outletControlRebootCmd

EATON-EPDU-MIB · .1.3.6.1.4.1.534.6.6.7.6.6.1.5

Object

column r/w Integer32
Outlet control command.
              
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn back On.
For outlets that are Off prior to the Reboot command, they will turn On after a delay of outletControlRebootOffTime
seconds from when the command is issued.
0-n : Time in seconds until the Reboot command is issued
-1 : Cancel a pending outlet Reboot command 
              
When read, returns -1 if no command is pending, or the current downcount in seconds of a pending command.
              
Certain ePDUs (mainly those with part numbers beginning with IPV or IPC) do not support delayed control
commands.  These will respond with an error if a command value of > 0 is written to this object.

Context

MIB
EATON-EPDU-MIB
OID
.1.3.6.1.4.1.534.6.6.7.6.6.1.5
Type
column
Access
readwrite
Status
current
Parent
outletControlEntry
Table
outletControlTable
Siblings
8

Syntax

Integer32

Values & Constraints

Object Constraints
range: -1-99999

Related Objects

Sibling Objects