inputCurrentCrestFactor
EATON-EPDU-MIB ·
.1.3.6.1.4.1.534.6.6.7.3.3.1.10
Object
column
SNMPv2-SMIInteger32
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
Context
- MIB
- EATON-EPDU-MIB
- OID
.1.3.6.1.4.1.534.6.6.7.3.3.1.10- Type
- column
- Access
- readonly
- Status
- current
- Parent
- inputCurrentEntry
- Table
- inputCurrentTable
- Siblings
- 11
Syntax
SNMPv2-SMIInteger32
- Source
- SNMPv2-SMIInteger32
- Base type
Integer32
Values & Constraints
Type Constraints
range: -2147483648..2147483647
Related Objects
Sibling Objects
| Object | Type | Syntax | OID |
|---|---|---|---|
| inputCurrentIndex A unique value for each input current measurement. Its value ranges
from 1 to inputCurrentCount. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.1 |
| inputCurrentPercentLoad Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not avail… | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.11 |
| inputPhaseDesignator Alphanumeric physical name for the input. | column | OctetString | .1.3.6.1.4.1.534.6.6.7.3.3.1.12 |
| inputCurrentMeasType Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.3.3.1.2 |
| inputCurrentCapacity Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.3 |
| inputCurrent An input current measurement value. Units are milliamps. | column | SNMPv2-SMIInteger32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.4 |
| inputCurrentThStatus Status of the measured input current relative to the configured thresholds. | column | Enumeration | .1.3.6.1.4.1.534.6.6.7.3.3.1.5 |
| inputCurrentThLowerWarning Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.6 |
| inputCurrentThLowerCritical Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.7 |
| inputCurrentThUpperWarning Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.8 |
| inputCurrentThUpperCritical Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. | column | Integer32 | .1.3.6.1.4.1.534.6.6.7.3.3.1.9 |