6.6.7.6.6.1.6
outletControlSequenceDelay
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to exclude this outlet from Global Sequence …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.7
outletControlRebootOffTime
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
Integer32r/w
Constraints:
range: 1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.8
outletControlSwitchable
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled.
Enumerationr/w
Enumerated Values:
1switchable
2notSwitchable
.1.3.6.1.4.1.534.6.6.7.6.6.1.9
outletControlShutoffDelay
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then write it to the command outletControlOffCmd.
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.10
.1.3.6.1.4.1.534.6.6.7.6.7 · 1 row entry · 1 columns
A list of globlal configuration on all outlets.
outletGlobalEntry entry .1.3.6.1.4.1.534.6.6.7.6.7.1
An entry for a global variable on all outlets.
Indexes
strappingIndex
Column Syntax OID
outletAutomaticShutoff
Determines the state of all outlets when the unit is power off:
0 : not applicable (read only)
1 : Keep the outlet relays in the current position when the PDU is powered down
2 : Makes the outlet relays go to the positi…
Enumerationr/w
Enumerated Values:
0notApplicable
1keepTheCurrentPosition
2shutoffTheOutlets
.1.3.6.1.4.1.534.6.6.7.6.7.1.2
.1.3.6.1.4.1.534.6.6.7.7.1 · 1 row entry · 9 columns
A list of temperature probe measurements.  The number of entries is
given by temperatureCount.
temperatureEntry entry .1.3.6.1.4.1.534.6.6.7.7.1.1
An entry for a temperature measurement.
Indexes
strappingIndex temperatureIndex
Column Syntax OID
temperatureIndex
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.7.1.1.1
temperatureName
A descriptive name for the temperature probe.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.1.1.2
temperatureProbeStatus
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.1.1.3
temperatureValue
Units are in tenths of a degree according to the scale specified by
temperatureScale (either Fahrenheit or Celsius). Divide by ten to get
degrees.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.7.1.1.4
temperatureThStatus
Status of the measured temperature relative to the configured
thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.7.1.1.5
temperatureThLowerWarning
Lower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.6
temperatureThLowerCritical
Lower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.7
temperatureThUpperWarning
Upper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.8
temperatureThUpperCritical
Upper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.9
.1.3.6.1.4.1.534.6.6.7.7.2 · 1 row entry · 9 columns
A list of humidity probe measurements.  The number of entries is
given by humidityCount.
humidityEntry entry .1.3.6.1.4.1.534.6.6.7.7.2.1
An entry for a humidity measurement.
Indexes
strappingIndex humidityIndex
Column Syntax OID
humidityIndex
A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.7.2.1.1
humidityName
A descriptive name for the humidity probe.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.2.1.2
humidityProbeStatus
Indicates whether a probe is connected or not.
Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.2.1.3
humidityValue
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
SNMPv2-SMIInteger32
Textual Convention: SNMPv2-SMIInteger32 Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.7.2.1.4
humidityThStatus
Status of the measured humidity relative to the configured
thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.7.2.1.5
humidityThLowerWarning
Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.6
humidityThLowerCritical
Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.7
humidityThUpperWarning
Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.8
humidityThUpperCritical
Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.9
.1.3.6.1.4.1.534.6.6.7.7.3 · 1 row entry · 4 columns
A list of contact sensors.  The number of entries is
given by contactCount.
contactEntry entry .1.3.6.1.4.1.534.6.6.7.7.3.1
An entry for a contact sensor
Indexes
strappingIndex contactIndex
Column Syntax OID
contactIndex
A unique value for each contact sensor. Its value ranges from 1 to
contactCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.6.7.7.3.1.1
contactName
A descriptive name for the contact sensor.
OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.3.1.2
contactProbeStatus
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU,
in that case only contactState should be read.
Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.3.1.3
contactState
The state of the contact sensor.
Enumeration
Enumerated Values:
-1contactBad
0contactOpen
1contactClosed
.1.3.6.1.4.1.534.6.6.7.7.3.1.4